Magnum MMG100 Generator Set

The Magnum MMG100 is a 86 kW (107 kVA) diesel standby generator set powered by a John Deere PE4045HF285 engine. It is available at 120/240 V, 120/208 V and 277/480 V, single-phase, 60 Hz and rated 96 A. It holds about 15.5 L (4.1 gal) of oil and 29.8 L (7.9 gal) of coolant, with a maximum ambient rating of 48.89 °C. Starting uses 1 battery rated 720 CCA at 12 V. The set measures 4010×1520×2130 mm (157.9×59.8×83.9 in), weighs about 1543 kg (3402 lb) and produces 68 dBA at 7.01 m. An integrated tank holds 556.4 L (147.0 gal), roughly 22 hours of runtime.

86 kW
Standby
4.5 L
Displacement
15.5 L
Oil capacity
1
Document types

Typical fuel consumption for 80–85 kW Diesel generators →

Compare with other 80–85 kW Diesel generators →

Service parts for the MMG100

Grouped by system, with how many of each the parts manual calls for.

Air intake

1 required
25-1476Air filtersee priceAmazon

Fuel system

1 required
25-1639Fuel filtersee priceAmazon

Oil system

1 required
25-1648Oil filtersee priceAmazon

Electrical

1 required
RC115Batterysee priceeBay

Prices captured from merchant listings; some links are affiliate links. Confirm against your serial number before ordering.

Specifications

Fueldiesel
Frequency60.0 Hz
Standby power86 kW
Standby kVA107
Prime power78 kW
EmissionsTier III
ControllerMagnum Digital (MDC), Power Zone
Oil capacity15.5 L
Voltage options120/240 V, 120/208 V, 277/480 V
Phasesingle phase / three phase (selectable via selector switch)
Rated current96 A
Power factor0.8
Circuit breaker400 A
Battery cranking720 CCA
Battery voltage12 V
Battery quantity1
Max ambient48.89 °C
Dimensions (L×W×H)4010×1520×2130 mm
Dry weight1543 kg
Wet weight1978 kg
Sound level68.0 dBA @ 7.01 m
Fuel tank556.4 L
Tank runtime22 hr

Engine

John Deere PE4045HF285
Oil capacity13.7 L
Coolant capacity29.8 L
Displacement4.5 L
Aspirationturbocharged
Rated speed1800 rpm

Maintenance & consumables

for the John Deere PE4045HF285
ItemSpecCapacityPart #Interval
Air filterAir Filter Minders25-1476 Amazon eBay
Fuel filterFuel Filters25-1639 Amazon eBay
Oil filterOil Filters25-1648 Amazon eBay
Battery12VDC SuperStart RC115×1RC115 eBay
Belt—500 hr
Coolant—
Coolant filter—
Oil12.0—250 hr
Spark plug—

Service specifications

18
TypeItemValueUnitCondition
OtherFuel level shutdown5%shutdown
OtherFuel level warning15%warning
OtherGenerator over frequency electrical trip110%electrical trip
OtherGenerator over frequency warning105%warning
OtherGenerator under frequency electrical trip90%electrical trip
OtherGenerator under frequency warning95%warning
PressureOil pressure shutdown20psishutdown
PressureOil pressure warning25psiwarning
SpeedOverspeed protection shutdown115%shutdown
TemperatureCoolant freeze protection-25F
TemperatureCoolant temperature shutdown230°Fshutdown
TemperatureCoolant temperature warning220°Fwarning
VoltageBattery voltage over15VDCover
VoltageBattery voltage under11VDCunder
VoltageGenerator over voltage electrical trip111%electrical trip
VoltageGenerator over voltage warning110%warning
VoltageGenerator under voltage electrical trip86%electrical trip
VoltageGenerator under voltage warning87%warning

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
Coolant60/4060/40 Coolant - cold weather applications (option)
Fueldiesel147.0 galSteel, single wall fuel tank built into skid; 22 hr run time at full load

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
120/208Vthree phaseLow WyeStandard selector switch mode
120/240Vsingle phaseZig ZagStandard selector switch mode
120/240Vthree phaseDeltaOptional 4 position phase switch
277/48033 position voltage selector switch12 lead reconnectableGenerator end is 12 lead reconnectable; NON-PMG (no permanent magnet generator)
277/480Vthree phaseHigh WyeStandard selector switch mode

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

What size generator is the Magnum MMG100?

