Generac G0072100 — Manual Transfer Operation

Operation · transfer switch

For the Generac G0072100, from the Generac owner's manual.

Applies to: Generac G0072100, Generac G-Force 400 Series engine, Generac G-Force 800 Series engine, Generac G-Force 1000 Series engine

Before you start

  • Electrocution. Do not manually transfer under load. Disconnect transfer switch from all power sources prior to manual transfer.

Procedure

  1. Verify generator is in OFF mode and set generator MLCB (generator disconnect) to OFF (OPEN).
  2. Turn off utility power supply to transfer switch using means provided (such as a utility MLCB).
  3. Use manual transfer handle inside transfer switch to move main contacts to STANDBY.
  4. Press MANUAL button on control panel to crank and start engine.
  5. Allow engine to stabilize and warm up for a few minutes.
  6. Set generator MLCB (generator disconnect) to ON (CLOSED); standby source now powers loads.