Specifications
| Fuel | gasoline/LPG |
|---|---|
| Frequency | 60.0 Hz |
| Controller | A1, EC-AGS+ |
| Oil capacity | 1.8 L |
| Voltage options | 120/240 V, 120 V |
| Phase | 1 |
| Rated current | 45.8 A |
| Power factor | 1.0 |
| Battery cranking | 450 CCA |
| Battery voltage | 12 V |
| Dry weight | 127 kg |
| Sound level | 67.0 dBA @ 3 m |
Maintenance & consumables
| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Air filter | — | 500 hr | |||
| Fuel filter | — | 100 hr | |||
| Oil filter | — | 50 hr | |||
| Battery | — | 10000 hr | |||
| Belt | — | 30000 hr | |||
| Coolant | 3.7 L | — | 500 hr | ||
| Oil | Engine Oil Recommendations | 4.6 L | — | 50 hr | |
| Spark plug | Periodic Maintenance section | — | 500 hr |
Service intervals
19| Item | Action | Hours | Months | Notes |
|---|---|---|---|---|
| Genset | Other | 1 hr | 1 mo | Exercise at least 1 hour each month at approximately 1/2 rated power if use is infrequent |
| Engine oil level | Check | 8 hr | First service — Section 4.2 | |
| Exhaust system | Inspect | 8 hr | Inspect for exhaust leaks at every startup and after every eight hours of running | |
| General inspections | Inspect | 8 hr | Every day or every 8 hours | |
| Genset | Inspect | 8 hr | Every day or every 8 hours; general inspections | |
| Genset general inspection | Inspect | 8 hr | Before first start of the day and after every 8 hours of operation | |
| Engine oil | Change | 50 hr | In dusty environments change engine oil every 50 hours | |
| Spark arrester | Clean | 50 hr | Every 50 hours | |
| Spark arrestor | Clean | 50 hr | Table 3-1 Periodic Maintenance Schedule | |
| Air filter element | Replace | 450 hr | Perform more often when operating in dusty environments | |
| Engine cooling fins | Clean | 450 hr | Perform more often when operating in dusty environments | |
| Engine oil & oil filter | Change | 150 hr | 12 mo | First service — Perform more often in dusty environments and hot weather; at least once a year |
| Engine oil and oil filter | Change | 150 hr | 12 mo | First service — Perform more often in dusty/hot environments; at least yearly |
| Fuel filter | Replace | 500 hr | 36 mo | Sooner if engine performance deteriorates; by trained mechanic |
| Cylinder heads | Clean | 500 hr | Clean or replace; required for optimum performance | |
| Spark plugs | Replace | 500 hr | Sooner if performance deteriorates | |
| Valve lash | Adjust | 500 hr | Must be performed by trained mechanic (authorized Cummins dealer) | |
| Battery | Clean | 1 mo | Clean and check monthly (more often in hot weather) | |
| Battery and battery connections | Clean | 1 mo | Perform more often in hot weather |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Service specifications
60| Type | Item | Value | Unit | Condition |
|---|---|---|---|---|
| Clearance | Crankshaft End Play | 0.005 - 0.012 | in | |
| Clearance | Crankshaft End Play | 0.127 - 0.305 | mm | |
| Clearance | Crankshaft Oil Seal depth below surface | 0.020 to 0.060 | in | |
| Clearance | Crankshaft end play | 0.005 – 0.012 | in (0.127 – 0.305 mm) | |
| Clearance | Crankshaft end play | 0.005-0.012 | in | |
| Clearance | Crankshaft oil seal press depth | 0.020 to 0.060 | in | below surface |
| Clearance | Cylinder head flatness max | 0.004 | in | |
| Clearance | Cylinder head flatness maximum | 0.004 | in (0.1 mm) | |
| Clearance | Exhaust Valve Lash (Cold) | 0.10 | mm (0.004 in) | cold |
