Cummins/Onan — Flashing Field (Section I)

Repair & overhaul · Exciter field

From a Cummins/Onan service manual covering: 300.0 DFT, 350.0 DFU, 350.0 WF, 400.0 DFV, 400.0 WK, 450.0 DFW, 500.0 DFY, 600.0 DWV. Check it applies to your exact model before use.

Applies to: Cummins/Onan YB series

Before you start

  • High voltage will be present on voltage regulator terminals if output builds up.
  • Do not keep field flashing circuitry connected longer than 5 seconds or damage may occur.

Procedure

  1. Assemble six-volt supply, resistor, and diode as shown in Figure 3.
  2. Remove frontal grille to access voltage regulator.
  3. Disconnect lead F1 at VR1-3.
  4. Start unit.
  5. Touch positive lead of supply to F1 and negative to VR1-2.
  6. Hold leads until voltage starts building.
  7. Shut down unit and reconnect wires.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Do not keep field flashing circuitry connected longer than 5 seconds.

Full service-parts list: Cummins/Onan YB series →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.