Cummins/Onan A15 — Servicing the PMG

Testing & diagnosis · PMG exciter

For the Cummins/Onan A15, from the Cummins/Onan service manual.

Applies to: Cummins/Onan DGBB, Cummins/Onan DGBC, Cummins/Onan DGCA, Cummins/Onan DGCB, Cummins/Onan DGCC, Cummins/Onan DGDA, Cummins/Onan DGDB, Cummins/Onan DGEA, Cummins/Onan DGFA, Cummins/Onan DGFB, Cummins/Onan B and C Series diesel engine

Before you start

  • Touching uninsulated high voltage parts can result in severe personal injury or death.

Procedure

  1. Disconnect leads P2, P3, P4 from voltage regulator.
  2. Start engine and let speed stabilize.
  3. Measure voltage across lead pairs P2-P3, P3-P4, P4-P2; should be at least 150 VAC (50Hz) or 180 VAC (60Hz).
  4. Stop set and measure resistance across same lead pairs; each winding approximately 4.4 ohms.
  5. Torque PMG rotor center bolt to 40 ft-lbs (54 Nm) when reassembling; stator leads must be at 12 o'clock.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • 150/180 VAC minimum
  • 4.4 ohms per winding
  • rotor center bolt 40 ft-lbs (54 Nm)