| Clearance | Intake Valve Lash (Cold) | 0.10 | mm (0.004 in) | cold |
| Clearance | Piston-to-cylinder clearance at skirt max | 0.0098 | in | |
| Clearance | Valve guide inside diameter max | 0.242 | in | |
| Clearance | Valve guide inside diameter standard | 0.2376 – 0.2383 | in (6.035 – 6.053 mm) | |
| Gap | Magneto Air Gap | 0.012 | in (0.3 mm) | |
| Gap | Magneto Air Gap | 0.3 | mm | |
| Gap | Spark Plug Gap | 0.025 | in (0.6-0.7 mm) | |
| Gap | Spark Plug Gap | 6-7 | mm (0.025 in) | |
| Injection timing | Ignition Timing | 20 deg BTDC | degrees BTDC | non-adjustable magneto |
| Other | EC-AGS+ gateway dimensions | 120 x 108 x 38 | mm | |
| Other | Ignition Timing | 20° BTDC | non-adjustable magneto | |
| Other | LPG low-pressure supply (vapor) | 9-13 | in WC | |
| Other | Maximum exhaust back pressure | 35 | in WC | |
| Other | Spark plug kit torque specification | 18-25 | lb-ft | |
| Other | Temperature sensor dimensions | 51 x 70 x 17 | mm | |
| Pressure | Carburetor fuel pump outlet pressure | 2.5 to 4 | psi | priming |
| Pressure | Compression | 3.9 | kgf/cm2 (55.47 lbf/in2) | @ 500 RPM |
| Pressure | Crankcase Vacuum | 7 to 10 | inches of water column | measured through a tap in the oil fill cap |
| Pressure | Crankcase vacuum | 7-10 | inches water column | measured through oil fill cap tap |
| Pressure | Cylinder Compression Test | 153-188 | psi | |
| Pressure | Engine Compression | 153 and 188 | psi | |
| Pressure | Fuel Pump pressure (carburetor models) | 2.5 to 4 | psi (17 to 27 kPa) | |
| Pressure | Fuel Rail Pressure (EFI) | 43.5 psi (300 kPa) nominal | psi | |
| Pressure | Fuel rail pressure differential | 43.5 | psi | nominal |
| Pressure | Gasoline EFI fuel pressure (between fuel rail and high pressure fuel pump, priming) | approximately 45 | psi | generator set off and priming |
| Pressure | Hydraulic Pump Inlet Conditions | 5 | in Hg Vacuum or 20 psi Pressure max | |
| Pressure | Hydraulic Pump Inlet Conditions | Not to exceed 5 in Hg Vacuum or 20 psi | in Hg / psi | |
| Pressure | Hydraulic pump | 1.6 | gpm @ 2500 psi | 5.5 model pumps |
| Pressure | Hydraulic pump | 1.8 | gpm @ 2500 psi | HGJAD/HGJAE pumps |
| Pressure | LPG Vapor Supply Pressure | 9-13 | in (228-330 mm) WC | |
| Pressure | LPG supply pressure (low-pressure) | 9-13 | in (228-330 mm) WC | all loads |
| Pressure | Low Oil Pressure Cutoff | less than 17 | psi | |
| Pressure | Low Oil Pressure Fault threshold | less than 17 | psi | |
| Pressure | Low oil pressure fault threshold | 17 | psi | less than 17 psi |
| Pressure | Low oil pressure switch opens | 14.2 | psi | |
| Pressure | Low-Pressure LPG demand regulator lock-off pressure | 0.20 to 0.35 | inches WC | |
| Pressure | Low-Pressure LPG supply pressure | 9-13 | inches WC | |
| Pressure | Low-pressure LPG lock-off pressure | 0.20 to 0.35 | inches WC (5.1 to 8.9 mm) | |
| Pressure | Max Exhaust Back Pressure (HGJAF models) | 35 | in (889 mm) WC | |
| Pressure | Max exhaust back pressure | 35 | in (889 mm) WC | |
| Pressure | Nominal Engine Oil Pressure | 43 | psi | |
| Pressure | Nominal oil pressure | 43 | psi | |
| Pressure | Oil Pressure (nominal) | 43 | psi | |
| Pressure | Oil Pressure Switch (opens) | 14.2 | psi | |
| Resistance | Fuel Injector resistance | 12.5 | Ohms | |
| Resistance | Fuel injector electrical resistance | approximately 12.5 | ohms | |
| Resistance | Gateway harness continuity maximum resistance | 10 | Ohms | repair or replace harness if greater |
