Home›Repair guides›Magnum›Changing Output Voltage (MMG235 Only)

Magnum — Changing Output Voltage (MMG235 Only)

Adjustments · Reconnect board

From a Magnum operator's manual covering: MMG120, MMG120 Super Start, MMG150D, MMG150D Super Start, MMG185, MMG185D Super Start, MMG235, MMG235 Super Start. Check it applies to your exact model before use.

Applies to: Magnum MMG120, Magnum MMG150D, Magnum MMG185, Magnum MMG235, Magnum MMG235 Super Start, John Deere PE4045HF285 engine, John Deere PE6068HF485 engine

Before you start

  • Never change voltage while engine is running.

Procedure

  1. Shut down generator; main breaker and control power OFF.
  2. Remove reconnect box door.
  3. Remove all 1/2 inch nuts holding shorting board.
  4. Move board to upper position for 208/120V 3Ø.
  5. Move board to lower position for 480/277V 3Ø.
  6. Replace hardware and tighten to 25 ft-lbs.
  7. Reinstall reconnect box door.
  8. Start generator and verify voltage.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • 25 ft-lbs

Source: Magnum operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.

More Magnum repair guides →