Home›Cummins/Onan›Cummins/Onan YB series

Cummins/Onan YB series Generator Set

The Cummins/Onan YB series is a generator set. It is available at 50 V and 100 V.

1
Document types

How to read your Cummins/Onan serial & model number →

Service parts for the YB series

Grouped by system, with how many of each the parts manual calls for.

Air intake

1 required
91SdAir filtersee priceAmazon

Oil system

1 required
O9EP-Z19Oil filtersee priceAmazon

Prices captured from merchant listings; some links are affiliate links. Confirm against your serial number before ordering.

Specifications

AlternatorUV
Voltage options50 V, 300 V, 100 V, 600 V

Maintenance & consumables

ItemSpecCapacityPart #Interval
Air filter3%2Z6/A4091Sd Amazon eBay
Oil filterLHDI7 IO9EP-Z19 Amazon eBay

Service specifications

42
TypeItemValueUnitCondition
OtherCranking limiter time45- to 90seconds
OtherCycle cranker crank cycles3cycles15 seconds each, 10-second rest
OtherK11 oil pressure time-delay15secondsafter 24VDC applied
OtherOvercrank time limit70- to 80secondsnominal 75
PressureLow oil pressure cut-off switch closes12 to 16psi (83- to 110 kPa)
PressureLow oil pressure pre-alarm switch closes18 to 22psi (124- to 152 kPa)
ResistanceCR21 CR1 diode6- to 50ohmsohmmeter RX1
ResistanceCR21 CR2 diode6- to 50ohmsohmmeter RX1
ResistanceCR21 CR3 anode-cathodeInfinityohmsohmmeter RX10K
ResistanceCR21 CR3 gate-cathode6- to 50ohmsohmmeter RX1
ResistanceCR21 CR4 anode-AC1Infinityohmsohmmeter RX10K
ResistanceCR21 CR5 anode-AC2Infinityohmsohmmeter RX10K
ResistanceExciter rotor winding resistance0.1463- to 0.1788ohmsat 20°C (68°F)
ResistanceExciter stator winding resistance14.85- to 18.15ohmsat 20°C (68°F)
ResistanceGenerator rotor winding resistance1.646- to 2.695ohmsat 20°C (68°F)
ResistanceGenerator stator winding resistance0.00322- to 0.00394ohmsat 20°C (68°F)
ResistanceL1 commutating reactor coil resistance0.0693- to 0.0847ohmsat 20°C
ResistanceL2 reactor coil resistance308.8- to 377.4ohmsat 20°C
ResistanceSCR anode-cathode resistance1 megohm or greaterohmsohmmeter R x 10K
ResistanceSCR gate-anode shorted resistance25-ohms or lessohms
SpeedOverspeed switch closes2000- to 2200rpmnominal 2100
TemperatureHET pre-alarm switch closes200 to 210°F (93.3 to 98.9°C)
TemperatureHET shutdown switch closes210 to 220°F (98.9 to 104.4°C)
TemperatureHigh water temperature switch closes102°Capprox
TemperatureLET switch opens at85°F (29.4°C)nominal
TemperatureLow engine temperature light off at80 to 90°F (26.7 to 32.2°C)
TemperatureLow engine temperature light on below65°F (18.3°C)
TorqueBearing locknut150- to 200lb-ft (203- to 271 N·m)
TorqueDiode mounting on rotating exciter assembly15lb-in (1.7 N·m)
TorqueEnd bell bolts30- to 35lb-ft (40- to 48 N·m)
TorqueGenerator support bracket bolts195- to 200lb-ft (264- to 272 N·m)
TorqueRotor bolts120- to 125lb-ft (162- to 170 N·m)
TorqueStator bolts65- to 70lb-ft (88- to 95 N·m)
TorqueTwo-5/8-inch studs (support bracket)195- to 200lb-ft (264- to 272 N·m)
VoltageCR21 CR4 test voltageless than 3Volts6V battery with resistor, DC voltmeter
VoltageCR21 CR5 test voltageless than 3Volts6V battery with resistor, DC voltmeter
VoltageVR1 terminals 2 and 310- to 90VDCengine running
VoltageVR1 terminals 4 and 5 residual voltage20- to 24VACengine running
VoltageVR1 terminals 6 and 8120VAC
VoltageVR21 terminals + and -5 to 10VDC
VoltageVR21 terminals 1 and 25 to 10VAC
VoltageVR21 terminals 11 and 125 to 10VAC

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Voltage Adjustment (VR21) adjustment