| Resistance | Governor actuator stator winding | 4.5 and 5.5 | ohms | |
| Resistance | Ignition Coil LEFT (No. 1 Cyl) maximum | 33,000 | Ohms | |
| Resistance | Ignition Coil LEFT (No. 1 Cyl) minimum | 13,700 | Ohms | |
| Resistance | Ignition Coil RIGHT (No. 2 Cyl) maximum | 27,000 | Ohms |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Recommended fluids
| Fluid | Grade | Standard | Ambient | Capacity | Notes |
|---|---|---|---|---|---|
| Engine oil | API Class SJ, SH or SG | 2.0 quart (1.8 l) | Oil capacity | ||
| Engine oil | OnaMax 10W-30 (A063E183) | API SM, SN, or better | 1.8 l | Recommended for temperatures above 0 °F | |
| Engine oil | 5W-30 | API SJ, SH or SG (may combine with CH-4, CG-4 or CF-4) | -28°C to 10°C | –20° F to 50° F (–28° C to 10° C) | |
| Engine oil | SAE 5W-30 | API Class SJ, SH or SG (may be combined with CH-4, CG-4 or CF-4) | -28°C to 10°C | –20°F to 50°F | |
| Engine oil | 10W-30 | API SJ, SH or SG (may combine with CH-4, CG-4 or CF-4) | -18°C to 27°C | 0° F to 80° F (–18° C to 27° C) | |
| Engine oil | 10W-30 (OnaMax), 10W-40 | API SM, SN, or better | -18°C to 38°C | -18 to 38 °C (0 to 100 °F) | |
| Engine oil | 10W-30 10W-40 | API SJ, SH or SG (with CH-4, CG-4 or CF-4) | -18°C to 27°C | 1.8 l | 0 deg F to 80 deg F (-18 deg C to 27 deg C) |
| Engine oil | 10W-30, 10W-40 | API SJ/SH/SG (may combine CH-4, CG-4, CF-4) | -18°C to 27°C | ||
| Engine oil | 10W-40 | API SJ, SH or SG (may combine with CH-4, CG-4 or CF-4) | -18°C to 27°C | 0° F to 80° F (–18° C to 27° C) | |
| Engine oil | SAE 10W-30 / 10W-40 | API Class SJ, SH or SG (may be combined with CH-4, CG-4 or CF-4) | -18°C to 27°C | 0°F to 80°F | |
| Engine oil | 15W-40 (OnaMax) | API SJ, SH or SG (may combine with CH-4, CG-4 or CF-4) | -12°C to 38°C | 10° F to 100° F (–12° C to 38° C) | |
| Engine oil | SAE 15W-40 (OnaMax) | API Class SJ, SH or SG (may be combined with CH-4, CG-4 or CF-4) | -12°C to 38°C | 10°F to 100°F | |
| Engine oil | 30 | API SM, SN, or better | above 0°C | 0 °C (32 °F) and higher | |
| Engine oil | SAE 30 | API SJ, SH or SG (may combine with CH-4, CG-4 or CF-4) | above 0°C | 32° F (0° C) and higher; single-grade SAE 30 preferable when temperatures consistently above freezing | |
| Engine oil | 10W-30 / 10W-40 | 18°C to 27°C | 1.8 liters (2.0 qt) | -18 to 27°C (0 to 80°F) | |
| Fuel | HD-5 LPG, min 90% propane | Commercial LPG may contain up to 2.5% butane | |||
| Fuel | HD-5 grade LPG (at least 90 percent propane) | Commercial LPG may contain more than 2.5 percent butane causing poor vaporization/starting below 32° F (0° C) | |||
| Fuel | HD-5 grade LPG (min 90% propane) | LPG models; butane >2.5% prevents vaporization below 32 °F (0 °C) | |||
| Fuel | HD-5 grade LPG or equivalent, at least 90 percent propane | LPG models; commercial LPG may contain more than 2.5% butane | |||
| Fuel | HD-5 grade liquefied petroleum gas (LPG) | at least 90 percent propane | LPG models. Commercial LPG may contain more than 2.5 percent butane causing poor vaporization below 32 F (0 C). | ||
| Fuel | HD-5 grade liquefied petroleum gas (LPG), at least 90% propane | Butane content may result in poor vaporization below 32 °F (0 °C) | |||
| Fuel | HD-5 grade liquified petroleum gas (LPG), at least 90 percent propane | Commercial LPG may contain more than 2.5 percent butane | LPG models; low-pressure LPG vapor pressure per Specifications | ||
