Home›Repair guides›Cummins/Onan›Testing the PMG

Cummins/Onan 2100 Series — Testing the PMG

Testing & diagnosis · Permanent Magnet Generator

For the Cummins/Onan 2100 Series, from the Cummins/Onan service manual.

Applies to: Cummins/Onan DFAB, Cummins/Onan DFAC, Cummins/Onan DFBF, Cummins/Onan DFCB, Cummins/Onan DFCC, Cummins/Onan DFCE, Cummins/Onan DFGB, Cummins/Onan DFGE, Cummins/Onan DFLB, Cummins/Onan DFLC, Cummins/Onan DFLE

Before you start

  • Hazardous voltage inside control housing and output box.

Procedure

  1. Disconnect PMG leads PMG 2, PMG 3 and PMG 4 from AC harness.
  2. Start engine and let speed stabilize.
  3. Measure voltage across PMG 2&3, PMG 3&4 and PMG 4&2.
  4. Voltage should be at least 150 VAC for 50 Hz sets.
  5. At least 180 VAC for 60 Hz sets; readings approximately equal.
  6. Stop set and measure resistance across lead pairs.
  7. Refer to Table 7-2 for resistance values.

Tools required

  • Voltmeter Amazon
  • Wheatstone bridge or digital ohmmeter Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • At least 150 VAC (50 Hz) / 180 VAC (60 Hz)

Full service-parts list: Cummins/Onan DFBF →, Cummins/Onan DFCC →, Cummins/Onan DFCE →, Cummins/Onan DFGB →, Cummins/Onan DFGE →, Cummins/Onan DFLB →, Cummins/Onan DFLC →, Cummins/Onan DFLE →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.