The Cummins/Onan KTTA50 is an engine. It powers generator sets from Cummins/Onan, including the DFLC and DFLE. It holds 169 L (44.6 gal) of oil and 386 L (102.0 gal) of coolant.
Also known as: Cummins KTTA50
Part of the Cummins/Onan KTTA50 engine family — 3 variants share parts & fitment.
| Oil capacity | 169.0 L |
|---|---|
| Coolant capacity | 386.0 L |
How to read your Cummins/Onan engine serial & model number →
Compiled from service & troubleshooting documentation across every generator set that uses the Cummins/Onan KTTA50.
Step-by-step procedures compiled from the Cummins/Onan service manual for this engine.
| Item | Action | Hours | Months | Notes |
|---|---|---|---|---|
| crankcase oil | Change | 50 hr | First service — Drain and replace the crankcase oil after the first 50 hours of operation on new generator sets (break-in) | |
| Check Electrolyte Level (batteries) | Check | 200 hr | At least every 200 hours of operation | |
| Change Crankcase Oil and Filter | Change | 250 hr | 12 mo | If used for standby applications, change oil every 12 months or 250 hours, whichever comes first (footnote X6) |
| Crankcase oil and filter | Change | 250 hr | 12 mo | Standby applications: change oil every 12 months or 250 hours, whichever comes first |
| Grease generator bearing (P7) | Lubricate | 4000 hr | Table 5-2 explicit interval; grease type Kluber ASONIC GHY72, 75 grams | |
| Generator bearing (P7 only) | Lubricate | 4500 hr | Re-lubrication period 4000-4500 hours; 75 grams Kluber ASONIC GHY72 | |
| Exercise generator set | Test | 1 mo | At least once a month for a minimum of 30 minutes, under not less than 30 percent of nameplate rating | |
| Rupture basin leak detect switch | Test | 12 mo | Some areas may require weekly inspections by safety code. |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Type | Item | Value | Unit | Condition |
|---|---|---|---|---|
| Clearance | Air cleaner nozzle distance from element | at least 1 (25) | inch (mm) | |
| Clearance | Angular alignment maximum T.I.R. | 0.001 | inch per inch of radius (center of shaft to indicator axis) | measuring deflection to bolt heads |
| Clearance | Float switch assembly float lift clearance below C-clip stop | 1/8 | inch (3 mm) | use a feeler gauge |
| Clearance | Generator-to-engine angular alignment (T.I.R.) | .001 in. per inch of radius (center of shaft to indicator axis), maximum | in | 750 kW gensets and larger |
| Clearance | MPU sensor to gear tooth adjustment | back out one quarter turn | turn | after contacting gear tooth |
| Gap | Float switch lift to test open | 1/8 | inch | below C-clip stop |
| Gap | MPU sensor to flywheel ring gear tooth | back it out one quarter turn | turn | sensor threaded in until it just touches gear tooth |
| Other | AVR Droop setting | 5 | % at full load, 0 PF | |
| Other | AVR voltage regulation (load regulation) | approximately ±0.5 | % RMS | |
| Other | Air cleaner element cleaning air pressure | 30 (207) | psi (kPa) | low pressure compressed air through element from clean side |
| Other | Angular alignment maximum T.I.R. | .001 inches per inch of radius | in/in | center of shaft to indicator axis |
| Other | B+ output fuse | 10 | amp | F1, Base board, 12/24 volt |
| Other | Battery charging current | 45 | Amps | |
| Other | Battery electrolyte specific gravity | 1.260 | at 80°F | |
| Other | Battery specific gravity (high ambient, above 95F/35C) | 1.225 | recommended to reduce electrolyte loss | |
| Other | Battery specific gravity (recharge threshold) | below 1.260 | ||
| Other | Battery specific gravity - charge threshold (below this, charge battery) | 1.215 | ||
| Other | Battery specific gravity - fully charged (corrected) | 1.260 | ||
| Other | Battery specific gravity, fully charged | approximately 1.260 | specific gravity | at 80 F (27 C) |
| Other | Continuous crank without cycle cranking option (PCC) | up to 75 | seconds | |
| Other | Customer Output relay contact rating | 2 | amps at 30 VDC | TB1 customer outputs 1-4, normally open |