| Fuel | Unleaded gasoline | minimum octane rating (Anti-Knock Index) of 87 | Gasoline models. Do not use gasoline containing methanol. | ||
| Fuel | Unleaded gasoline, min 87 octane | Not more than 10% ethanol; not more than 5% methanol | |||
| Fuel | Unleaded gasoline, min octane 87 (Anti-Knock Index) | Max 10% ethanol; max 5% methanol with solvents/corrosion inhibitors | Gasoline models | ||
| Fuel | Unleaded gasoline, min. octane rating (Anti-Knock Index) 87 | Ethanol blend not more than 10% ethanol; methanol blend not more than 5% methanol with solvents and corrosion inhibitors | Gasoline models | ||
| Fuel | Unleaded gasoline, minimum octane rating (Anti-Knock Index) 87 | Do not use gasoline/additives containing methanol; avoid leaded gasoline | |||
| Hydraulic oil | Transmission or Petroleum-Based Hydraulic Fluid | Operating Viscosity: 80-1000 SSU; Maximum Start-Up Viscosity: 4000 SSU | |||
| Hydraulic oil | Transmission or petroleum-based hydraulic fluid | Operating viscosity 80-1000 SSU; maximum start-up viscosity 4000 SSU | Optional hydraulic pump models HGJAD/HGJAE/HGJAF |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Fault codes
35| Code | Name | Meaning | Severity | Action |
|---|---|---|---|---|
| 1 | High Engine Coolant Temperature | Status indicator light blinks 1 time - shutdown due to high engine coolant temperatures | Shutdown | Allow engine to cool; inspect cooling system |
| 12 | Overvoltage Shutdown | Instantaneous: AC voltage S1-S2 greater than 150 VAC. Delayed: greater than 138 VAC but less than 150 VAC for 3 continuous minutes | Shutdown | Verify FC12; measure AC voltage; cycle loads; reduce battery charge rate; balance loads; run in ERO mode; measure winding resistances; check brush alignment. |
| 13 | Undervoltage Shutdown | Controller unable to maintain rated voltage | Shutdown | Verify FC13; measure AC voltage in/out of sense transformer; cycle loads; reduce charger rate; measure winding resistances; check brush alignment. |
| 14 | Overfrequency Shutdown | Instantaneous: frequency greater than 70 Hz. Delayed: greater than 66 Hz but less than 70 Hz for 3 continuous seconds | Shutdown | Verify FC14; measure AC current and load capability; check governor, fuel supply, air filter, exhaust, choke, magnetos; run ERO test. |
| 15 | Underfrequency Shutdown | Engine governor unable to maintain rated frequency. | Shutdown | Verify FC15; measure AC current; check governor, fuel supply, air filter, exhaust, choke, magnetos; run ERO test. |
| 17 | Fuel Pump Fault | Open fuel pump circuit at control (active prior to 2001) | Shutdown | Verify pump in prime mode; check fuse F1; replace pump |
| 19 | Governor Actuator Shutdown | Shorted or open connection between governor leads after pressing start; P1-17 | Shutdown | Verify actuator function with DC voltage; measure actuator terminal resistance; check P1-28 continuity |
| 2 | Low Oil Pressure Shutdown | Low oil pressure cutoff switch did not open. | Shutdown | Verify FC2; measure oil level; inspect P1 pins per PSB-676; measure continuity; measure oil pressure with a mechanical gauge; repair/replace relief valve and oil pump. |
| 22 | Governor Actuator Overload Shutdown | Only active prior to 2001; maximum governor output (PWM) for 10 continuous seconds. | Shutdown | Verify FC22; measure AC current, load capability; check air filter, intake manifold gaskets, exhaust, fuel pump pressure; verify actuator; check magnetos. |
