The Generac MD750 - GEM is a 750 kW #2D Diesel standby generator set powered by a Generac 12.0 DTA engine. It is available at 277/480 V and 600 V, 3-phase, 60 Hz and rated 1128 A. It holds about 31.04 L (8.2 gal) of oil and 83.3 L (22.0 gal) of coolant, with a maximum ambient rating of 50 °C. Starting uses 2 group-27 batteries rated 700 CCA at 12 V.

750 kW
Standby
11.9 L
Displacement
31.04 L
Oil capacity
1
Document types

How to read your Generac serial & model number →

Typical fuel consumption for 750–755 kW Diesel generators →

Compare with other 750–755 kW Diesel generators →

Specifications

Fuel#2D Diesel
Frequency60.0 Hz
Standby power750 kW
ControllerPowerManager Digital Platform
Oil capacity31.04 L
Voltage options277/480 V, 600 V
Phase3-phase
Rated current1128 A
Power factor0.8
Battery group27F
Battery cranking700 CCA
Battery voltage12V V
Battery quantity2
Coolant capacity83.3 L
Max ambient50 °C

Engine

Generac 12.0 DTA
Oil capacity31.04 L
Coolant capacity83.3 L
Displacement11.9 L
AspirationTurbocharged and Aftercooled
Rated speed2280 rpm

Maintenance & consumables

for the Generac 12.0 DTA
ItemSpecCapacityPart #Interval
Air filterDry—
Fuel filterOptional—
Oil filterfull flow and bypass—
CoolantPressurized, Closed Recovery83.3 liters—

Service specifications

7
TypeItemValueUnitCondition
OtherPiston speed11.4m/sec.60 Hz
PressureBMEP264psi60 Hz
PressureMax. external pressure drop after radiator0.5in. H2O
PressureMaximum recommended back pressure (exhaust)5.1kPaat rated output
SpeedCoolant flow/min.223liters/min60 Hz
SpeedRated RPM (engine, each)2280rpm60 Hz
TemperatureExhaust temperature at rated output (pre-turbo)732°Cat rated output

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
Fuel#2D (Min. Cetane #40)Fuel pump lift 40 in.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

1
Typical Operational Sequence operation
  1. A transfer switch in the PM-DCP configuration detects a utility failure and issues a start command.
  2. The command goes to the PM-SC which issues a start command to the PM-PCs.
  3. Each generator will start on its own.
  4. The first generator attaining rated frequency and voltage connects to the common generator bus via the switching mechanism.
  5. The second generator synchronizes and closes into the bus via the switching mechanism.
  6. When both gensets are paralleled to the bus, the PM-SC signals transfer switches to transfer to the load in up to 3 programmed steps.
  7. If an NFPA 10 second start requirement exists, the first unit connects to the bus so a separate emergency transfer switch transfers to the NFPA load.
  8. If a single generator fails, load shed contacts disconnect selected non critical loads.
  9. If load conditions are reduced (night time operation), one generator can be programmed off line (optional).
  10. When utility returns, PM-SC transfers loads back to utility and commands individual PM-PCs to disconnect from the bus.
  11. Each PM-PC operates its generator for the cool-down period and then issues a shutdown command.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

What size generator is the Generac MD750 - GEM?

The Generac MD750 - GEM is rated 750 kW standby.

What engine does the Generac MD750 - GEM use?

The Generac MD750 - GEM is powered by the Generac 12.0 DTA engine.

What fuel does the Generac MD750 - GEM use?

The Generac MD750 - GEM runs on #2D Diesel.

How much oil does the Generac MD750 - GEM take?

The Generac 12.0 DTA engine in the Generac MD750 - GEM has an oil capacity of 31.04 liters.

What is the cooling system capacity of the Generac MD750 - GEM?

The Generac MD750 - GEM cooling system holds 83.3 liters (22.0 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.

What voltage does the Generac MD750 - GEM produce?

The Generac MD750 - GEM is offered in 277/480 V, 600 V, 3-phase-phase.

What battery does the Generac MD750 - GEM use?

The Generac MD750 - GEM uses 2 batteryies, 12V V each, 700 CCA, group 27F, per the manufacturer specification sheet.

Repair guides

1

Step-by-step procedures compiled from the Generac service manual for this model.

Fuel consumption

RatingLoadL/hgal/h
Standby25%68.1418.0
Standby50%128.734.0
Standby75%184.7348.8
Standby100%238.4863.0

Available documents

Spec sheet — 0168820SBY (Generac)Spec sheet — 750 Gemini Spec Sheet (Generac)

This page was generated from the 2 manufacturer documents above by automated extraction; every figure shown is copied from one of them. How the data is compiled.