Magnum MMG185 Generator Set

The Magnum MMG185 is a 177 kW (221 kVA) Diesel standby generator set powered by a John Deere PE6068HF485 engine. It is available at 120 V, 139 V, 208 V, 220 V, 240 V, 277 V, 440 V and 480 V, 1Ø and 3Ø and 60 Hz. It holds about 31.2 L (8.2 gal) of oil and 35.9 L (9.5 gal) of coolant, with a maximum ambient rating of 49 °C. Starting uses 1 group-31 battery rated 1000 CCA at 12 V. The set measures 5330×2180×2360 mm (209.8×85.8×92.9 in), weighs about 2617 kg (5769 lb) and produces 68 dBA at 7 m. An integrated tank holds 1295 L (342.1 gal), roughly 21 hours of runtime.

177 kW
Standby
6.8 L
Displacement
31.2 L
Oil capacity
3
Document types

Typical fuel consumption for 175–180 kW Diesel generators →

Compare with other 175–180 kW Diesel generators →

Specifications

FuelDiesel
Frequency60.0 Hz
Standby power177 kW
Standby kVA221
Prime power162 kW
EmissionsTier III
ControllerMagnum Digital (MDC)
Oil capacity31.2 L
AlternatorMarathon 431PSL6202
Voltage options120 V, 139 V, 208 V, 220 V, 240 V, 277 V, 440 V, 480 V
Phase1Ø and 3Ø
Power factor1 (1Ø), 0.8 (3Ø)
Circuit breaker700 A
Battery groupGroup 31
Battery cranking1000 CCA
Battery voltage12 V
Battery quantity1
Starting system12 V DC
Coolant capacity35.9 L
Max ambient49 °C
Dimensions (L×W×H)5330×2180×2360 mm
Dry weight2617 kg
Wet weight3792 kg
Sound level68.0 dBA @ 7 m
Fuel tank1295.0 L
Tank runtime21 hr

Engine

John Deere PE6068HF485
Oil capacity31.2 L
Coolant capacity35.9 L
Displacement6.8 L
Aspirationturbocharged
Rated speed1800 rpm

Maintenance & consumables

for the John Deere PE6068HF485
ItemSpecCapacityPart #Interval
Air filter—
Fuel filter—
Oil filter—
Battery—
Belt—
Coolant—
Oil—
Spark plug—

Service intervals

5
ItemActionHoursMonthsNotes
Engine oil and oil filterChange250 hrFirst service — First 100 hours; do not exceed 100 hours with break-in oil
WrnMaintenance service reminderOther250 hrReset time to service to 250 hours
BeltInspect500 hr12 moRemove and check for wear; inspect pulleys and bearings
Diesel Particulate Filter (DPF)Clean3000 hrExpected service at least 3000 or 4500 hours; actual when indicator light appears
Trailer wheel bearingsLubricate12 moOr every 12,000 miles (19,312 km)

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

18
TypeItemValueUnitCondition
OtherFuel level shutdown5%shutdown
OtherFuel level warning15%low fuel warning
PressureAir filter restriction20in. H2Oreplace air filter
PressureEngine oil pressure35-80psinormal operating
PressureEngine oil pressure minimum5psi (34 kPa)within five seconds
PressureEngine oil pressure shutdownless than 20psi (138 kPa)shutdown
PressurePrimary air cleaner restriction25in. H2Oreplace primary air cleaner
SpeedOperating speed1800rpm
TemperatureEngine coolant temperature shutdown230°F (110°C)shutdown
TemperatureViscous fan clutch temperature range170-200°F (77-93°C)depending on unit model
TorqueGenerator drive plate bolts46ft-lbs
TorqueShorting (link) board 1/2 inch nuts25ft-lbsMMG235 reconnect board
TorqueWheel lug nuts20-25ft-lbsfirst pass
TorqueWheel lug nuts50-60ft-lbssecond pass
TorqueWheel lug nuts90-120ft-lbsthird pass
VoltageBattery voltage normal13-14V12 volt systems with engine running
VoltageFine voltage adjustment tolerance10%within 45 seconds of start-up
VoltageVoltage regulation+/- 1%

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
Engine oilJohn Deere Plus 50 IIBreak-in oil supplied from factory; do not exceed 100 hours with break-in oil
FuelUltra low sulfur dieselUse clean diesel fuel only
GreaseHigh quality wheel bearing greaseFor trailer wheel bearings