| Other | Fuel lift height limit | 6 | feet | (1.8 meters) between fuel lift pump and bottom of dip tube |
| Other | GOV GAIN default value for paralleling applications | 70 | % | |
| Other | Ground Fault Relay current setting | 5 to 1200 | amperes | optional GFR |
| Other | Ground Fault Relay time delay setting | 0 to 1 | second | optional GFR |
| Other | Low oil pressure / high engine temperature fault time delay after starter disconnect | about 10 | seconds | |
| Other | Maximum cranking voltage drop | 2 | volts | difference between battery and starter terminals while cranking |
| Other | Optional control relay (K11/K12/K13) contact rating | 10 | amps at 600 VAC | |
| Other | Output frequency adjustment range | +/- 5 | % | set running, not in idle mode |
| Other | Over/Under Frequency Sensor Module - Over Hz Set, 50 Hz nominal | 55 | Hz | reset 53 Hz |
| Other | Over/Under Frequency Sensor Module - Over Hz Set, 60 Hz nominal | 65 | Hz | reset 63 Hz |
| Other | Over/Under Frequency Sensor Module - Under Hz Set, 50 Hz nominal | 45 | Hz | reset 47 Hz |
| Other | Over/Under Frequency Sensor Module - Under Hz Set, 60 Hz nominal | 55 | Hz | reset 57 Hz |
| Other | Over/Under Voltage Sensor Module time delay | typically 25 percent, approximately 2.5 | seconds | |
| Other | Overcrank cranking limit | 75 | seconds | three 15-second cranking cycles with two 15-second rest periods |
| Other | Overcrank cranking limit (standard control) | 75 | seconds | |
| Other | Overcrank cycle cranking (Detector, standard) | three 15-second cranking cycles with two 15-second rest periods | seconds | |
| Other | Overcrank cycle cranking (PCC) | 3, 4, or 5 cycles; crank and rest times 7 to 20 | seconds | |
| Other | Overcrank cycling option | three 15-second cranking cycles with two 15-second rest periods | 12-lamp control | |
| Other | Overcrank limit (Detector, optional) | 75 | seconds | |
| Other | REG VHZ (underfrequency roll-off) adjustable range | 1 through 50; normal range 7 through 21 | ||
| Other | Start delay (PCC, remote start in Auto) | 0 to 300 | seconds | |
| Other | Start delay adjustment range | 0 to 300 | seconds | |
| Other | Stop delay (PCC, remote stop in Auto) | 0 to 600 | seconds | |
| Other | Stop delay adjustment range | 0 to 600 | seconds | |
| Other | Switched B+ output fuse | 5 | amp | F2, Base board, 12/24 volt |
| Other | Under Frequency Roll Off (UFRO) knee point, 50 Hz units | 48 to 49 | Hz | |
| Other | Under Frequency Roll Off (UFRO) knee point, 60 Hz units | 58 to 59 | Hz | |
| Other | Under-frequency roll-off threshold (UFRO) | typically 59 Hz for 60 Hz applications and 49 Hz for 50 Hz applications | Hz | AVR UFRO pot preset |
| Pressure | Air cleaner element cleaning, compressed air pressure | 30 | psi (207 kPa) | blow through element from clean side; nozzle at least 1 inch (25 mm) away |
| Pressure | Detector oil pressure normal range after reset | 25 to 40 | psi (172 to 275 kPa) | |
| Pressure | Engine oil pressure - K19 normal | 50-70 | psi (345-482 kPa) | run mode |
| Pressure | Engine oil pressure - K38 normal | 45-65 | psi (310-448 kPa) | run mode |
| Pressure | Engine oil pressure - K50 normal | 50-70 | psi (345-482 kPa) | run mode |
| Pressure | Engine oil pressure - L10/M11 normal | 30-50 | psi (207-345 kPa) | run mode |
| Pressure | Engine oil pressure - NTA 855 normal | 35-50 | psi (241-345 kPa) | run mode |
| Pressure | Engine oil pressure - V28 normal | 50-90 | psi (345-620 kPa) | run mode |
| Pressure | Engine oil pressure shutdown limit - L10/M11 | 20 | psi (138 kPa) | run mode value |
| Pressure | Engine oil pressure shutdown limit - L10/M11 | 8 | psi (55 kPa) | idle mode value |
| Pressure | Engine oil pressure warning limit - L10/M11 | 12 | psi (83 kPa) | idle mode value |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Fluid | Grade | Standard | Ambient | Capacity | Notes |
|---|---|---|---|---|---|
| Coolant | soft water / E.G. / DCA mixture | Cooling system to be filled with soft water/E.G./DCA mixture (on-site review checklist). | |||
