Magnum — Shutting Down the Generator
Operation
From a Magnum operator's manual covering: MMG35D, MMG45K, MMG55D. Check it applies to your exact model before use.
Applies to: Magnum MMG35D, Magnum MMG45K, Magnum MMG55D, John Deere PE4024TF281 engine, Kubota V3600-T-E3BG engine, John Deere 4024HF285 engine
Procedure
- Notify personnel using generator power that power will be turned off.
- Remove all loads by opening all circuit breakers (OFF/O).
- Let the engine run about five minutes to cool down.
- Push the red ENGINE STOP button.
- Move the CONTROL ON/OFF toggle switch to CONTROL OFF/O.
- For extended storage time, disconnect the battery.
Specs & values
- 15 second shutdown timer (Stop Value); Stop Fail alarm if not shut down in 15 seconds
Source: Magnum operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.