HomeGeneracGenerac RXSC100A3

Generac RXSC100A3 Generator Set

Generac RXSC100A3 generator set: . Specifications, engine details, filters, oil capacity and 3 document types.

3
Document types

How to read your Generac serial & model number →

Specifications

Ratings spec sheet not in our library yet — see the documents below.

Service specifications

35
TypeItemValueUnitCondition
OtherEngine Cooldown Timer60seconds
OtherEngine Warmup Delay5seconds
OtherEngine cool-down timer60seconds
OtherEngine warm up delay5seconds
OtherExerciser5 or 12minutesadjustable weekly/Bi-weekly/Monthly
OtherExerciser5 to 12minutesEvolution; Adjustable, Weekly/Bi-Weekly/Monthly
OtherExerciser5 to 30minutesPower Zone 200; Adjustable, Weekly/Bi-Weekly/Monthly
OtherExerciser5 to 60minutesPower Zone 410; Adjustable, Weekly/Bi-Weekly/Monthly
OtherExerciser (Evolution)5 to 12minutesAdjustable, Weekly/Bi-weekly/Monthly
OtherExerciser (Nexus)12minutesWeekly
OtherRated short circuit current, 100A rated switch10,000 RMS symmetrical amperes, 250 VAC maximumAprotected by a 100A maximum circuit breaker (Siemens types QP or BQ) or 150A maximum circuit breaker (Square D Q2, Westinghouse CA-CAH, General Electric TQ2 and Siemens QJ2)
OtherRated short circuit current, 200A rated switch22,000 RMS symmetrical amperesA240 VAC when protected by a circuit breaker without an adjustable short time response or by fuses
OtherRe-transfer time delay15seconds
OtherTimer to generator start10secondsfactory set, adjustable between 2-1500 seconds by a qualified dealer
SpeedFrequency across transfer switch terminals E1 and E2greater than 59Hzat maximum rated load
SpeedFrequency at terminals E1 to E260–62Hzno-load
TorqueConductor tightening torque, 100A switch50in-lbs (5.6 Nm)
TorqueConductor tightening torque, 150/200A switch275in-lbs (31 Nm)
TorqueControl wiring screw heads (straight bladed and cross-bladed)3.5in-lb (0.4 Nm)
TorqueUtility service circuit breaker, 100A models Type BQ50in-lbs. (5.6 Nm)
TorqueUtility service circuit breaker, 150/200A Type 225AF, Line375in-lbs (42.4 Nm)
TorqueUtility service circuit breaker, 150/200A Type 225AF, Load - ATS275in-lbs. (31 Nm)
TorqueUtility service circuit breaker, Siemens 150/200A Type QN, Line250in-lbs (28.2 Nm)
TorqueUtility service circuit breaker, Siemens 150/200A Type QN, Load - ATS275in-lbs. (31 Nm)
VoltageStandby voltage sensor65%for 5 seconds
VoltageTerminals E1 to E2240–246VACno-load
VoltageTerminals E1 to NEUTRAL120–123VACno-load
VoltageTerminals E2 to NEUTRAL120–123VACno-load
VoltageUtility Voltage Drop-out58-71%Evolution; Adjustable by a Qualified Dealer
VoltageUtility Voltage Drop-out75-80%Power Zone 200 or Power Zone 410; Adjustable
VoltageUtility Voltage Pickup79-90%Evolution; Adjustable by a Qualified Dealer
VoltageUtility Voltage Pickup84-89%Power Zone 200 or Power Zone 410; Adjustable
VoltageUtility voltage drop-out<65%
VoltageUtility voltage pickup>80%
VoltageVoltage across transfer switch terminals E1 and E2greater than 230VACat maximum rated load (240 VAC system)

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Checking Automatic Operation diagnostic
  1. Verify generator is OFF.
  2. Set the utility service disconnect circuit breaker of the transfer switch to OFF or OPEN.
  3. Verify switch is de-energized.
  4. Install front cover of the transfer switch.
  5. Set the utility service disconnect circuit breaker of the transfer switch to ON or CLOSED.
  6. Set the generator main circuit breaker to ON.
  7. On the generator panel, select AUTO.
  8. Set the utility service disconnect circuit breaker of the transfer switch to OFF or OPEN.
Generator Tests Under Load diagnostic

⚠ DO NOT OVERLOAD.