| Coolant | water/antifreeze mixture (permanent type antifreeze) | Clean, low mineral content water free of chloride, sulphate or acid | Mix water and antifreeze per supplier recommendation for lowest expected ambient temperature; do not use antifreeze containing anti-leak additives | ||
| Engine oil | SAE 5W synthetic | API class CC/CD; sulphated ash content not exceeding 1.85 percent; pour point 9°F (5°C) below lowest expected temperature; viscosity 10,000 mPa.s maximum at -31°F (-35°C) and 4.1 mm2/s minimum at 212°F (100°C) | above -25°C | Recommended when ambient temperature is consistently below -13°F (-25°C) and there is no provision to keep the engine warm; do not use petroleum base 5W grade oil | |
| Engine oil | multigrade / multiviscosity | API Class CC/CD; maximum sulphated ash content 1.85 percent | -25°C to 35°C | Specifications section lists ambient ranges -13°F to 95°F (-25°C to 35°C), 14°F (-10°C) and above, and 32°F (0°C) and above; single grade oil not recommended; do not mix oils of another classification or brand | |
| Fuel | ASTM No. 2 diesel | ASTM | Alternate diesel fuels per Cummins engine O&M Manual specifications | ||
| Fuel | Diesel | Day tank fuel transfer pump maintains reservoir of diesel fuel in the day tank. | |||
| Fuel | No. 2 diesel | Engine will also operate on No. 1 fuel or other similar fuels if they meet certain specifications | |||
| Grease | Kluber, type ASONIC GHY72 | 75.0 grams | P7 generator bearing re-lubrication grease fill quantity; fill period 4000-4500 hours. Must not be mixed with any other type. | ||
| Grease | Lithium based grease | Mobilux No. 2 or Shell Alvania R3 | 2.74 oz (81 ml) | Generator end bearing. Temperature range -22F to +248F (-30C to +120C). Grease should be equally divided between the bearing, bearing cap cavity, and bearing cartridge cavity. | |
| Grease | Lithium based | -30°C to 120°C | 81.0 ml | Mobilux No. 2 or Shell Alvania R3; generator end bearing; temperature range -22 F to +248 F (-30 C to +120 C); grease divided between bearing, bearing cap cavity and cartridge cavity. | |
| Grease | Lithium based grease, Mobilux No. 2 or Shell Alvania R3 | -30°C to 120°C | 2.74 oz (81 ml) | End bearing lubricant; grease equally divided between bearing, bearing cap cavity and bearing cartridge cavity. | |
| Other | Donaldsons D1400 solvent (or equivalent) | Air cleaner element cleaning: soak filter at least 15 minutes in water and Donaldsons D1400 solvent. |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Code | Name | Meaning | Severity | Action |
|---|---|---|---|---|
| 101 | IDLE MODE | Indicates that the engine is operating in idle mode. Grounding the engine idle input causes generator build-up to be inhibited and the engine to be governed at 800 RPM. | Warning | Remove ground from engine idle input to return to normal speed and voltage. |
| 102 | EMERGENCY STOP | Local or remote Emergency Stop activated | Shutdown | Turn the switch clockwise and allow it to pop out (local only); move the Run/Off/Auto switch to Off; press the Reset switch; select Run or Auto as required. Can be reset only at the PCC front panel. |
| 1122 | Rated/Idle Trans | Info | ||
| 1123 | Shutdown After Battle Short | Shutdown fault occurred while Battle Short was enabled and then disabled. | Shutdown | Review Fault History and perform corrective action. |
| 1124 | Delayed Shutdown | Shutdown fault became active while Delayed Shutdown feature was enabled. | Warning | Review Fault History and perform corrective action. |
| 1131 | Battle Sh Active | Control is in Battle Short mode. | Warning | Bypasses several critical fault shutdowns for emergency operation. |
| 121 | Speed Signal Lost | Mag pickup speed indication is not being sensed. | Shutdown | Restart and check RPM on the digital display. |
| 1311 | Customer Input #1 | Optional customer selection (e.g. Low Fuel Day Tank, Water In Fuel, Ground Fault). Programmable via service tool: enable/disable, status/warning/shutdown, active open/closed, display name. | ||