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Fault codes

31
CodeNameMeaningSeverityAction
AnInIOM SdAnInIOM SdShutdown alarm configurable on the input of IG-IOM/IGS-PTM.Shutdown
AnInIOM WrnAnInIOM WrnWarning alarm configurable on the input of IG-IOM/IGS-PTM.Warning
Battery FlatBattery FlatController switches off during starting sequence due to bad battery condition; does not try to start again.Shutdown
Binary InputBinary InputConfigurable warning/shutdown alarms on the inputs of IL-NT.Warning
ChrgAlternFailChrgAlternFailFailure of the alternator to charge the battery.Warning
EmergencyStopEmergencyStopIf the input Emergency Stop is opened, shutdown is immediately activated.Shutdown
Engine Temp SdEngine Temp SdWater temperature is greater than Sd Water Temp setpoint.Shutdown
Engine Temp WrnEngine Temp WrnWater temperature is greater than Wrn Water Temp setpoint.Warning
Fgen<, >Fgen<, >Generator frequency is out of limits given by Gen >f and Gen <f setpoints.Shutdown
Fuel Level SdFuel Level SdFuel level is smaller than Sd Fuel Level setpoint.Shutdown
Fuel Level WrnFuel Level WrnFuel level is smaller than Wrn Fuel Level setpoint.Warning
GCB failGCB failFailure of the generator circuit breaker.Shutdown
Igen unblIgen unblThe generator current is unbalanced.Shutdown
Low BackupBattLow BackupBattRTC backup battery is flat.Warning
Oil Press SdOil Press SdOil pressure is smaller than Sd Oil Press setpoint.Shutdown
Oil Press WrnOil Press WrnOil pressure is smaller than Wrn Oil Press setpoint.Warning
OverloadOverloadThe load is greater than the value given by Overload setpoint.Shutdown
OverspeedOverspeedProtection comes active if speed is greater than Overspeed setpoint.Shutdown
ParamFailParamFailWrong checksum of parameters; controller stays in INIT mode.InfoCheck all parameters; write at least one new parameter.
PickupFaultPickupFaultFailure of the magnetic pick-up sensor for speed measurement.Shutdown
Sd IOM failSd IOM failIOM/IGS-PTM module.Shutdown
SprinkIActiveSprinkIActiveProtection is active if the output Sprinkler is closed.Warning
Start failedStart failedGen-set start failed.Shutdown
Stop failStop failGen-set stop failed.Shutdown
UbatUbatBattery voltage is out of limits given by Batt Overvolt and Batt Undervolt setpoints.Warning
UnderspeedUnderspeedDuring starting, speed can drop under Start RPM again; underspeed protection becomes active.Shutdown
Vgen unblVgen unblGenerator voltage is unbalanced more than Volt unbal setpoint.Shutdown
Vgen<, >Vgen<, >Generator voltage is out of limits given by Gen <V and Gen <V setpoints.Shutdown
Wrn ECM AlarmWrn ECM AlarmECM alarm list is not empty.Warning
Wrn RA15 failWrn RA15 failWarning alarm in case of lost connection to IGL=RA15 module.Warning
WrnMaintenanceWrnMaintenanceService period set by WrnMaintenance setpoint; running hours reached.Warning

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Changing Output Voltage (MMG235 Only) adjustment

⚠ Never change voltage while engine is running.

Tools: Wrench

  1. Shut down generator; main breaker and control power OFF.
  2. Remove reconnect box door.
  3. Remove all 1/2 inch nuts holding shorting board.
  4. Move board to upper position for 208/120V 3Ø.
  5. Move board to lower position for 480/277V 3Ø.
  6. Replace hardware and tighten to 25 ft-lbs.
  7. Reinstall reconnect box door.
  8. Start generator and verify voltage.
Adjusting Display Back Lighting maintenance
  1. Press and hold Enter.
  2. Press up or down arrow to increase or decrease brightness.
  3. Release Enter when desired brightness is attained.
Checking Generator Drive Plate Torque maintenance

Tools: Torque wrench

  1. Disconnect engine starting battery.
  2. Remove generator fan guard.
  3. Torque each drive plate bolt to 46 ft-lbs.
  4. Reinstall fan guard.
  5. Reconnect battery.
Lubricating Trailer Wheel Bearings maintenance

Tools: Grease gun

  1. Remove small rubber plug on grease cap.
  2. Attach standard grease gun to grease zerk fitting.
  3. Pump grease until new grease is visible at nozzle.
  4. Wipe excess grease from hub with clean cloth.
  5. Replace rubber plug.
Resetting the Time to Service Reminder maintenance
  1. Power up controller with Control On/Off switch.
  2. Press PAGE SELECT; Alarm List appears.
  3. Press down arrow to select Engine Protect.
  4. Press Enter; WrnMaintenance appears.
  5. Press Enter; current run time appears.
  6. Press up arrow to set 250 hours.
  7. Press Enter to save.
  8. Move CONTROL switch to OFF / O.
AUTO (Remote) Starting of the Generator operation

⚠ Verify remote switch contacts are OPEN before AUTO.

