Home›Repair guides›Cummins/Onan›Flashing the Field (Self-Excited Generators)

Cummins/Onan A15 — Flashing the Field (Self-Excited Generators)

Repair & overhaul · exciter stator

For the Cummins/Onan A15, from the Cummins/Onan service manual.

Applies to: Cummins/Onan DGBB, Cummins/Onan DGBC, Cummins/Onan DGCA, Cummins/Onan DGCB, Cummins/Onan DGCC, Cummins/Onan DGDA, Cummins/Onan DGDB, Cummins/Onan DGEA, Cummins/Onan DGFA, Cummins/Onan DGFB, Cummins/Onan B and C Series diesel engine

Procedure

  1. Shut down set, disconnect AVR.
  2. Apply 110 to 220 VAC for 1 to 2 seconds to X and XX leads through a diode and 3 amp fuse.
  3. Alternatively, with set running and disconnected from loads, apply 12 VDC battery for 1 to 2 seconds with correct polarity (+ to X, - to XX).

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Full service-parts list: Cummins/Onan DGBB →, Cummins/Onan DGBC →, Cummins/Onan DGCA →, Cummins/Onan DGCB →, Cummins/Onan DGCC →, Cummins/Onan DGDA →, Cummins/Onan DGDB →, Cummins/Onan DGEA →, Cummins/Onan DGFA →, Cummins/Onan DGFB →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.