| 1311, 1312, 1317, 1318 | CUSTOMER INPUT #1 - #4 | Optional customer-selected fault input is active. | Warning | Check external wiring and active input (closed/open) selection. |
| 1312 | Customer Input #2 | See code 1311. | ||
| 1313-1316 | Network Fault 1 thru 4 | |||
| 1317 | Customer Input #3 | See code 1311. | ||
| 1318 | Customer Input #4 | See code 1311. | ||
| 1334 | Crit Scaler Out Of Range | Incorrect feature or calibration entered into control. | Shutdown | Reload correct calibration. |
| 1335 | Noncrit Scaler Out Of Range | Incorrect feature or calibration entered into control. | Warning | Reload correct calibration. |
| 1337 | No Message | Info | ||
| 135 | Oil Pressure Sensor H | Engine oil pressure sender signal is shorted high. | Warning | Check sender/connectors/wires. |
| 141 | Oil Pressure Sensor L | Engine oil pressure sender signal is shorted low. | Warning | Check sender/connectors/wires. |
| 1416 | Fail To Shutdown | Genset continues to run after shutdown command. | Warning | Check Battle Short feature enabled condition. |
| 1417 | Powr Down Error | Controller cannot power down. | Warning | Controller cannot power down; possible drain on battery. Contact an authorized service center. |
| 143 | Pre-Low Oil Pres | Engine oil pressure has dropped to an unacceptable level. | Warning | If generator is powering critical loads and cannot be shut down, wait until next shutdown period and then follow code 415 procedure. |
| 1433 | Emergency Stop | Local Emergency Stop. | Shutdown | Pull button out; move switch to O; press Fault Acknowledge/Reset; select Manual or Auto. |
| 1434 | Remote E-Stop | Remote Emergency Stop. | Shutdown | See code 1433 to reset. |
| 1435 | Low Coolant Temp | Warning LED illuminates when engine jacket water coolant temperature falls below 70°F (21°C); per NFPA 110 requirement, indicates engine may not accept load within 10 seconds | Warning | Set is not operating; occurs when coolant temperature is 70°F (21°C) or lower. Check coolant heater power/fuse/cord, check coolant level and leaks. |
| 1438 | Fail To Crank | Engine failed to crank after PCC received a start signal. | Shutdown | Possible fault with control, speed sensing, or starting system. See code 441 for corrective action. |
| 144 | Coolant Sensor High | Engine coolant temperature signal is shorted high. | Warning | Check sender/connectors/wires. |
| 1442 | Weak Battery | Battery voltage at or below weak battery warning trip point during cranking. | Warning | See code 441 for corrective action. |
| 1443 | Battery Failed | Dead battery - engine will not start. | Shutdown | See code 441 for corrective action. |
| 1444 | KW Overload | Generator output power exceeded 105% of genset rating. | Warning | Check load and load lead connections; check CTs. |
| 1445 | Short Circuit | Generator output current has exceeded 175% of rated. | Shutdown | Check load and load lead connections. |
| 1446 | High AC Voltage | One or more phase voltages exceeded 130% of nominal. | Shutdown | Check fault simulation, load removal, threshold settings, Base board/generator. |
| 1447 | Low AC Voltage | Phase voltages dropped below 85% of nominal for 10 seconds. | Shutdown | Check overload, output terminal connections, PMG/field wiring, rectifier diodes. |
| 1448 | Under Frequency | Engine speed dropped below 90% of nominal for 10 seconds. | Shutdown | Check fuel supply, intake air supply and load. |
| 1449 | Over Frequency | Frequency is 10% above base frequency for 20 seconds. | Warning | Check fuel or air delivery; check connections. |
| 145 | Coolant Sensor Low | Engine coolant temperature signal is shorted low. | Warning | Check sender/connectors/wires. |
| 1452 | Gen CB Not Close | Genset circuit breaker (S2) failed to close when PTC is enabled. | Warning | Refer to Section 5 troubleshooting charts. |
| 1453 | Gen CB Not Open | Genset circuit breaker (S2) failed to open when PTC is enabled. | Warning | Refer to Section 5 troubleshooting charts. |
