Cummins/Onan 2100 Series — Rupture Basin Leak Detect Switch Test
Maintenance
For the Cummins/Onan 2100 Series, from the Cummins/Onan service manual.
Applies to: Cummins/Onan DFAB, Cummins/Onan DFAC, Cummins/Onan DFBF, Cummins/Onan DFCB, Cummins/Onan DFCC, Cummins/Onan DFCE, Cummins/Onan DFGB, Cummins/Onan DFGE, Cummins/Onan DFLB, Cummins/Onan DFLC, Cummins/Onan DFLE
Procedure
- Remove pipe fitting/switch assembly from rupture basin tank.
- Move O/Manual/Auto switch to MANUAL position.
- Activate leak detect switch (move float upward).
- Check control display for Rupture Basin fault message.
- If no fault, repair defective circuit.
- Apply thread sealant and install switch assembly.
Full service-parts list: Cummins/Onan DFBF →, Cummins/Onan DFCC →, Cummins/Onan DFCE →, Cummins/Onan DFGB →, Cummins/Onan DFGE →, Cummins/Onan DFLB →, Cummins/Onan DFLC →, Cummins/Onan DFLE →
Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.