Cummins/Onan — Disconnecting Generator Set Systems (Set Removal)

Repair & overhaul

From a Cummins/Onan service manual — check it applies to your exact model before use.

Applies to: Cummins/Onan HDKA, Cummins/Onan HDKAQ, Cummins/Onan HDKAR

Before you start

  • Generator set is heavy; use adequate lifting devices and keep hands and feet clear.
  • Leakage of fuel presents a fire or explosion hazard; plug all fuel line openings and keep an ABC fire extinguisher nearby.

Procedure

  1. Disconnect the generator set negative (-) battery cable at the battery terminal.
  2. Disconnect the generator set positive (+) battery cable from the starter solenoid.
  3. Disconnect the remote control plug wire from the generator set (if applicable).
  4. Disconnect the generator set load wires; tag for identification when reconnecting.
  5. Disconnect the exhaust system and support brackets or hangers to allow set removal.
  6. Disconnect the fuel line at the generator set fuel pump; securely plug the fuel line end.
  7. Verify the set is adequately supported before loosening any mounting bolts or supports.

Tools required

  • Adequate lifting devices Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Full service-parts list: Cummins/Onan HDKA →, Cummins/Onan HDKAQ →, Cummins/Onan HDKAR →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.