Tools: screwdriver

  1. Center the voltage adjust knob so pointer is vertical.
  2. Open meter panel doors. Start unit.
  3. Using a screwdriver, turn R18 potentiometer on printed circuit board VR21.
  4. Observe voltmeter on meter panel while adjusting. Set voltage with no load connected. Example: for 120/240 volt connection, set at approximately 246 volts.
  5. If voltage is unstable or tends to hunt, turn R26 potentiometer to increase voltage dampening.
Checking Reactors diagnostic

Tools: Wheatstone bridge ohmmeter, Simpson 260 ohmmeter

  1. Measure L1 resistance across coil terminals; should be 0.0693- to 0.0847-ohms at 20°C.
  2. Set ohmmeter to R x 10K; measure between either coil terminal and frame. Less than infinity indicates low insulation; replace reactor.
  3. Measure L2 resistance across terminals 1 and 4; should be 308.8- to 377.4-ohms at 20°C, R x 1 scale.
  4. With R x 10K, reading less than infinity between any coil terminal and frame indicates low insulation; replace reactor.
  5. Measure continuity between terminal 1 or 4 and terminals 2 and 3 to verify taps are not broken.
Exciter Rotor diagnostic

Tools: Kelvin bridge, ohmmeter, wrench

  1. Use a Kelvin bridge instrument for this test.
  2. Remove rotating diodes CR1, CR2, CR3 from heat sinks.
  3. Measure resistance of rotor windings. Should be within 0.1463- to 0.1788-ohms at 20°C (68°F).
  4. Replace rotating diodes on heat sinks. Hold body with wrench while torquing to 15 lb-in (1.7 N·m).
  5. Using ohmmeter on R x 10K, measure between any rotating diode lead and generator frame. Less than infinity indicates low insulation.
Testing Diodes diagnostic

⚠ Excessive dust or dirt on diodes causes overheating and eventual failure. Keep assemblies clean.

Tools: ohmmeter

  1. Remove one diode at a time from heat sink. Test and reinstall before proceeding.
  2. Connect one ohmmeter lead to top of diode and other to diode stud. Observe reading.
  3. Reverse leads and again observe reading.
  4. A good diode has higher resistance in one direction than the other.
  5. If both readings are high or both low, diode is defective and must be replaced with identical part.
Testing Exciter Stator diagnostic

Tools: ohmmeter

  1. Testing for grounds: using ohmmeter on R x 10K, measure insulation resistance between either lead F1 or F2 and generator frame. Less than infinity indicates ground.
  2. Testing winding resistance: measure coil resistance between leads F1 and F2 with ohmmeter on R x 1.
  3. Resistance should be 14.85- to 18.15-ohms at 20°C (68°F).
Testing Generator Rotor diagnostic

Tools: ohmmeter, Wheatstone or Kelvin bridge

  1. Remove F+ and F- rotor leads from diode heat sink assemblies.
  2. Ground test: connect ohmmeter on R x 10K between either rotor lead and rotor shaft. Less than infinity indicates a ground.
  3. Winding resistance: use Wheatstone or Kelvin bridge. Connect meter leads between F+ and F-.
  4. Resistance should be 1.646- to 2.695-ohms at 20°C (68°F).
Testing Generator Stator diagnostic

Tools: ohmmeter, Wheatstone or Kelvin bridge

  1. Disconnect stator leads from bus bar assembly; observe wire identification.
  2. Connect all stator output leads (T1-T12) together.
  3. Use ohmmeter on R x 10K to measure insulation resistance between windings and stator frame. Less than infinity indicates ground.
  4. Testing for shorts: connect ohmmeter between each individual winding and other windings connected together. Repeat for all six coils.
  5. Measure resistance of windings using Wheatstone or Kelvin bridge. Readings should be 0.00322- to 0.00394-ohms at 20°C (68°F).
  6. If any windings are shorted, open, or grounded, replace stator assembly. Check leads for broken wires or damaged insulation.
Testing L21 Reactor diagnostic

Tools: ohmmeter

  1. L21 mounts inside control box, below VR21 voltage regulator.
  2. Coils 1-2 and 3-4 are wound on the same core.
  3. Resistance between 1-2 and 3-4 should be equal.
  4. Resistance between coils (e.g., 1-4) or from any terminal to frame should be infinity.
Testing Rectifier Bridge Assembly (CR21) diagnostic

