Generac GEM750 Generator Set

The Generac GEM750 is a 750 kW #2D (Min. Cetane #40) standby generator set powered by a Generac 12.0 DTA engine. It is available at 277/480 V and 600 V, 3-phase, 60 Hz and rated 1128 A. It holds about 31.04 L (8.2 gal) of oil and 83.3 L (22.0 gal) of coolant, with a maximum ambient rating of 50 °C. Starting uses 2 group-27 batteries rated 700 CCA at 12 V.

750 kW
Standby
11.9 L
Displacement
31.04 L
Oil capacity
1
Document types

How to read your Generac serial & model number →

Specifications

Fuel#2D (Min. Cetane #40)
Frequency60.0 Hz
Standby power750 kW
ControllerPowerManager Digital Platform (PM-DCP); PM-PC per; PM-SC system
Oil capacity31.04 L
Alternator12 Lead 375 kW 60 Hz Generator
Voltage options277/480 V, 600 V
Phase3-phase
Rated current1128 A
Power factor0.8
Battery group27F
Battery cranking700 CCA
Battery voltage12 V
Battery quantity2
Starting system24 V DC
Coolant capacity83.3 L
Max ambient50 °C

Engine

Generac 12.0 DTA
Oil capacity31.04 L
Coolant capacity83.3 L
Displacement11.9 L
AspirationTurbocharged and Aftercooled
Rated speed2280 rpm

Maintenance & consumables

for the Generac 12.0 DTA
ItemSpecCapacityPart #Interval
Air filterDry—
Fuel filterOptional—
Oil filterfull flow and bypass—
CoolantPressurized, Closed Recovery83.3 liters—

Service specifications

7
TypeItemValueUnitCondition
OtherPiston speed11.4m/sec.60 Hz
PressureBMEP264psi60 Hz
PressureMax. external pressure drop after radiator0.5in. H2O
PressureMaximum recommended back pressure (exhaust)5.1kPaat rated output
SpeedCoolant flow/min.223liters/min60 Hz
SpeedRated RPM (engine, each)2280rpm60 Hz
TemperatureExhaust temperature at rated output (pre-turbo)732°Cat rated output

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
Fuel#2D (Min. Cetane #40)Fuel pump lift 40 in.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

1
Typical Operational Sequence operation
  1. A transfer switch in the PM-DCP configuration detects a utility failure and issues a start command.
  2. The command goes to the PM-SC which issues a start command to the PM-PCs.
  3. Each generator will start on its own.
  4. The first generator attaining rated frequency and voltage connects to the common generator bus via the switching mechanism.
  5. The second generator synchronizes and closes into the bus via the switching mechanism.
  6. When both gensets are paralleled to the bus, the PM-SC signals transfer switches to transfer to the load in up to 3 programmed steps.
  7. If an NFPA 10 second start requirement exists, the first unit connects to the bus so a separate emergency transfer switch transfers to the NFPA load.
  8. If a single generator fails, load shed contacts disconnect selected non critical loads.
  9. If load conditions are reduced (night time operation), one generator can be programmed off line (optional).
  10. When utility returns, PM-SC transfers loads back to utility and commands individual PM-PCs to disconnect from the bus.
  11. Each PM-PC operates its generator for the cool-down period and then issues a shutdown command.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

What is the power rating of the Generac GEM750?

The Generac GEM750 is rated 750 kW standby.

What engine is in the Generac GEM750?

The Generac GEM750 is powered by the Generac 12.0 DTA engine.

What kind of fuel does the Generac GEM750 run on?

The Generac GEM750 runs on #2D (Min. Cetane #40).

How much oil does the Generac GEM750 take?

The Generac 12.0 DTA engine in the Generac GEM750 has an oil capacity of 31.04 liters.

What is the coolant capacity of the Generac GEM750?

The Generac GEM750 cooling system holds 83.3 liters (22.0 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.

What voltages is the Generac GEM750 available in?

The Generac GEM750 is offered in 277/480 V, 600 V, 3-phase-phase.

What size battery does the Generac GEM750 need?

The Generac GEM750 uses 2 batteryies, 12 V each, 700 CCA, group 27F, per the manufacturer specification sheet. The starting system is 24 V DC.

What alternator comes on the Generac GEM750?

The Generac GEM750 uses a 12 Lead 375 kW 60 Hz Generator alternator.

Repair guides

1

Step-by-step procedures compiled from the Generac service manual for this model.

Fuel consumption

RatingLoadL/hgal/h
Standby25%68.1418.0
Standby50%128.734.0
Standby75%184.7348.8
Standby100%238.4863.0

Available documents

Spec sheet — 0168820SBY (Generac)Spec sheet — 750 Gemini Spec Sheet (Generac)

This page was generated from the 2 manufacturer documents above by automated extraction; every figure shown is copied from one of them. How the data is compiled.