Home›Repair guides›Cummins/Onan›Rupture Basin Leak Detect Switch Test

Cummins/Onan 2100 Series — Rupture Basin Leak Detect Switch Test

Maintenance

For the Cummins/Onan 2100 Series, from the Cummins/Onan service manual.

Applies to: Cummins/Onan DFAB, Cummins/Onan DFAC, Cummins/Onan DFBF, Cummins/Onan DFCB, Cummins/Onan DFCC, Cummins/Onan DFCE, Cummins/Onan DFGB, Cummins/Onan DFGE, Cummins/Onan DFLB, Cummins/Onan DFLC, Cummins/Onan DFLE

Procedure

  1. Remove pipe fitting/switch assembly from rupture basin tank.
  2. Move O/Manual/Auto switch to MANUAL position.
  3. Activate leak detect switch (move float upward).
  4. Check control display for Rupture Basin fault message.
  5. If no fault, repair defective circuit.
  6. Apply thread sealant and install switch assembly.

Full service-parts list: Cummins/Onan DFBF →, Cummins/Onan DFCC →, Cummins/Onan DFCE →, Cummins/Onan DFGB →, Cummins/Onan DFGE →, Cummins/Onan DFLB →, Cummins/Onan DFLC →, Cummins/Onan DFLE →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.