| 23 | Oil Pressure Switch Fault | Only active prior to 2001 - continuous open on oil pressure switch input before cranking | Shutdown | Verify harness lead connected; measure continuity to ground at switch and through harness at P1 |
| 27 | Voltage Sense Shutdown | No sense voltage (0 VAC across S1-S2) for 1 continuous second after start disconnect. | Shutdown | Verify FC27; measure AC voltage; inspect P1 pins; check air filter and exhaust; run ERO test; check fuel and ignition systems. |
| 29 | High Battery Voltage Shutdown | Voltage across battery system is greater than 19 Volts. | Warning | Verify FC29; measure DC voltage at battery, generator set and P1; check grounds; replace controller if needed. |
| 3 | Service Check Shutdown | Single-digit fault indicating shutdown due to a two-digit fault | Shutdown | While LED flashing three times, press stop once (1 second) and troubleshoot the two-digit fault code. |
| 31 | Overspeed Shutdown | Engine speed greater than 3400 rpm | Shutdown | Verify FC31; measure frequency and droop; check governor, air filter, exhaust, fuel, magnetos; run ERO test. |
| 32 | Low Cranking Speed Shutdown | Quadrature frequency less than or equal to 3 Hz and engine RPM less than or equal to 100 RPM for 12 continuous seconds after pressing start. | Shutdown | Verify FC32; measure battery voltage; verify engine rotation; check starter, air filter, spark plug, exhaust; check magnetos. |
| 33 | Fault Code 33 | There is a single-digit fault which indicates a shutdown due to a two-digit fault code; Fault Code 3 interpreted as a non-assigned Fault Code 33. | Shutdown | While LED flashing three times, press stop once (1 second); troubleshoot the two-digit fault code. |
| 35 | Control Card Failure Shutdown | Microprocessor EEPROM error occurred during self test. | Shutdown | Verify FC35; replace the control. |
| 36 | Stopped Without Fault Condition | RPM less than 500 and sense voltage S1-S2 at 0 VAC with no other fault | Shutdown | Verify FC36; check AGS; verify engine rotation; inspect P1 pins; check air filter, spark plug, exhaust; run ERO test. |
| 37 | Invalid Set Configuration | Wrong frequency/rpm ratio | Shutdown | Verify FC37; if alternating with FC47 reset magneto gap; run ERO test; measure winding resistances; verify magnetos and board. |
| 38 | Overcurrent (Field Overload) Shutdown | Low power factor loads. | Shutdown | Verify FC38; measure F1-F2 DC voltage and AC current; reduce charger rate; inspect P1 pins; measure winding resistances; check brush alignment. |
| 4 | Overcrank Shutdown | First-level shutdown code—Cranking exceeded 30 seconds without engine starting (4 blinks) | Shutdown | Verify FC4; measure battery voltage; check start/stop switch and P1; check air filter, spark plug, exhaust system, fuel supply, ignition and magnetos. |
| 41 | Generator Rotor Shutdown | Only active after 2003; field voltage F1-F2 at 0 VDC and sense voltage S1-S2 at 0 VAC for 1 continuous second. | Shutdown | Verify FC41; measure F1-F2 DC voltage and AC current; inspect P1 pins; run ERO test; measure winding resistances; check brush alignment. |
| 42 | Processor Shutdown | ROM error during self-test | Shutdown | Verify FC42; replace the control. |
| 43 | Processor Shutdown | RAM error during self-test | Shutdown | Verify FC43; replace the control. |
| 45 | Speed Sense Shutdown | While running, the quadrature frequency dropped to 0 Hz for 1 continuous second. | Shutdown | Verify FC45; check AGS; verify engine rotation; inspect P1 pins; check air filter, exhaust, loads; run ERO test; check magnetos. |