The Magnum MMG100 is rated 86 kW standby (107.0 kVA).

Which engine powers the Magnum MMG100?

The Magnum MMG100 is powered by the John Deere PE4045HF285 engine.

Is the Magnum MMG100 diesel or gas?

The Magnum MMG100 runs on diesel.

What's the oil capacity on a Magnum MMG100?

The John Deere PE4045HF285 engine in the Magnum MMG100 has an oil capacity of 13.7 liters.

What is the cooling system capacity of the Magnum MMG100?

The Magnum MMG100 cooling system holds 29.8 liters (7.9 US gallons) for the engine, per the manufacturer specification sheet.

What is the continuous rating of the Magnum MMG100?

The Magnum MMG100 is rated 78 kW prime (98 kVA), against 86 kW standby.

What is the sound level of the Magnum MMG100?

The Magnum MMG100 is rated at 68.0 dBA at 7.01 m, per the manufacturer specification sheet.

What is the dry weight of the Magnum MMG100?

The Magnum MMG100 has a dry weight of 1543 kg (3401 lb).

What size fuel tank does the Magnum MMG100 have?

The Magnum MMG100 has a 556.4 liter (147 US gallon) fuel tank, giving about 22 hours of runtime.

What voltages is the Magnum MMG100 available in?

The Magnum MMG100 is offered in 120/240 V, 120/208 V, 277/480 V, single phase / three phase (selectable via selector switch)-phase.

What size battery does the Magnum MMG100 need?

The Magnum MMG100 uses 1 battery, 12 V each, 720 CCA, per the manufacturer specification sheet.

What oil filter does the Magnum MMG100 use?

The Magnum MMG100 uses oil filter part number 25-1648.

What fuel filter does the Magnum MMG100 use?

The Magnum MMG100 uses fuel filter part number 25-1639.

What air filter does the Magnum MMG100 use?

The Magnum MMG100 uses air filter part number 25-1476.

