Generac G0072100 — Shutting Generator Down While Under Load or During a Utility Outage

Operation

For the Generac G0072100, from the Generac service manual.

Applies to: Generac G0072100

Before you start

  • Automatic start-up. Disconnect utility power and render unit inoperable before working on unit.

Procedure

  1. Set utility MLCB to OFF (OPEN).
  2. Set generator MLCB (disconnect) to OFF (OPEN).
  3. Allow generator to run for cool-down approximately one minute.
  4. Set generator to OFF at the controller.
  5. Remove 7.5A fuse from controller.

Full service-parts list: Generac G0072100 →

Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.