Generac — Shutting Generator Down While Under Load or During a Utility Outage
Operation
From a Generac service manual covering: RXSC100A3, RXSC200A3, RXSW100A3, RXSW150A3, RXSW200A3. Check it applies to your exact model before use.
Browse Generac generators & specs →
Before you start
- Automatic start-up. Disconnect utility power and render unit inoperable before working on unit.
Procedure
- Set utility MLCB to OFF (OPEN).
- Set generator MLCB (generator disconnect) to OFF (OPEN).
- Allow generator to run for cool-down for approximately one minute.
- Set generator to OFF at the controller.
- Remove 7.5A fuse from controller.
- Install 7.5A fuse in controller.
- Verify generator MLCB (generator disconnect) is OFF (OPEN).
- Set generator to AUTO mode at the controller.
- Generator will start and run; allow warm up for a few minutes.
- Set generator MLCB (generator disconnect) to ON (CLOSED).
- Set utility MLCB to ON (CLOSED).
Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.