HomeEnginesJohn Deere PE6068HF485

John Deere PE6068HF485 Engine

The John Deere PE6068HF485 is a 6.8 L 6-cylinder turbocharged engine rated at 1800 rpm, producing up to 213 kW. It powers generator sets from John Deere and Magnum, including the MMG235, MMG185, MMG185D Super Start and MMG185DCAN6. It holds 13.7 L (3.6 gal) of oil and 29.8 L (7.9 gal) of coolant.

Also known as: John Deere PE6068HF485

6.8 L
Displacement
6
Cylinders
1800 rpm
Rated speed
213 kW
Gross power

Engine specifications

Oil capacity13.7 L
Coolant capacity29.8 L
Displacement6.8 L
Cylinders6
Aspirationturbocharged
Rated speed1800 rpm
Gross power213 kW

Common problems

15
  • Warning (WRN) WRN
  • Sensor fail (FLS) SD
  • OVERSPEED OR UNDERSPEED SHUT DOWN
    Cause: Engine speed is above or below 60.0 Hz.
    Fix: Disconnect all loads and restart the generator to read frequency (Hz). Adjust engine speed as necessary.
  • OVERCRANK SHUT DOWN
    Cause: Engine will not start.
    Fix: Check fuel level in tank and proper operation of the fuel pump. Check air filter for blockage.
  • LOW OIL PRESSURE SHUT DOWN
    Cause: Engine oil pressure is less than 20 psi (138 kPa).
    Fix: Check engine oil level and add oil if required. Visually inspect the engine for oil leaks.
  • LOW FUEL LEVEL SHUT DOWN
    Cause: Fuel level on the Liquid Crystal Display (LCD) window is low or fuel tank has leaks.
    Fix: Check the fuel level and ensure it is not running dry. Check for leaks in the fuel tank.
  • LOW COOLANT LEVEL SHUT DOWN
    Cause: Coolant level in the radiator is low or coolant lines have visible leaks.
    Fix: Check the coolant level and add coolant if necessary. Inspect for leaks in coolant hoses, engine block, and water pump.
  • HIGH COOLANT TEMPERATURE SHUT DOWN
    Cause: Coolant temperature is 230°F (110°C) or more.
    Fix: Check coolant level in the overflow jug and add coolant if necessary. Inspect radiator, coolant hoses, engine block, water pump for leaks. Check serpentine drive belt tension.
  • Warning: Generator Line 1 Voltage < V Wrn Gen L1<V
  • SprinkIActive WRN
  • Shutdown: Generator Line 3 Voltage < V Sd Gen L3 <V
  • Shutdown: Generator Line 2 Voltage < V Sd Gen L2 <V
  • Shutdown: Generator Line 1 Voltage < V Sd Gen L1 <V
  • OVERSPEED OR UNDERSPEED SHUTDOWN
    Fix: Disconnect all loads and r
  • OVERCRANK SHUTDOWN
    Fix: Check the fuel level in tank. Check for proper operation of the fuel pump. Check air filter for blockage. If the engine will not start, consult the engine operator’s manual for additional information on trouble-shooting starting problems.

Compiled from service & troubleshooting documentation across every generator set that uses the John Deere PE6068HF485.

Maintenance schedule

ItemSpecCapacityPart #Interval
Air filter
Fuel filter
Oil filter
Battery
Belt
Coolant
Oil
Spark plug

Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.

Common questions

What is the oil capacity of the John Deere PE6068HF485?

The John Deere PE6068HF485 engine has an oil capacity of 13.7 liters.

What is the displacement of the John Deere PE6068HF485?

The John Deere PE6068HF485 has a displacement of 6.8 liters with 6 cylinders.

Which generators use the John Deere PE6068HF485 engine?

The John Deere PE6068HF485 powers 7 generator set(s), including John Deere MMG235, Magnum MMG185, Magnum MMG185D Super Start, Magnum MMG185DCAN6, Magnum MMG235.

What is a common problem with the John Deere PE6068HF485 engine?

A commonly reported issue on generators using the John Deere PE6068HF485 is: Warning (WRN).