Generac — Current Calibration

Adjustments · Controller CTs

From a Generac service manual covering: 10 KVA, 13 kVA, 8 kVA. Check it applies to your exact model before use.

Applies to: Generac EcoGen 6 kW, Generac GH-410 engine, Generac GH-426 engine, Generac GT-530 engine, Generac GT-530 engine, Generac GT-999 engine, Generac OHVI engine

Before you start

  • Electrocution. Lethal voltage may be present at CTs.

Procedure

  1. Connect load bank to output.
  2. Place amp meter over circuit.
  3. Start generator and warm up.
  4. Apply rated load.
  5. Select Current Calibration menu.
  6. Adjust display to match amp meter.
  7. Save calibration.
  8. Repeat for CT2.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • CT output approx 0-1.5 VAC based on load

Full service-parts list: Generac EcoGen 6 kW →

Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.