Home›Repair guides›Cummins/Onan›Testing Exciter Stator Winding

Cummins/Onan A15 — Testing Exciter Stator Winding

Testing & diagnosis

For the Cummins/Onan A15, from the Cummins/Onan service manual.

Applies to: Cummins/Onan DGBB, Cummins/Onan DGBC, Cummins/Onan DGCA, Cummins/Onan DGCB, Cummins/Onan DGCC, Cummins/Onan DGDA, Cummins/Onan DGDB, Cummins/Onan DGEA, Cummins/Onan DGFA, Cummins/Onan DGFB, Cummins/Onan B and C Series diesel engine

Procedure

  1. Measure winding resistance with Wheatstone bridge or digital ohmmeter between the two stator leads X and XX.
  2. Replace stator if resistance not as specified in Table 7-1.
  3. Disconnect leads from terminals X and XX; measure insulation resistance between either lead and stator laminations with ohmmeter.
  4. Replace stator if insulation resistance less than 1 megohm.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • insulation resistance minimum 1 megohm

Full service-parts list: Cummins/Onan DGBB →, Cummins/Onan DGBC →, Cummins/Onan DGCA →, Cummins/Onan DGCB →, Cummins/Onan DGCC →, Cummins/Onan DGDA →, Cummins/Onan DGDB →, Cummins/Onan DGEA →, Cummins/Onan DGFA →, Cummins/Onan DGFB →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.