Magnum MMG55D Generator Set

The Magnum MMG55D is a 50 kW (63 kVA) standby generator set powered by a John Deere 4024HF285 engine. It is available at 120 V, 139 V, 208 V, 220 V, 240 V and 277 V, 3-phase, 60 Hz and rated 78 A. It holds about 8.5 L (2.2 gal) of oil and 18 L (4.8 gal) of coolant. Starting uses 1 battery rated 720 CCA at 12 V. The set weighs about 1064 kg (2346 lb). An integrated tank holds 401 L (105.9 gal), roughly 28.5 hours of runtime.

50 kW
Standby
2.4 L
Displacement
8.5 L
Oil capacity
0
Document types

Specifications

Frequency60.0 Hz
Standby power50 kW
Standby kVA63
Prime power47 kW
Oil capacity8.5 L
AlternatorMarathon 286PSL1701
Voltage options120 V, 139 V, 208 V, 220 V, 240 V, 277 V
Phase3
Rated current78 A
Power factor1 (1Ø), 0.8 (3Ø)
Circuit breaker225 A
Battery cranking720 CCA
Battery voltage12 V
Battery quantity1
Dry weight1064 kg
Fuel tank401.0 L
Tank runtime28.5 hr

Engine

John Deere 4024HF285
Oil capacity8.5 L
Coolant capacity18.0 L
Displacement2.4 L
Rated speed1800 rpm

Common questions

What is the power rating of the Magnum MMG55D?

The Magnum MMG55D is rated 50 kW standby (63.0 kVA).

What engine does the Magnum MMG55D use?

The Magnum MMG55D is powered by the John Deere 4024HF285 engine.

What is the oil capacity of the Magnum MMG55D?

The John Deere 4024HF285 engine in the Magnum MMG55D has an oil capacity of 8.5 liters.

What alternator does the Magnum MMG55D use?

The Magnum MMG55D uses a Marathon 286PSL1701 alternator.

Troubleshooting

8

Fault codes

CodeMeaning
FCECU alarm FailureCode
nullThe door covering the customer connection lugs/cam lock receptacles is opened.

Symptoms & remedies

SymptomCauseRemedy
LOW FUEL LEVEL SHUT DOWNFuel level is low or fuel tank has leaks.Check the fuel level on the LCD window. Ensure no leaks in the fuel tank. Check the fuel level sender and connecting wiring for damage.
LOW OIL PRESSURE SHUT DOWNOil pressure is less than 20 psi (138 kPa).Check the engine oil level with a dipstick. Visually inspect for oil leaks. If oil level is good, restart and verify oil pressure within five seconds. Check the oil pressure sender.
LOW COOLANT LEVEL SHUT DOWNCoolant level in the radiator is low.Allow engine to cool. Check coolant level in the radiator. Access the radiator cap by removing the access panel from the top of the enclosure.
High Coolant Temperature Shut downCheck the coolant level in the overflow jug. Restart the engine and read the coolant temperature to verify High Coolant Temperature Shut down. Stop the engine immediately if the coolant temperature is 230°F (110°C) or more. Allow the engine to cool. Add coolant to the overflow jug if it is low and then check the level of coolant in the radiator. To access the radiator cap, you must remove the access panel from the top of the enclosure directly above the radiator. Add coolant until it is 3/4” below the filler neck. Secure the radiator cap back into its original position. Check the radiator shroud and ducting for blockage and remove any foreign matter. Inspect coolant hoses, engine block and water pump for visible leaks.
Overcrank Shut downCheck the fuel level in the tank. Check for proper operation of the fuel pump. Check air filter for blockage. If the engine will not start, consult the engine operation and maintenance manual for additional information on troubleshooting starting problems.
Overspeed or Underspeed Shut downDisconnect all loads and restart the generator. Read the frequency (Hz) on the LCD display. With no loads on the generator, the frequency should read 60.0 Hz. If the frequency is above or below 60.0 Hz, the engine speed will have to be adjusted. See the engine manual for throttle adjustments on mechanically governed units and see the electronic governor manual for electronically controlled units.

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.

Parts

1
Part #DescriptionQtySystem
MMG55DGenerator Make: _______________________________________ Generator Model Number:________________________________ Generator Serial Number: ________________________________Service part / kit PartsGeek

Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.

Fuel consumption

RatingLoadL/hgal/h
Prime11.43.0
Standby9.82.6