| 1459 | Reverse Power | Improper CT phasing. | Shutdown | Check wiring to voltage sense circuit; refer to CT Installation in Section 6. |
| 146 | Pre-High Coolant Temp | Engine has begun to overheat. | Warning | Reduce load; check air inlets/outlets; follow code 151 if engine can be stopped. |
| 1461 | Loss Of Field | Loss of field (electric) due to reverse kVAR. | Shutdown | Check excitation circuit. |
| 1466 | Modem Failure | Control cannot communicate with the modem. | Warning | Check for open, short to ground and loose connections to the modem. |
| 1468 | Network Error | Momentary loss of communication from the LonWorks Network. | Warning | Refer to LonWorks Network publications. |
| 1469 | Speed/Hz Match | Measured speed and measured AC output frequency do not agree. | Shutdown | Check calibration file. |
| 1471 | Over Current | Generator output current exceeded 110% of rated for 60 seconds. | Warning | Check load and load lead connections. |
| 1472 | Over Current | Output current exceeded 110% of rated and time/current calculation initiated shutdown. | Shutdown | Check load and load lead connections. |
| 151 | High Coolant Temp | Engine has overheated above the shutdown trip point. | Shutdown | Allow engine to cool completely. Check coolant level and replenish if low, look for leaks and repair. Check for obstructions to cooling airflow. Check fan belt. Check blower fan/circulation pumps on remote radiator installations. Reset control and restart. |
| 197 | Low Coolant Level | Engine coolant level has fallen below the warning trip point. | Warning | Optional. If generator is powering critical loads and cannot be shut down, wait until next shutdown period, then follow code 235 procedure. If engine can be stopped, follow code 235 procedure. |
| 200 | LOW OIL PRESSURE | Indicates engine oil pressure has dropped to an unacceptable level. | Warning | If generator is powering critical loads and cannot be shut down, wait until next shutdown period and then follow 201-SHUTDOWN procedure. Access the Oil Pressure menu prior to clearing the fault. |
| 201 | LOW OIL PRESSURE | Indicates engine oil pressure has dropped below the shutdown trip point. | Shutdown | Check oil level, replenish if low, reset control and restart; contact authorized service center. |
| 204 | OIL PRES SENDER | Indicates that the control has sensed that the engine oil pressure sender is out of its working range. | Warning | Check that the engine oil pressure sender is properly connected. |
| 210 | LOW COOLANT TEMP | Warning occurs when engine coolant temperature is 70°F (21°C) or lower. | Warning | Indicates engine coolant heater is not operating or is not circulating coolant. Check coolant heater power supply, low coolant level, and heater element current draw. |
| 211 | HIGH COOLANT TEMP | Indicates the engine coolant temperature is getting close to the recommended maximum temperature limit: 215° F (102° C) − standby or 207° F (97° C) − primary. | Warning | Review 212 correction list; increase in load or higher ambient may cause shutdown. |
| 212 | Oil Temp Sensor H | Indicates engine has overheated (coolant temperature has risen above the shutdown trip point: 215 F (102 C) - standby or 207 F (97 C) - primary). | Warning | Cool engine; check coolant level, airflow obstructions and fan belt; reset and restart. |
| 213 | Oil Temp Sensor L | Resistance of the coolant temperature sender is out of range. | Warning | Contact authorized service center. |
| 214 | LOW COOLANT LVL | Indicates engine coolant level has fallen below the trip point. | Warning | Cool engine; check coolant level and leaks; reset control and restart. |
| 215 | LOW COOLANT LVL | Indicates engine coolant level has fallen below the trip point. | Shutdown | Cool engine; check coolant level and leaks; reset control and restart. Shutdown will not occur in Idle mode. |
