Magnum — Auto Exercise Timer
Operation · Magnum Digital Controller (MDC)
From a Magnum operator's manual covering: MMG320, MMG320 Super Start, MMG405, MMG405 Super Start, MMG465. Check it applies to your exact model before use.
Applies to: Magnum MMG320, Magnum MMG320 Super Start, Magnum MMG405, Magnum MMG405 Super Start, Magnum MMG465, John Deere RG6090HF485 engine, John Deere RG6135HF485 engine
Before you start
- The controller must be in AUTO mode to run at the programmed time.
Procedure
- Press the PAGE SELECT button until Password appears at the top of the screen.
- Press the down arrow to select Date/Time and press ENTER.
- Press the down arrow to select Timer1 Repeat and press ENTER; choose the day(s) and press ENTER.
- Select Timer1 ON Time and press ENTER; adjust the desired start time.
- Select Timer1Duration and press ENTER; set the run duration.
- Press PAGE SELECT three times to return to the main menu.
- Press the AUTO button to switch modes to automatic.
Full service-parts list: Magnum MMG320 →
Source: Magnum operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.