Troubleshooting

57

Fault codes

CodeMeaningCauseRemedy
3Battery Flat — If the controller switches off during starting sequence due to bad battery condition, it doesn't try to start again and activates this protection.
4Binary Input — Configurable warning/shutdown alarms on the inputs of IL-NT.
5ChrgAlternFail — Failure of the alternator to charge the battery.
6EmergencyStop — If the input Emergency Stop is opened (pushed in), shutdown is immediately activated.
7Engine Temp Sd — Water temperature is greater than Sd Water Temp setpoint.
8Engine Temp Wrn — Water temperature is greater than Wrn Water Temp setpoint.
9Fgen<, > — The generator frequency is out of limits given by Gen >f and Gen <f setpoints.
10Fuel Level Sd — Fuel level is smaller than Sd Fuel Level setpoint.
11Fuel Level Wrn — Fuel level is smaller than Wrn Fuel Level setpoint.
12GCB fail — Failure of the generator circuit breaker.
13Igen unbl — The generator current is unbalanced.
14Low BackupBatt — RTC backup battery is flat.
15Oil Press Sd — Oil pressure is smaller than Sd Oil Press setpoint.
16Oil Press Wrn — Oil pressure is smaller than Wrn Oil Press setpoint.
17Overload — The load is greater than the value given by Overload setpoint.
18Overspeed — The protection comes active if the speed is greater than Overspeed setpoint.
19ParamFail — Wrong checksum of parameters. Happens typically after downloading new firmware or changing of the parameter. The controller stays in INIT mode.Wrong checksum of parameters; happens typically after downloading new firmware or changing of the parameter.Check all parameters write at least one new parameter.
20PickupFault — Failure of the magnetic pick-up sensor for speed measurement.
21Sd IOM fail — IOM/IGS-PTM module.
22SprinkIActive — The protection is active if the output Sprinkler is closed.
23Start failed — Gen-set start failed.
24Stop fail — Gen-set stop failed.
25Ubat — Battery voltage is out of limits given by Batt Overvolt and Batt Undervolt setpoints.
26Underspeed — During starting of the engine, when the RPM reaches the value of Starting RPM setpoint, the starter is switched off and the speed of the engine can drop under Start RPM again. Then the underspeed protection becomes active. Protection evaluation starts 5 seconds after start up.
27Vgen<, > — The generator voltage is out of limits given by Gen <V and Gen <V setpoints.
SPN:100EngOil Press
SPN:102Boost Press
SPN:105Intake Temp
SPN:110EngCool Temp
SPN:175EngOil Temp
SPN:629Controller #1
SPN:636PositionSensor
SPN:637TimingSensor
SPN:651InjectorCyl#1
SPN:652InjectorCyl#2
SPN:653InjectorCyl#3
SPN:654InjectorCyl#4
SPN:655InjectorCyl#5
SPN:656InjectorCyl#6
SPN:677EngStartRelay
SPN:1485ECU MainRelay
WrnMaintenanceWrnMaintenance — The period for servicing is set by the WrnMaintenance setpoint. The protection comes active if the running hours of the engine reach this value.Reset the running hours to 250: with the unit shut down, power up the controller with the CONTROL ON/OFF toggle switch; press the PAGE SELECT button; press the down button to move the > cursor down to the Engine Protect line of text; press ENTER; press ENTER again; press the up button and reset the current run time hour setting to 250; press ENTER to save the current run time hour setting; move the CONTROL ON/I toggle switch to the CONTROL OFF/O position
Wrn ECU AlarmWrn ECU Alarm — ECU alarm list is not empty.
Wrn RA15 failWrn RA15 fail — Warning alarm in case of lost connection to IGL=RA15 module.