| 220 | MAG PICKUP | Mag pickup speed indication not sensed or does not match output frequency | Shutdown | Restart and check RPM; check PCC model setting; inspect and test MPU. |
| 221 | FAIL TO CRANK | Possible fault with control or starting system. | Shutdown | Clean and tighten battery cables; recharge or replace battery; contact service center. |
| 222 | OVERCRANK | Possible fuel system problem. | Shutdown | Check fuel tank, leaks, plugged lines, fuel filter and air filter; reset control and restart. |
| 223 | OVERSPEED | Indicates engine has exceeded normal operating speed. (115% ±1% of nominal). | Shutdown | Contact authorized service center. |
| 224 | FAIL TO SYNCHRONIZE | Generator set has not synchronized to the system bus within the allowable time frame. | Warning | Check governor system stability; adjust governing and synchronizer parameters; check fuel system. |
| 226 | FAIL TO CLOSE | Paralleling breaker has been given a signal to close, but has not closed properly. | Shutdown | Verify breaker charging mechanism; check close signal; verify auxiliary contact signals. |
| 230 | LOW DC VOLTAGE | Indicates battery voltage is below 10 VDC. | Warning | Recharge or replace the battery; check the battery charger fuse. Clean and tighten battery cable connections. Check engine DC alternator; replace if normal charging voltage is not obtained. Check float level if applicable. |
| 231 | HIGH DC VOLTAGE | Indicates battery voltage exceeds 32 VDC. | Warning | Lower battery charger float level if applicable; check engine DC alternator. |
| 232 | WEAK BATTERY | Indicates battery voltage drops below 60% of nominal for two seconds, during starting. | Warning | See warning message 230 LOW DC VOLTAGE. |
| 2323-2326 | Network Fault 5 thru 8 | |||
| 2327 | PTC Fault | PTC module or communication link is not working properly. | Warning | Check PTC module power, ground shield, cycle control power. |
| 2329 | Low S1 Frequency | Low utility (S1) frequency. | Warning | Check S1 AC inputs and wiring to PTC at TB5; check sensor set points. |
| 2331 | Low S1 Voltage | Low utility (S1) voltage. | Warning | Check S1 AC inputs and wiring to PTC at TB5; check pickup/dropout set points. |
| 2335 | Excitation Fault | Loss of all three voltage sense leads or failure in excitation circuit. | Shutdown | Check field wiring (X1 and X2) for shorts or opens. |
| 2336 | Memory Error | Control memory error; data corruption of critical operating parameters. | Shutdown | Try reloading calibration file. |
| 2337 | Pwr Tran Disabled | PTC module available but PTC feature not enabled. | Warning | Enable PTC feature with InPower; cycle control power. |
| 2338 | Pwr Tran Failure | Control could not communicate with the PTC module. | Warning | Check PTC module power and cable ground shield; cycle control power. |
| 2339 | Pwr Down Enabled | Power Down (sleep) enabled but PTC module or network board is active. | Warning | None required. |
| 234 | Overspeed | Engine has exceeded normal operating speed. | Shutdown | Check for large block load removal, flammable vapors or leaking turbocharger seals. |
| 2341 | High Control Temp | Control temperature above 158 F (70 C) for longer than set time. | Warning | Check genset room air flow. |
| 2342 | Too Long In Idle (10 min.) | Genset has been in Idle mode too long. | Warning | Exit idle mode. |
| 235 | Low Coolant Level | Engine coolant level has fallen below the shutdown trip point. | Shutdown | Optional. Allow engine to cool completely. Check coolant level and replenish if low, look for leaks and repair. Reset control and restart. |
| 2358 | High S1 Voltage | Utility (S1) voltage increased above the over-voltage threshold. | Warning | Measure S1 AC inputs at PTC module; check sensor set points. |
| 2396 | S1 CB Not Close | Utility contact (S1) failed to close with PTC enabled. | Warning | Refer to Section 5 troubleshooting charts. |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
⚠ Accidental starting of the generator set during this procedure presents the hazard of severe personal injury or death.
