| AnInIOM Sd | Analog Input IOM Shutdown | Shutdown alarm configurable on the input of IG-IOM/IGS-PTM. | Shutdown | |
| AnInIOM Wrn | Analog Input IOM Warning | Warning alarm configurable on the input of IG-IOM/IGS-PTM. | Warning | |
| Battery Flat | Battery Flat (low battery) | If the controller switches off during starting sequence due to bad battery condition, it doesn't try to start again and activates this protection. | Shutdown | |
| Binary Input | Binary Input | Configurable warning/shutdown alarms on the inputs of IL-NT. | | |
| ChrgAlternFail | Charge Alternator Fail | Failure of the alternator to charge the battery. | Warning | |
| EmergencyStop | Emergency Stop | If the input Emergency Stop is opened or the red E-Stop button is pushed, shutdown is immediately activated. | Shutdown | |
| Engine Temp Sd | Engine Temperature Shutdown | Water temperature is greater than Sd Water Temp setpoint. | Shutdown | |
| Engine Temp Wrn | Engine Temperature Warning | Water temperature is greater than Wrn Water Temp setpoint. | Warning | |
| Fgen<, > | Generator Frequency Out of Limits | The generator frequency is out of limits given by Gen >f and Gen <f setpoints. | Shutdown | |
| Fuel Level Sd | Fuel Level Shutdown | Fuel level is smaller than Sd Fuel Level setpoint (5%). | Shutdown | |
| Fuel Level Wrn | Fuel Level Warning | Fuel level is smaller than Wrn Fuel Level setpoint (15%). | Warning | |
| GCB fail | Generator Circuit Breaker Fail | Failure of the generator circuit breaker. | Shutdown | |
| Igen unbl | Generator Current Unbalanced | The generator current is unbalanced. | Shutdown | |
| Low BackupBatt | Low Backup Battery | RTC backup battery is flat (low). | Warning | |
| Oil Press Sd | Oil Pressure Shutdown | Oil pressure is smaller than Oil Press Sd setpoint. | Shutdown | |
| Oil Press Wrn | Oil Pressure Warning | Oil pressure is smaller than Oil Press Wrn setpoint. | Warning | |
| Overload | Overload | The load is greater than the value given by Overload setpoint. | Shutdown | |
| Overspeed | Overspeed | The protection comes active if the speed is greater than Overspeed setpoint. | Shutdown | |
| ParamFail | Parameter Fail | Wrong checksum of parameters. Happens typically after downloading new firmware or changing of the parameter. The controller stays in INIT mode. Check all parameters, write at least one new parameter. | | Check all parameters; write at least one new parameter |
| PickupFault | Pickup Fault | Failure of the magnetic pick-up sensor for speed measurement. | Shutdown | |
| SPN:100 | EngOil Press | John Deere ECU alarm list parameter (SPN shown as FC on bottom left of LCD). | | Refer to John Deere Operator's Manual |
| SPN:102 | Boost Press | John Deere ECU alarm list parameter. | | Refer to John Deere Operator's Manual |
| SPN:105 | Intake Temp | John Deere ECU alarm list parameter. | | Refer to John Deere Operator's Manual |
| SPN:110 | EngCool Temp | John Deere ECU alarm list parameter. | | Refer to John Deere Operator's Manual |
| SPN:1485 | ECU MainRelay | John Deere ECU alarm list parameter. | | Refer to John Deere Operator's Manual |
| SPN:175 | EngOil Temp | John Deere ECU alarm list parameter; oil temp always displays #####. | | Refer to John Deere Operator's Manual |
| SPN:629 | Controller #1 | John Deere ECU alarm list parameter. | | Refer to John Deere Operator's Manual |
| SPN:636 | PositionSensor | John Deere ECU alarm list parameter. | | Refer to John Deere Operator's Manual |
| SPN:637 | TimingSensor | John Deere ECU alarm list parameter. | | Refer to John Deere Operator's Manual |
| SPN:651 | InjectorCyl#1 | John Deere ECU alarm list parameter. | | Refer to John Deere Operator's Manual |
| SPN:652 | InjectorCyl#2 | John Deere ECU alarm list parameter. | | Refer to John Deere Operator's Manual |
| SPN:653 | InjectorCyl#3 | John Deere ECU alarm list parameter. | | Refer to John Deere Operator's Manual |
| SPN:654 | InjectorCyl#4 | John Deere ECU alarm list parameter. | | Refer to John Deere Operator's Manual |
| SPN:655 | InjectorCyl#5 | John Deere ECU alarm list parameter. | | Refer to John Deere Operator's Manual |
| SPN:656 | InjectorCyl#6 | John Deere ECU alarm list parameter. | | Refer to John Deere Operator's Manual |
| SPN:677 | EngStartRelay | John Deere ECU alarm list parameter. | | Refer to John Deere Operator's Manual |
| Sd IOM fail | IOM Fail | IOM/IGS-PTM module failure. | Shutdown | |
| SprinkIActive | Sprinkler Active | The protection is active if the output Sprinkler is closed. | Warning | |
| Start failed | Start Failed | Unit did not start. | Shutdown | After starter cools two minutes, press FAULT RESET and retry |
| Stop fail | Stop Fail | Unit did not stop. | Shutdown | |
| Ubat | Battery Voltage Out of Limits | Battery voltage is out of limits given by Batt Undervolt setpoints. | Warning | |
| Underspeed | Underspeed | During starting of the engine, when the RPM reaches the value of Starting RPM setpoint, the starter is switched off and the speed of the engine can drop under Start RPM again. Then the underspeed protection becomes active. Protection evaluation starts 5 seconds after start up. | Shutdown | |
| Vgen unbal | Generator Voltage Unbalanced | The generator voltage is unbalanced more than the value of Volt unbal setpoint. | Shutdown | |
| Vgen<, > | Generator Voltage Out of Limits | The generator voltage is out of limits given by Gen <V and Gen <V setpoints. | Shutdown | |
| Wrn ECU Alarm | ECU Alarm Warning | ECU alarm list is not empty. | Warning | View ECU Alarm List; resolve fault and clear code |
| Wrn RA15 fail | RA15 Module Failure Warning | Warning alarm in case of lost connection to IGL=RA15 module. | Warning | |
| WrnMaintenance | Maintenance Warning | The period for servicing is set by the WrnMaintenance setpoint. The protection comes active if the running hours of the engine reach this value. | Warning | Service unit and reset Time to Service to 250 hours |