Magnum — Shutting Down the Generator

Operation

From a Magnum operator's manual covering: MMG35D, MMG45K, MMG55D. Check it applies to your exact model before use.

Applies to: Magnum MMG35D, Magnum MMG45K, Magnum MMG55D, John Deere PE4024TF281 engine, Kubota V3600-T-E3BG engine, John Deere 4024HF285 engine

Procedure

  1. Notify personnel using generator power that power will be turned off.
  2. Remove all loads by opening all circuit breakers (OFF/O).
  3. Let the engine run about five minutes to cool down.
  4. Push the red ENGINE STOP button.
  5. Move the CONTROL ON/OFF toggle switch to CONTROL OFF/O.
  6. For extended storage time, disconnect the battery.

Specs & values

  • 15 second shutdown timer (Stop Value); Stop Fail alarm if not shut down in 15 seconds

Source: Magnum operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.