HomeEnginesJohn Deere PE4045HF285

John Deere PE4045HF285 Engine

The John Deere PE4045HF285 is a 4.5 L turbocharged engine rated at 1800 rpm, producing up to 86 kW. It powers generator sets from Generac and Magnum, including the MMG150D, MMG100, MMG120 and MMG120 Super Start. It holds 13.7 L (3.6 gal) of oil and 29.8 L (7.9 gal) of coolant.

Also known as: John Deere PE4045HF285

4.5 L
Displacement
1800 rpm
Rated speed
86 kW
Gross power
13.7 L
Oil capacity

Engine specifications

Oil capacity13.7 L
Coolant capacity29.8 L
Displacement4.5 L
Aspirationturbocharged
Rated speed1800 rpm
Gross power86 kW

Common problems

15
  • Warning (WRN) WRN
  • Sensor fail (FLS) SD
  • OVERSPEED OR UNDERSPEED SHUT DOWN
    Cause: Engine speed is above or below 60.0 Hz.
    Fix: Disconnect all loads and restart the generator to read frequency (Hz). Adjust engine speed as necessary.
  • OVERCRANK SHUT DOWN
    Cause: Engine will not start.
    Fix: Check fuel level in tank and proper operation of the fuel pump. Check air filter for blockage.
  • LOW OIL PRESSURE SHUT DOWN
    Cause: Engine oil pressure is less than 20 psi (138 kPa).
    Fix: Check engine oil level and add oil if required. Visually inspect the engine for oil leaks.
  • LOW FUEL LEVEL SHUT DOWN
    Cause: Fuel level on the Liquid Crystal Display (LCD) window is low or fuel tank has leaks.
    Fix: Check the fuel level and ensure it is not running dry. Check for leaks in the fuel tank.
  • LOW COOLANT LEVEL SHUT DOWN
    Cause: Coolant level in the radiator is low or coolant lines have visible leaks.
    Fix: Check the coolant level and add coolant if necessary. Inspect for leaks in coolant hoses, engine block, and water pump.
  • HIGH COOLANT TEMPERATURE SHUT DOWN
    Cause: Coolant temperature is 230°F (110°C) or more.
    Fix: Check coolant level in the overflow jug and add coolant if necessary. Inspect radiator, coolant hoses, engine block, water pump for leaks. Check serpentine drive belt tension.
  • OVERSPEED OR UNDERSPEED SHUTDOWN
    Cause: Engine speed is above or below 60.0 Hz.
    Fix: Disconnect loads and adjust engine speed as needed based on manual instructions.
  • OVERCRANK SHUTDOWN
    Cause: Engine will not start.
    Fix: Check fuel level, fuel pump operation, air filter for blockage. Refer to manual for additional troubleshooting.
  • LOW OIL PRESSURE SHUTDOWN
    Cause: Oil pressure is less than 20 psi (138 kPa).
    Fix: Check oil level, inspect for leaks, and check the oil pressure sender.
  • LOW FUEL LEVEL SHUTDOWN
    Cause: Fuel level in the tank is low or fuel lines are running dry.
    Fix: Check and refill the fuel level. Inspect for leaks and check the fuel level sender.
  • LOW COOLANT LEVEL SHUTDOWN
    Cause: Coolant level in the radiator is low.
    Fix: Check coolant level, inspect hoses, engine block, water pump for leaks, and check oil for coolant contamination.
  • HIGH COOLANT TEMPERATURE SHUTDOWN
    Cause: Coolant temperature is 230°F (110°C) or more.
    Fix: Check coolant level, remove any blockages, inspect hoses and components for leaks, check water pump belt tension, and load the unit to prevent overheating.
  • Warning: Generator Line 1 Voltage < V Wrn Gen L1<V

Compiled from service & troubleshooting documentation across every generator set that uses the John Deere PE4045HF285.

Maintenance schedule

ItemSpecCapacityPart #Interval
Air filter
Fuel filter
Oil filter
Battery
Belt
Coolant
Coolant filter
Oil
Spark plug

Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.

Common questions

What is the oil capacity of the John Deere PE4045HF285?

The John Deere PE4045HF285 engine has an oil capacity of 13.7 liters.

What is the displacement of the John Deere PE4045HF285?

The John Deere PE4045HF285 has a displacement of 4.5 liters.

Which generators use the John Deere PE4045HF285 engine?

The John Deere PE4045HF285 powers 9 generator set(s), including Generac MMG150D, Magnum MMG100, Magnum MMG120, Magnum MMG120 Super Start, Magnum MMG120CAN6.

What is a common problem with the John Deere PE4045HF285 engine?

A commonly reported issue on generators using the John Deere PE4045HF285 is: Warning (WRN).