Symptoms & remedies

SymptomCauseRemedy
Low Fuel Level ShutdownFuel level low; fuel tank leak or tank running dry; fuel level sender and connecting wiring damaged.Check the fuel level on the LCD window and confirm the generator is sitting level; check for leaks in the fuel tank; check the fuel level sender and the connecting wiring for damage and check for continuity between the sender and the engine controller.
Low Oil Pressure ShutdownEngine oil level low; oil leaks; loss of oil pressure; oil pressure sender fault.Check the level of the engine oil with the dipstick and add oil if required; visually inspect the engine for oil leaks; restart the unit and verify the loss of oil pressure, shutting the engine down immediately if the oil pressure value does not read 5 psi (34 kPa) within five seconds; check the oil pressure sender and refer to the troubleshooting section of the engine operation and maintenance manual.
Low Coolant Level ShutdownCoolant level low; visible leaks in coolant hoses, engine block or water pump; coolant mixed with engine oil.Allow the engine to cool; check the coolant level in the radiator and add coolant until it is 3/4" below the filler neck, then secure the radiator cap; inspect coolant hoses, engine block and water pump for visible leaks; check engine oil to verify no coolant has mixed with it and consult the ENGINE OPERATION & MAINTENANCE MANUAL.
High Coolant Temperature ShutdownCoolant level low; radiator shroud and ducting blockage; visible leaks in coolant hoses, engine block or water pump; loose serpentine drive belt for the water pump; engine overheating.Check the coolant level in the overflow jug; restart the engine and read the coolant temperature, stopping the engine immediately if the coolant temperature is 230°F (110°C) or more; allow the engine to cool, add coolant to the overflow jug if low and check the radiator level, adding coolant until it is 3/4" below the filler neck; check the radiator shroud and ducting for blockage and remove any foreign matter; inspect coolant hoses, engine block and water pump for visible leaks; check the tension of the serpentine drive belt for the water pump; if no other problems are found, remove the load on the generator and restart the engine, checking the coolant temperature and shutting the engine down immediately if it starts to overheat, and consult the engine operation and maintenance manual.
Overcrank ShutdownFuel level low; fuel pump not operating properly; air filter blockage; engine will not start.Check the fuel level in the tank; check for proper operation of the fuel pump; check air filter for blockage; if the engine will not start, consult the ENGINE OPERATION AND MAINTENANCE MANUAL for additional information on troubleshooting starting problems.
Overspeed or Underspeed ShutdownFrequency above or below 60.0 Hz with no loads on the generator, requiring engine speed adjustment.Disconnect all loads and restart the generator, read the frequency (Hz) on the LCD display (should read 60.0 Hz with no loads); if the frequency is above or below 60.0 Hz, adjust the engine speed — see the engine manual for throttle adjustments on mechanical governed units and the electronic governor manual for electronically controlled units.
Wet StackingDiesel engine run at less than 35% of its full load capacity, causing unburned fuel to accumulate in the exhaust system; can also cause fouling of injectors and buildup on engine valves.Load the unit heavily for five hours or until the exhaust is clear; diesel engines operate properly when applied loads are between 35% and 100% capacity.
Low fuel level shutdownFuel level low; fuel tank leak; fuel level sender or connecting wiring damagedCheck the fuel level on the LCD window and confirm the generator is sitting level; check for leaks in the fuel tank; check the fuel level sender and the connecting wiring for damage and check for continuity between the sender and the engine controller
Low oil pressure shutdownEngine oil level low; oil leaks; loss of oil pressure; oil sender faultCheck the level of the engine oil with the dipstick and add oil if required; visually inspect the engine for oil leaks; restart the unit and verify the loss of oil pressure, shutting the engine down immediately if the oil pressure value does not read 5 psi (34 kPa) within five seconds; check the oil sender and refer to the troubleshooting section of the engine operator's manual
Low coolant level shutdownCoolant level low; coolant leaks; coolant mixed with engine oilAllow the engine to cool; check the coolant level in the radiator and add coolant until it is 3/4 in. (1.9 cm) below the filler neck; inspect coolant hoses, engine block and water pump for visible leaks; check the engine oil to verify no coolant has mixed with it and consult the engine operator's manual
High coolant temperature shutdownCoolant level low; radiator shroud and ducting blockage; coolant leaks; loose serpentine drive belt for the water pump; engine overheatingCheck the coolant level in the overflow jug; restart the engine and read the coolant temperature to verify a high coolant temperature shutdown, stopping the engine immediately if the coolant temperature is 230°F (110°C) or more; allow the engine to cool, add coolant to the overflow jug if it is low and check the level of coolant in the radiator, adding coolant until it is 3/4 in. (1.9 cm) below the filler neck; check the radiator shroud and ducting for blockage and remove any foreign matter; inspect coolant hoses, engine block and water pump for visible leaks; check the tension of the serpentine drive belt for the water pump; if no other problems are found, remove the load on the generator and restart the engine, checking the coolant temperature and shutting the engine down immediately if it starts to overheat, and consult the engine operator's manual
Overcrank shutdownFuel level low; fuel pump not operating properly; air filter blocked; engine will not startCheck the fuel level in the tank; check for proper operation of the fuel pump; check the air filter for blockage; if the engine will not start, consult the engine operator's manual for additional information on troubleshooting starting problems
Overspeed or underspeed shutdownEngine speed not adjusted (frequency above or below 60.0 Hz)Disconnect all loads and restart the generator and read the frequency (Hz) on the LCD display (with no loads the frequency should read 60.0 Hz); if the frequency is above or below 60.0 Hz, adjust the engine speed per the engine operator's manual for throttle adjustments on mechanical governed units and the electronic governor manual for electronically controlled units

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.