Tools: Jumper wire minimum 16 gauge

  1. Perform manual start once to verify engine operation.
  2. Remove wires from remote start terminal block if testing.
  3. Press AUTO; LCD highlights AUTO.
  4. Jumper the two remote start terminals with minimum 16 gauge wire.
  5. Engine cranks, starts and runs.
  6. Remove jumper; engine stops.
  7. Reconnect remote start switch wires.
  8. Confirm AUT displayed; close main circuit breaker and lock doors.
Auto Exercise Timer operation

⚠ Controller must be in AUTO mode to run at programmed time.

  1. Press PAGE SELECT until Password appears.
  2. Select Date/Time and press ENTER.
  3. Select Timer1 Repeat and press ENTER.
  4. Choose day or days and press ENTER.
  5. Set Timer1 ON Time and press ENTER.
  6. Set Timer1Duration and press ENTER.
  7. Press PAGE SELECT three times to return.
  8. Press AUTO to switch to automatic mode.
Auxiliary Fuel Tank Operation operation
  1. Shut down unit; internal tank fuel above five percent.
  2. Attach auxiliary tank lines to AUXILIARY FUEL INLET and OUTLET.
  3. Open AUXILIARY FUEL INLET and OUTLET valves inside right front door.
Fuel Transfer Pump Option operation
  1. Shut down unit unless external bulk fuel supply already connected.
  2. Attach external bulk fuel supply to FUEL TRANSFER INLET fitting.
  3. Turn on Fuel Transfer Switch.
Manual Starting of the Generator operation

⚠ Do not start under load in MANUAL mode.

  1. Move CONTROL ON/OFF toggle switch to CONTROL ON / I.
  2. Confirm LCD shows MAN mode and Ready; Ready/Manual LED lit.
  3. Press green ENGINE START button.
  4. Wait for preheat countdown and cranking; engine starts.
  5. Allow 45-second V Detect countdown.
  6. Check for leaks, noise, vibration before applying load.
  7. Verify AC voltage and frequency approximately 60 Hz.
  8. Close main circuit breaker and convenience outlet breakers.
Shutting Down the Generator operation
  1. Remove all loads by opening all circuit breakers.
  2. Let engine run approximately five minutes to cool.
  3. Push red ENGINE STOP button.
  4. Wait for 15-second Stop Value timer.
  5. Move CONTROL ON/OFF switch to CONTROL OFF / O.
  6. Disconnect battery for extended storage.
Towing the Trailer operation
  1. Raise or lower trailer onto hitch; lock coupling.
  2. Attach safety chains or cables and raise jack foot.
  3. Connect trailer wiring; check stop and signal lights.
  4. Make sure all doors are properly latched.
  5. Check trailer tire inflation.
  6. Check wheel lugs; tighten loose or replace missing.
  7. Maximum highway towing speed 45 mph (72 km/h).

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
208/120V3-phase208/120V 3-PHASET1,T2,T3,T4,T5,T6,T7,T8,T9,T10,T11,T12; L1,L2,L3,NL1-L2=208V; L2-L3=208V; L3-L1=208V; L1-N=120V; L2-N=120V; L3-N=120V
208/120V 3Ø3-phaseMMG235 link board upper positionT1,T9,T11,T7,T10,T4,T12,T8,T3,T6,T2,T5Shorting (link) board upper position; torque 25 ft-lbs
240/120V1-phase240/120V 1-PHASET1,T2,T3,T4,T5,T6,T7,T8,T9,T10,T11,T12; L1,L3,NL1-L3=240V; L1-N=120V; L3-N=120V
480/277V3-phase480/277V 3-PHASET1,T2,T3,T4,T5,T6,T7,T8,T9,T10,T11,T12; L1,L2,L3,NL1-L2=480V; L2-L3=480V; L3-L1=480V; L1-N=277V; L2-N=277V; L3-N=277V
480/277V 3Ø3-phaseMMG235 link board lower positionT1,T9,T11,T7,T10,T4,T12,T8,T3,T6,T2,T5Shorting (link) board lower position; torque 25 ft-lbs

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

What is the power rating of the Magnum MMG185?

The Magnum MMG185 is rated 177 kW standby (221.0 kVA).

What engine does the Magnum MMG185 use?

The Magnum MMG185 is powered by the John Deere PE6068HF485 engine.

What fuel does the Magnum MMG185 use?

The Magnum MMG185 runs on Diesel.

What's the oil capacity on a Magnum MMG185?

The John Deere PE6068HF485 engine in the Magnum MMG185 has an oil capacity of 31.2 liters.