| 47 | Ignition Shutdown | No ignition signal at P1 (P1-15 for HGJAB/C; P1-5 for HGJAA/D/E/F) for 1 continuous second | Shutdown | Verify FC47; if alternating with FC37 reset magneto gap; test magnetos; run ERO test; measure winding resistances. |
| 48 | Generator Field Sense Shutdown | The controller is unable to sense field voltage. | Shutdown | Verify FC48; replace the control. |
| 51 | Processor Shutdown | Processor error; faulty control | Shutdown | Verify FC51; use breakout board per Instruction Sheet R1098; replace the control. |
| 52 | Fuel Injector Shutdown | Open or shorted fuel injector; P1-17; wire connections | Shutdown | Verify FC52; inspect injector connector and P1 pins; measure continuity between P1-23 INJ1 and P1-35 INJ2; replace injector. |
| 54 | MAT Sensor Fault (EFI) | The MAT sender input is greater than 300k Ohms. | Shutdown | Verify FC54; inspect sender connector and P1 pins; measure continuity between P1-25 MAT(A) and P1-20 MAT(B); replace sender. |
| 56 | MAP Sensor Fault (EFI) | The MAP sensor input is less than 50 kPa at start. | Shutdown | Verify ambient pressure; test sender; replace sender |
| 57 | Overprime Shutdown | The generator set has been priming for 3 consecutive minutes. | Shutdown | Verify FC57; check for an object holding the switch in stop position; inspect P1 pins; check start/stop switch. |
| 58 | Exhaust Gas Temperature Shutdown | Exhaust gas temperatures reach 650C (1202F) for 2 secs when the set is running | Shutdown | Verify FC58; check spark plugs and cables; test magnetos; check carburetor/LP mixer/regulator/EFI injector; check EGT sensor and wiring; check compression and leakdown. |
| 81 | Overprime Shutdown | While running, the EGT falls below 60 °C (140 °F) for 2 minutes or is not above 60 °C 2 minutes after starting. | Shutdown | Verify FC81; check connector at muffler and harness; check wiring; measure resistance between EGT sensor connector and J1-15/J1-21; use InPower; replace the EGT sensor. |
| 82 | Exhaust Gas Temperature Sensor Shorted | With the set running and/or startup - control reads 1000C (1832F) for 1 second | Shutdown | Verify FC82; measure resistance between ground and J1-21; use InPower; replace the EGT sensor if a short exists. |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Procedures
12Adjusting Governor (Mechanical) adjustment
⚠ Voltage/frequency-sensitive equipment may be damaged by power line frequency variations; disconnect them before adjustments.
Tools: Variable load bank up to 7 kW, Frequency meter (within 0.3%), Voltmeter (within 0.5%), AC ammeter
- Warm up the genset for at least 5 minutes at 1/2 to 3/4 rated load with the choke fully open.
- Adjust frequency close to the Table 8-3 value with the speed adjusting nut.
- With the engine warm, remove all loads and adjust the idle stop screw to 51-53 Hz (60 Hz genset) or 41-43 Hz (50 Hz genset).
- Let the throttle lever go and recheck/adjust No-Load frequency to Table 8-3; bump the governor arm to check stabilization.
- Connect rated load; if droop is out of spec move the governor spring hook one or two notches and recheck.
- Confirm the governor does not hunt under the loading sequence.
Adjusting Governor (Mechanical, HGJAB and HGJAE) adjustment
⚠ Disconnect all voltage/frequency-sensitive devices before making carburetor/governor adjustments.