Tools: Voltmeter, Frequency meter

  1. Set the generator main circuit breaker to OFF or OPEN.
  2. Set the utility service disconnect circuit breaker to OFF or OPEN, and turn OFF all load circuit breakers.
  3. Manually actuate the transfer switch main contacts to the emergency (standby) position.
  4. Select MANUAL mode to start the generator; let it stabilize for a few minutes.
  5. Set the generator main circuit breaker to ON or CLOSED.
  6. Turn on electrical loads to the full rated wattage/amperage capacity of the generator. DO NOT OVERLOAD.
  7. With maximum rated load applied, check voltage and frequency across transfer switch terminals E1 and E2.
  8. Let the generator run under rated load for at least 30 minutes.
  9. Set main circuit breaker of the generator to the OFF or OPEN position.
  10. Let the generator run at no-load for several minutes, then shut down by selecting the OFF mode.
  11. Move the main switch contacts back to the utility position.
  12. Set the utility service disconnect circuit breaker of the transfer switch to ON or CLOSED.
Generator Voltage Checks diagnostic

⚠ Electrocution. High voltage is present at transfer switch and terminals.

Tools: Accurate AC voltmeter, Frequency meter

  1. On the generator panel, select the MANUAL mode of operation.
  2. Let the generator stabilize and warm up at no-load for at least five minutes.
  3. Set the generator's main circuit breaker (CB1) to its ON or CLOSED position.
  4. Check the no-load voltage and frequency across ATS terminal lugs E1 to E2; E1 to NEUTRAL and E2 to NEUTRAL.
  5. When generator supply voltage is correct, turn OFF the generator supply to the transfer switch.
  6. Set the generator main circuit breaker (CB1) to OFF or OPEN.
  7. On the generator panel, select the OFF mode to shut down the generator.
Testing The SACM diagnostic
  1. Turn on the utility supply to the ATS.
  2. Verify managed loads are powered and all LEDs illuminate on SACM.
  3. Press the TEST button on the SACM.
  4. Verify that all of the connected loads to be shed become disabled.
  5. After five (5) minutes verify A/C 1 is energized and Status LED A/C 1 is ON.
  6. After another 15 seconds, verify A/C 2 is energized and Status LED A/C 2 is ON.
  7. After another 15 seconds, verify Load A/C 3 is energized and Status LED Load A/C 3 is ON.
  8. After another 15 seconds, verify A/C 4 is energized and Status LED A/C 4 is ON.
Utility Voltage Checks diagnostic

⚠ Electrocution. High voltage is present at transfer switch and terminals.

Tools: Accurate AC voltmeter, Digital Multimeter (DMM) with LowZ setting

  1. Turn ON the utility power supply to the transfer switch using the utility service disconnect circuit breaker.
  2. With an accurate AC voltmeter, check for correct voltage across ATS terminal lugs N1 and N2; N1 to NEUTRAL and N2 to NEUTRAL.
Connecting Power Source and Generator Power Supply installation

⚠ Electrocution. Turn utility and emergency power supplies to OFF before connecting power source and load lines.

⚠ A jumper wire (B) bonds the upper and lower Neutral lugs. NEVER remove this wire.

  1. Connect utility supply at the utility service disconnect circuit breaker terminals N1 and N2.
  2. Connect utility neutral and ground to the Upper Neutral and Ground terminals.
  3. Connect generator to the generator terminals (E1 and E2) on the transfer mechanism.
  4. Connect the generator neutral wire to the lower neutral lug.
  5. Connect a subpanel supply to lower T1 and T2 Terminals.
Open Enclosure maintenance

⚠ Inner Panel only available in models that are Service Entrance Rated.

  1. Remove thumb screw (B).
  2. Slide slot (C) over retention tab.
  3. Lower cover until clear of top flange (D), and pull away from enclosure.
  4. Loosen nut (F) until it clears t-slot (H) in inner panel.
  5. Grasp inner panel at two cutouts (G) and tilt panel, passing nut through t-slot.
  6. Lower inner panel until clear of two retention slots (J), and pull away from enclosure.
Preparing for Maintenance maintenance

⚠ Automatic start-up. Disconnect utility power and render unit inoperable before working on unit.

  1. At the controller, turn the generator OFF.
  2. Set the MLCB (generator disconnect) on the generator to OFF (OPEN).
  3. Turn the main utility disconnect OFF (OPEN).
  4. Remove 7.5A fuse from the controller.
  5. Follow maintenance procedure(s).
  6. Turn the main utility disconnect ON (CLOSED).
  7. Install 7.5A fuse in controller.
  8. Put the generator into AUTO mode.
  9. Set the MLCB (generator disconnect) on the generator to ON (CLOSED).
SACM Fuse Service maintenance

Tools: Fuse removal and installation tool, Diagonal pliers

  1. Snap the fuse removal and installation tool free with an appropriate tool such as diagonal pliers.
  2. Use it to replace the fuse.
  3. Store the tool in the SACM housing retainer directly above the fuses, with the large thumb tab facing out.
Close to Generator Source Side operation

Tools: Manual operating handle

  1. Verify switch position by observing manual operation handle.
  2. With the handle inserted into the movable contact carrier arm, move the handle DOWN.
  3. Remove manual operating handle from movable contact carrier arm. Return handle to storage bracket.
Close to Utility Source Side operation

Tools: Manual operating handle

  1. Verify switch position by observing manual operation handle.
  2. With the handle inserted into the movable contact carrier arm, move handle UP.
  3. Remove manual operating handle from movable contact carrier arm. Return handle to storage bracket.
Manual Operation operation

⚠ Electrocution. Do not manually transfer under load.

