Specifications
| Frequency | 50.0 Hz |
|---|---|
| Standby power | 72 kW |
| Standby kVA | 90 |
| Prime power | 65 kW |
| Controller | DSE7320 |
| Oil capacity | 8.0 L |
| Alternator | Mecc Alte ECP 34-1S/4 (4-pole, Class H insulation) |
| Voltage options | 415/240 V, 400/230 V, 380/220 V, 240/139 V, 230/133 V, 220/127 V |
| Phase | 3 |
| Power factor | 0.8 |
| Battery voltage | 12 V |
| Dimensions (L×W×H) | 2950×1100×1759 mm |
| Dry weight | 1620 kg |
| Sound level | 62.0 dBA @ 7 m |
| Fuel tank | 220.0 L |
Engine
| Oil capacity | 8.0 L |
|---|---|
| Coolant capacity | 13.0 L |
| Displacement | 4.4 L |
| Aspiration | Turbocharged |
| Rated speed | 1500 rpm |
Maintenance & consumables
for the Perkins 1104A-44TG2| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Air filter | — | 1200 hr | find | ||
| Fuel filter | — | 1200 hr | find | ||
| Oil filter | 901103 | 1200 hr | PartsGeek kuduparts $25.00 | ||
| Belt | — | 1200 hr | find | ||
| Coolant | 13.0 | — | 1200 hr | ||
| Coolant filter | — | find | |||
| Oil | — |
Compatible filters for the Perkins 1104A-44TG2 — cross-referenced via Donaldson. Options to verify against your serial number, not confirmed for this exact unit.
- Air filter: Donaldson P778972 Donaldson P780012
Common questions
What is the power rating of the Erga ERP-80S?
The Erga ERP-80S is rated 72 kW standby (90.5 kVA).
What engine does the Erga ERP-80S use?
The Erga ERP-80S is powered by the Perkins 1104A-44TG2 engine.
What is the oil capacity of the Erga ERP-80S?
The Perkins 1104A-44TG2 engine in the Erga ERP-80S has an oil capacity of 8.0 liters.
What alternator does the Erga ERP-80S use?
The Erga ERP-80S uses a Mecc Alte ECP 34-1S/4 alternator. It has 4 poles. Insulation class H.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 50% | 9.7 | |
| Prime | 75% | 14.0 | |
| Prime | 100% | 18.7 |