Parts

48
Part #DescriptionQtySystem
100-001Air Filter1Air filter Amazon Amazon eBay eBay
25-1476Air Filter Minders1Air filter Amazon eBay
25-1483Primary Air Cleaners1Air filter Amazon eBay
25-1639Fuel Filters1Fuel filter Amazon eBay
25-1648Oil Filters1Oil filter Amazon eBay
352793Oil Filter1Oil filter Amazon
C04521Element, Oil FilterOil filter Amazon eBay $24.99 NAPA $28.76
CO2775Element, Fuel Water SeparatorFuel filter Amazon eBay
CO2776Element, Fuel Filter PrimaryFuel filter Amazon eBay
G030071Air Cleaner Element (Engine) SecondaryAir filter Amazon eBay
G030073Air Cleaner Element (Engine) PrimaryAir filter Amazon eBay
G030074Air Cleaner Element (Engine) SecondaryAir filter Amazon eBay
G122208Clarke Eng Fluid - 5 galFluid Amazon eBay
G122209Clarke Eng Fluid -1 galFluid Amazon eBay
G30070Air Cleaner Element (Engine) PrimaryAir filter Amazon eBay
GM32809FILTER, OIL1Oil filter Amazon Amazon Amazon Amazon eBay $26.25 NAPA $28.76
GM50006Fuel Filter1Fuel filter Amazon eBay $26.99 NAPA $44.17
GM50074Fuel Filter (primary)1Fuel filter Amazon eBay $70.33 NAPA $38.35
GM66704-1Fan Belt (12V)1Belt Amazon eBay
GM66704-2Fan Belt (24V)1Belt Amazon eBay
GM77161Oil Filter1Oil filter Amazon eBay
PP88S12Pump PP88S121Pump Amazon eBay
01615Enclosure PanelsService part / kit Amazon eBay
01616Unit Decals - Left Side - MMG120Service part / kit Amazon eBay
12142Decal, ground1Service part / kit Amazon eBay NAPA $74.66
18396Decal, Panel Light Switch, Single1Service part / kit Amazon eBay KuduParts $53.00
21259Decal, Battery Charger (Optional)1Service part / kit Amazon eBay NAPA $86.31
22870Decal, Caution for 480V CSA1Service part / kit Amazon eBay
23597Decal, Panel Light Switch (Optional)1Service part / kit Amazon eBay
23827Decal, Controller Switches1Service part / kit Amazon eBay
23846Decal, Controller Instructions1Service part / kit Amazon eBay
24904Decal, 4 Pos. Outlet Usage in Delta (Optional for MMG100CAN Only)1Service part / kit Amazon eBay
28964Decal, Engine Block Heater (Optional)1Service part / kit Amazon eBay NAPA $44.60
30175Decal, UN31A tank caution1Service part / kit Amazon eBay NAPA $12.21 FridayParts $85.00
30176Decal, Flex - Tier III1Service part / kit Amazon eBay FridayParts $109.99
31024Decal, Fan Clutch (Optional)1Service part / kit Amazon eBay
33787Decal, Generator - Voltage Configuration (MMG100CAN6 Only)1Service part / kit Amazon eBay
34274Decal, Generator - 600V Circuit Breakers (MMG100CAN6 Only)1Service part / kit Amazon eBay
34275Decal, Caution - 120V & 240V Outlets1Service part / kit Amazon eBay
G122189250 hour Maintenance Kit (without fluids)Service part / kit Amazon eBay
G122190250 hour Maintenance Kit (without fluids)Service part / kit Amazon eBay
G122194250 hour Maintenance Kit (& engine fluids)Service part / kit Amazon eBay
G122195250 hour Maintenance Kit (& engine fluids)Service part / kit Amazon eBay
G122199500 hour Maintenance Kit (without fluids)Service part / kit Amazon eBay
G122200500 hour Maintenance Kit (without fluids)Service part / kit Amazon eBay
G122204500 hour Maintenance Kit (& Engine fluids)Service part / kit Amazon eBay
G122205500 hour Maintenance Kit (& Engine fluids)Service part / kit Amazon eBay
RC11512VDC SuperStart RC115 battery1Service part / kit eBay

Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.

Fuel consumption

RatingLoadL/hgal/h
Prime6.324.0
Prime50%11.73.1
Prime75%17.84.7
Prime100%23.56.2
Standby6.324.0

Available documents

Spec sheet — MMG100 Mobile (Magnum)Spec sheet — Magnum-MMG100-spec-sheet (Magnum)Reference — Magnum-MMG100-John-Deere-engine-SN-PE4045L267844-load-test-and-checklist-inspect (Charles Equipment)