What is the coolant capacity of the Magnum MMG185?

The Magnum MMG185 cooling system holds 35.9 liters (9.5 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.

What is the continuous rating of the Magnum MMG185?

The Magnum MMG185 is rated 162 kW prime (202 kVA), against 177 kW standby.

How loud is the Magnum MMG185?

The Magnum MMG185 is rated at 68.0 dBA at 7 m, per the manufacturer specification sheet.

How much does the Magnum MMG185 weigh?

The Magnum MMG185 has a dry weight of 2617 kg (5769 lb).

What size fuel tank does the Magnum MMG185 have?

The Magnum MMG185 has a 1295 liter (342 US gallon) fuel tank, giving about 21 hours of runtime.

What voltage does the Magnum MMG185 produce?

The Magnum MMG185 is offered in 120 V, 139 V, 208 V, 220 V, 240 V, 277 V, 1Ø and 3Ø-phase.

What battery does the Magnum MMG185 use?

The Magnum MMG185 uses 1 battery, 12 V each, 1000 CCA, group Group 31, per the manufacturer specification sheet. The starting system is 12 V DC.

What alternator does the Magnum MMG185 use?

The Magnum MMG185 uses a Marathon 431PSL6202 alternator.

Troubleshooting

6

Symptoms & remedies

SymptomCauseRemedy
Low fuel level shut downFuel level low or inaccurate reading; leaks in the fuel tank; fuel level sender and connecting wiring damagedCheck the fuel level on the LCD window and confirm the generator is sitting level; check for leaks in the fuel tank; check the fuel level sender and the connecting wiring for damage and check for continuity between the sender and the engine controller
Low oil pressure shut downLow engine oil level; oil leaks; loss of oil pressure; faulty oil pressure senderCheck the level of the engine oil with the dipstick and add oil if required; visually inspect the engine for oil leaks; restart the unit and verify the loss of oil pressure, shutting the engine down immediately if the oil pressure value does not read five psi (34 kPa) within five seconds; check the oil pressure sender and refer to the troubleshooting section of the engine operation and maintenance manual
Low coolant level shut downLow coolant level; leaks in coolant hoses, engine block or water pump; coolant mixed with engine oilAllow the engine to cool; check the coolant level in the radiator and add coolant until it is 3/4" below the filler neck, then secure the radiator cap; inspect coolant hoses, engine block and water pump for visible leaks; check engine oil to verify no coolant has mixed with it and consult the engine operation and maintenance manual
High coolant temperature shut downLow coolant level; blocked radiator shroud and ducting; leaks in coolant hoses, engine block or water pump; loose serpentine drive belt for the water pump; engine overheatingCheck the coolant level in the overflow jug; restart the engine and read the coolant temperature to verify High Coolant Temperature Shut down, stopping the engine immediately if the coolant temperature is 230°F (110°C) or more; allow the engine to cool, add coolant to the overflow jug if it is low and check the level of coolant in the radiator, adding coolant until it is 3/4" below the filler neck and securing the radiator cap; check the radiator shroud and ducting for blockage and remove any foreign matter; inspect coolant hoses, engine block and water pump for visible leaks; check the tension of the serpentine drive belt for the water pump; if no other problems are found, remove the load on the generator and restart the engine, checking the coolant temperature and shutting the engine down immediately if it starts to overheat, and consult the engine operation and maintenance manual
Overcrank shut downLow fuel level in tank; improper operation of the fuel pump; blocked air filter; engine will not startCheck the fuel level in tank; check for proper operation of the fuel pump; check air filter for blockage; if the engine will not start, consult the engine operation and maintenance manual for additional information on troubleshooting starting problems
Overspeed or underspeed shut downFrequency above or below 60.0 Hz; engine speed requires adjustmentDisconnect all loads and restart the generator, reading the frequency (Hz) on the LCD display (with no loads the frequency should read 60.0 Hz); if the frequency is above or below 60.0 Hz, adjust the engine speed — see the engine manual for throttle adjustments on mechanical governed units and the electronic governor manual for electronically controlled units

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing. Full Magnum MMG185 troubleshooting guide (12 entries) →

Parts

2
Part #DescriptionQtySystem
100-001Air Filter1Air filter Amazon Amazon eBay eBay
30175Decal, UN31A tank caution1Service part / kit Amazon eBay NAPA $12.21 FridayParts $85.00

Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.

Fuel consumption

RatingLoadL/hgal/h
Prime65.817.38
Prime50%28.86.6
Prime75%43.29.5
Prime100%28.07.4
Standby100%28.07.4

Available documents

Spec sheet — MMG185 Mobile (Magnum)Operator's manual — 26277 (Magnum)Service manual — MMG235 (Operation) (Magnum)