Tools: ohmmeter, 6 volt dry cell battery, DC voltmeter

  1. Rectifier bridge located in control cabinet, below voltage regulator.
  2. Contains 3 diodes CR1, CR2, CR3 and two SCRs CR4, CR5 encapsulated in hermetically sealed box.
  3. Failure of any diode or SCR means entire unit must be replaced.
  4. Disconnect wires from rectifier unit prior to testing.
  5. Test unit in order shown in Table 2.
  6. Refer to Figure 24 for CR4 and CR5 test circuit.
  7. When test is complete and satisfactory, reconnect unit observing correct wiring hook-up.
Testing SCRs diagnostic

Tools: ohmmeter

  1. Remove voltage regulator VR1 cover to gain access to SCRs.
  2. SCRs on VR1 are identified CR1 and CR2, positioned closest to terminal board.
  3. Remove gate and cathode wires from SCR.
  4. Set ohmmeter to R x 10K scale.
  5. Measure resistance across anode and cathode; should be 1 megohm or greater.
  6. Reverse leads; reading should again be 1 megohm or greater.
  7. Set ohmmeter to R x 1 scale.
  8. Short gate to anode; resistance should drop to 25-ohms or less.
  9. Remove short between gate and anode; resistance should remain unchanged.
  10. Replace SCR if results differ.
Flashing Field (Section I) repair

⚠ High voltage will be present on voltage regulator terminals if output builds up.

⚠ Do not keep field flashing circuitry connected longer than 5 seconds or damage may occur.

Tools: six-volt supply, resistor, diode

  1. Assemble six-volt supply, resistor, and diode as shown in Figure 3.
  2. Remove frontal grille to access voltage regulator.
  3. Disconnect lead F1 at VR1-3.
  4. Start unit.
  5. Touch positive lead of supply to F1 and negative to VR1-2.
  6. Hold leads until voltage starts building.
  7. Shut down unit and reconnect wires.
Flashing the Field (Section II) repair

⚠ Do not keep excitation circuitry connected longer than 5-seconds, or damage may occur to the exciter regulator.

Tools: six volt supply, resistor, diode

  1. Assemble six volt supply, resistor, and diode as shown in Figure 21.
  2. If six volt supply not available, a 12-volt can be used; substitute a 20-ohm resistor for the 10-ohm.
  3. Start the generator set.
  4. Touch positive lead to + on rectifier bridge, and negative lead to - terminal.
  5. Hold leads on terminals just long enough for voltage to build up.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
120/2083series wye, parallel wye, or deltaFactory connected to customer requirements per Table 1
120/2403series wye, parallel wye, or deltaFactory connected to customer requirements per Table 1
220/3803series wye, parallel wye, or delta50 Hz; factory connected to customer requirements per Table 1
240/4163series wye, parallel wye, or deltaFactory connected to customer requirements per Table 1
240/4803series wye, parallel wye, or deltaFactory connected to customer requirements per Table 1
277/4803series wye, parallel wye, or deltaFactory connected to customer requirements per Table 1
347/6003series wye, parallel wye, or deltaFactory connected to customer requirements per Table 1

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

What voltage does the Cummins/Onan YB series produce?

The Cummins/Onan YB series is offered in 50 V, 300 V, 100 V, 600 V.

What alternator comes on the Cummins/Onan YB series?

The Cummins/Onan YB series uses a UV alternator.

Which oil filter part number does the Cummins/Onan YB series take?

The Cummins/Onan YB series uses oil filter part number O9EP-Z19.

What air filter does the Cummins/Onan YB series use?

The Cummins/Onan YB series uses air filter part number 91Sd.