Tools: Dial indicator, Shims
⚠ Accidental starting of the generator set during this procedure presents the hazard of severe personal injury or death. Make sure to disconnect the negative (-) battery cable(s) before beginning.
Tools: Dial indicator, Wooden shims
⚠ Accidental starting during this procedure presents hazard of severe injury or death
⚠ Do not bar engine over by prying on fan blade
Tools: dial indicator
⚠ Accidental starting during this procedure presents the hazard of severe personal injury or death.
⚠ Do not bar engine over by prying on fan blade.
Tools: dial indicator
Tools: dial indicator
Tools: dial indicator
Tools: Frequency meter or tachometer, Jumper wire
Tools: Dial indicator with magnetic base or clamp
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Voltage | Phase | Connection | Leads | Notes |
|---|---|---|---|---|
| 12 lead generator sets | Load wires are routed through the CTs | Reconnectable gensets (12 leads) have dual secondary CTs (3 pins); CT wire 2/3 to pin 2 (high voltage) or pin 3 (low voltage). | ||
| 6 lead generator sets | Generator output leads are routed through the CTs | Non-reconnectable gensets (6 leads) have single secondary CTs (2 pins). | ||
| Cummins PowerCommand generic AC Reconnect Wiring Diagram 625-2755 (Rev. D) and 625-3100 (Rev. F) | Applies to models DFAA, DFAB, DFAC, DFBF, DFCB, DFCC, DFEB, DFEC, DFFB, DFGA, DFGB, DFJA, DFJB, DFJC, DFJD, DFLB, DFLC, DFLD, DFMB (625-2755) and models DFAA-DFMB plus DFCE, DFED, DQAA, DQAB, DQBA, DQBB (625-3100). | |||
| A (U) | CT21 | U load leads (A phase) | CT dot must face the generator; CT terminal 1 connects to metering circuit, terminal 2/3 to ground. | |
| B (V) | CT22 | V load leads (B phase) | CT dot must face the generator; terminal 1 to metering circuit, terminal 2/3 to ground. | |
| C (W) | CT23 | W load leads (C phase) | CT dot must face the generator; terminal 1 to metering circuit, terminal 2/3 to ground. | |
| 110 V - 120 V L-N | 1 | Single phase, 2-wire | PTC module jumper locations | |
| 190 V - 240 V L-L | 3 | Three phase | Use PTC module 0300-5382-01; 50/60 Hz | |
| 200 V - 240 V L-L | 1 | Single phase, 3-wire | PTC module jumper locations | |
| 380 V - 600 V L-L | 3 | Three phase | Use PTC module 0300-5382-02; 50/60 Hz |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Part # | Description | Category |
|---|---|---|
| 140-2503 | Bracket, Mounting | Air filter |
| 140-3163 | Cleaner, Air (No Replaceable Element) | Air filter |
| 140-3230 | Cleaner, Air (Includes Elements - See Ref. No. 25 and 26) | Air filter |
| 0300-4623-33 | DFLE (600V) | Current transformer |
| 0300-4623-57 | DFLE BR (0-480V) | Current transformer |
| 140-1260 | Fitting, Safety Filter | Service part / kit |
| 140-2395 | Tube, Air Inlet | Service part / kit |
| 140-2504-01 | Bracket - Right Side | Service part / kit |
| 140-2504-02 | Bracket - Left Side | Service part / kit |
| 140-2509 | Tube, Air Inlet | Service part / kit |
| 140-2528 | Shield – Air In Heat | Service part / kit |
Parts cataloged across all variants of this engine family — verify the exact part fits your specific variant and serial number before ordering.
The Cummins/Onan KTTA50 engine has an oil capacity of 169.0 liters.
The Cummins/Onan KTTA50 powers 2 generator set(s), including Cummins/Onan DFLC, Cummins/Onan DFLE.
A commonly reported issue on generators using the Cummins/Onan KTTA50 is: Warning Status Indicator: This yellow lamp is lit whenever the control detects a warning condition.. Fix: After the condition is corrected, warning indicators can be reset by pressing the Reset switch. (It is not necessary to stop the generator set.) In auto mode, warning indicators can also be reset by cycling the remote reset input after the condition is corrected..