Tools: Manual operating handle

  1. Verify the generator is in the OFF mode.
  2. Turn OFF both utility and emergency power supplies to the transfer switch.
  3. Note position of transfer mechanism main contacts (A) by observing the movable contact carrier arm.
  4. With handle inserted, move handle to the desired position.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
Generator control wiring (Class 1 signaling circuit)23 Transfer Control, 0 DC Ground, 194 +12 VDCControl system interconnections consist of N1, N2, and T1, and leads 23, 0, and 194
120/240VACsingle-phaseGenerator supplyE1, E2Connect generator to the generator terminals on the transfer mechanism
120/240VACsingle-phaseLoad / subpanel supplyT1, T2Connect subpanel supply to lower T1 and T2 Terminals
120/240VACsingle-phaseUtility supplyN1, N2Connect at utility service disconnect circuit breaker terminals

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Parts

34model family
Part #DescriptionQtySystem
085296SCREW HHC 1/4-20 X 1/2 SS1Bolt buy
0E3484DECAL WARN MANUAL OPER HANDLE1Decals buy
0H7274DECAL NEC COMPLIANCE1Decals buy
0K01120AL0RENCLOSURE 100/200A XFER SW_RAW1Enclosure buy
0K01130AL0RCOVER 100A XFER SWITCH_INST_RAW1Cover buy
0K1800DECAL TEST SEQUENCE 100/200A NON1Decals buy
0K8254U-CLIP ADHESIVE1Clip buy
0L1950DATA DECAL TSWS NON-SE1Decals buy
10000004183Installation DrawingInstallation drawing Amazon eBay $78.95
10000005117240 VAC, 6.3 Amps, 10,000 AIC1Fuse Amazon eBay $19.99
10000005872HARNESS 100/200A TS1Harness buy
10000008602DECAL WCR NEC COMPLIANCE1Decals buy
1000000944590 DEGREE STRAIGHT SPADE CONNECTOR4Connector buy
10000014617SUBPLATE 100/200A XFER SW1Subplate buy
10000037322DECAL PROP 65 EN/SP/FR1Decals buy
G074138LUG DIS QK NI-S 10X45 DEG BR/T1Lug buy
022152WASHER LOCK #101Service part / kit Amazon $23.99 eBay $12.00
026850WASHER SHAKEPROOF EXT 1/4 STEEL1Service part / kit Amazon eBay
026902SCREW HHTT #8-32 X 1/4 CZ5Service part / kit buy
036933PPHMS 10-32 X 3/8" LG4Service part / kit Amazon eBay $17.80
077033LUG SLDLSS 1/0-#14X9/16 AL/CU6Service part / kit Amazon eBay
0A2115WASHER NYLON M6-1/4”4Service part / kit Amazon eBay
0A9457DECAL NEUTRAL1Service part / kit Amazon eBay
0E6155ARM EXTENDER PIN1Service part / kit Amazon
0G3274DECAL LIVE CIRCUIT ENG/FRN/SPN1Service part / kit Amazon
0G8411NUT HEX FLANGE WHIZ 1/4-202Service part / kit Amazon
0J8202LUG SLDLSS 2/0-#14 AL9CU1Service part / kit Amazon
0K0108ASSY-NEUT BLK 100A1Service part / kit Amazon
0K1098DECAL RTS TRANSFER SW GENERAC1Service part / kit Amazon
0L2910XFRSW HSB 100A 2P 250V1Service part / kit buy
A0008188214Part No. A0008188214Service part / kit buy
G022473WASHER FLAT 1/4-M6 STEEL ZINC1Service part / kit Amazon
G074908SCREW HHTT M5-0.8 X 10 BP7Service part / kit Amazon
G090388SCREW HHTT M6-1.0 X 12 ZINC2Service part / kit Amazon

Compiled from this model's family documentation — may include parts for closely-related variants. Confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.

Available documents

Reference — Generac RXSW specs 2017 (Generac)Parts manual — 10000008120 (Generac)Service manual — 10000009569 (Generac)Service manual — 10000013459-(1) (Generac)Service manual — 10000013459-Rev-B (Generac)Service manual — 10000013459 (Generac)Service manual — generac datasheet stepid-2916807 (Generac)