Troubleshooting

6

Fault codes

CodeMeaning
CB1Circuit Breaker CB1

Symptoms & remedies

SymptomCauseRemedy
Starter will not crank.Possible fault location; Fault in Remote station or circuit to station. Starter relay not pulling in because— a. Starter relay K13 faulty. Ai2 printed circuit board faulty. All printed circuit board faulty. Relay K12 faulty. Overspeed switch stuck closed. Short to ground on overspeed switch wire. Starter fauity.1. Switch R-S-R- switch to Run. If starter cranks, problem is in Remote circuitry. Refer to troubleshooting guide condition B for this malfunction. 2. If starter does not crank with R-S-R- switch in Run, switch to Stop and check the following— a. Batteries for condition. Connections for security. b. Wiring to starter, and starter solenoid. Secure, clean, etc. 3. Open control cabinet. Check wiring to K13 starter solenoid; K12 Ignition relay; A11 Engine Monitor; A12 cranking control boards. 4. Toggle R-S-R- switch between Run and Stop positions. Action of K12 relay can be observed if it is operating, K13 can be felt. Both relays can be heard. 5. Relays K11 and K12 are interchangeable. If K12 does not operate remove it and plug K11 in its place. If the 'now' K12 relay operates then obviously the old one is defective. install new relay.
Low oil pressure shutdown.This type of malfunction is caused by one of the following— 1. Low oil quantity resulting in low oil pressure. Engine oil system malfunction. Ground between TB11-30 and LOP switch. Permanently closed LOP switch. Faulty engine monitor board.If the generator set has LOP pre-alarm, then the most possible reason for shutdown is either low oil quantity or an engine oil system malfunction. If the latter, refer to the engine manufacturer's manual for oil system troubleshooting guide. A grounded wire or permanently closed switch are unlikely because the pre-alarm switch has to operate to arm the shutdown system. However, a double fault is possible and should never be discounted. When all other troubleshooting possibilities have been tried, the double fault should be considered. This could be either— 1. Grounded wire between 1TB11-30 and LOP switch. 2. Grounded wire between TB11-34 and LOP pre-alarm switch. 3. Permanently closed LOP switch. 4. Permanently closed LOP pre-alarm switch. 5. Faulty engine monitor board.
No generator outputIs panel meter selection switch positioned correctly for a voltage/current reading? - Run 2 Is panel circuit breaker (CB1) in the ON position? - 3 3 Switch CB1 to ON. Does generator output build up? a. Is Output high or low? (See Guide B) b. Is output unstable? (See Guide C) c. Does CB1 trip? (See Guide D)
Generator output too high or too lowRotate voltmeter/ammeter phase selector switch. Is discrepancy identifiable on all switch positions? - 4 2 Can condition be corrected by adjustment of voltage control rheostat R1 on panel? - 3 3 If output too low, is unit overloaded? - 5
NO AC OUTPUT VOLTAGEENGINE RUNNING RATED RPMIs the Exciter Circuit Breaker (CB21) on the meter panel in the “ON” position? Switch CB21 to the “ON” position. Is the AC voltage measured at terminals 1 and 2 on voltage regulator (VR21) printed circuit board 5 to 10 volts? Is the AC voltage measured at terminals 11 and 12 on VR21 5 to 10 volts? Replace reactor assembly (L21). Is the DC voltage measured at terminals + and - on Rectifier Bridge (CR21) 5 to 10 volts? Shut down generator set. Check continuity between terminal 2 on VR21 and T8 on generator, between terminal 1 on VR21 and T7 on generator. If no continuity exists between VR21-1 and T7 (CB21-ON) apply a shorting jumper across CB21. Is continuity obtained? Replace circuit breaker CB21. Check for loose or broken wires on VR21, CR21, reference voltage transformer (T21), generator bus-bars and terminal board (TB21) in control box. Secure or repair where necessary. If repairs have been made, restart engine. Are diodes CR1, CR2 and CR3 on CR21 assembly good? Are SCRs 4 and 5 in CR21 good? Fault probably lies with a defective component on VR21. Replace voltage regulator VR21. Start engine. Place CB21 in “OFF” position. Using method prescribed under “M” in procedure section flash the exciter field to restore residual magnetism. Place CB21 ON. Shut off engine. Is the exciter field winding OK? Are the rotating diodes CR1, through CR6 on the exciter rotor OK?

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing. Full Cummins/Onan YB series troubleshooting guide (26 entries) →

Parts

10
Part #DescriptionQtySystem
6Z0S-2L9LHSOMT b WL/M4IG1Air filter Amazon eBay
91Sd3%2Z6/A401Air filter Amazon eBay
99EP-cL9LHDI1 S1Oil filter Amazon eBay
O9EP-Z19LHDI!T1Oil filter Amazon eBay
0890-00EMONITOR, ENGINE CONTROL1Service part / kit Amazon eBay
305-0524Bridge, Rectifier - Used on Standard Voltage Regulator Assemblies (VRA21CR21)1Service part / kit Amazon eBay
315-0342Reference transformer T211Service part / kit Amazon eBay
315-0384Reactor Assembly, Commutator1Service part / kit Amazon eBay
332-1704Voltage regulator VR21Service part / kit Amazon eBay
900-0181PCC Control Service Manual*Service part / kit Amazon eBay

Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.

Available documents

Service manual — 900-0192 Onan UV 300-600 KW Generators & Controls Service Manual (01-1975) (Cummins/Onan)

This page was generated from the 1 manufacturer document above by automated extraction; every figure shown is copied from one of them. How the data is compiled.