Tools: Variable load bank up to 7 kW, Frequency meter (within 0.3%), Voltmeter (within 0.5%)
- Warm up generator set for at least 5 minutes at 1/2 to 3/4 rated load.
- Adjust frequency with the speed adjusting nut toward the Table 11 value.
- With engine warm, remove all loads; adjust idle stop screw to 51-53 Hz (60 Hz) or 41-43 Hz (50 Hz).
- Let throttle lever go.
- Recheck and re-adjust no-load frequency per Table 11.
- Bump governor arm to see frequency stabilizes.
- Connect a rated load.
- If droop is greater than specified, move governor spring hook one or two notches toward governor shaft; recheck.
- If droop is less or set hunts, move spring hook one or two notches away from governor shaft.
Adjusting Mechanical Governor adjustment
⚠ Voltage/frequency-sensitive equipment may be damaged; disconnect before adjusting
Tools: load bank, frequency meter, voltmeter
- Warm up genset five minutes at 1/2 to 3/4 rated load.
- Adjust frequency to Table 8-4 value with speed adjusting nut.
- With engine warm and no loads, set idle stop screw to 51-53 Hz (60 Hz).
- Recheck no-load frequency and bump governor arm for stability.
- Connect rated load; move governor spring hook to correct droop.
- Check for hunting under the specified load sequence.
Adjusting Valve Lash adjustment
Tools: Socket wrench, Feeler gauge, Torque wrench
- Adjust when the engine is at room temperature.
- Remove the spark plugs so the engine is easier to turn over.
- Use a socket wrench on the generator pulley nut to turn the engine clockwise; remove the snap-in cover.
- Remove the valve covers with rags in place to catch oil.
- Turn engine until No. 2 intake valve is at max lift; adjust No. 1 intake valve lash.
- Turn engine until No. 2 exhaust valve is at max lift; adjust No. 1 exhaust valve lash.
- Turn engine until No. 1 intake valve is at max lift; adjust No. 2 intake valve lash.
- Turn engine until No. 1 exhaust valve is at max lift; adjust No. 2 exhaust valve lash.
- Secure valve covers using new gaskets and torque cover screws to 5.5 lb-ft (8 N-m).
- Replace the spark plugs and pulley nut cover.
Adjusting Voltage adjustment
⚠ If fault shutdown or STOP pressed during voltage set mode, adjustment is not stored
Tools: AC voltmeter, Frequency meter
- Disconnect all alternator loads.
- Connect accurate AC voltmeter and frequency meter.
- Start genset and let voltage/frequency stabilize 5-10 seconds.
- Rapidly press control switch to START 6 times within 1 minute.
- Press START briefly to raise voltage ~0.6 V per press.
- Press START for ~2 seconds to lower voltage ~0.6 V per press.
- Normal operation resumes 20 seconds after last adjustment.
Resetting Governor Arm adjustment
Tools: Battery terminal puller, Torque wrench
- Loosen the governor shaft nut by turning it clockwise and remove the arm.
- Use a battery terminal puller to break the taper fit of the shaft in the arm hub.
- Reattach arm and hub making sure the pins and holes engage; thread the shaft nut on counterclockwise.
- Check free rotation of the arm and let the governor spring take up all play; linkage must push throttle against the wide open throttle stop.
- Torque the shaft nut to 8 lb-ft (11 N-m) counterclockwise.
- Push the governor arm down and check for binding or interference.
Setting Ignition Coil Air Gaps adjustment
Tools: Feeler gauge, Torque wrench
- Bar the engine until the lands on the flywheel directly face the coils.
- Place a 0.012 inch (0.03 mm) thick feeler gauge between the coil and the land.
- Hold the coil tight against the feeler gauge and land and torque the two mounting bolts to 5 lb-ft (7 N-m).
Setting Magneto Air Gaps adjustment
Tools: feeler gauge, torque wrench
- Bar the engine until the flywheel lands directly face the coils.
- Place a 0.012 inch (0.3 mm) feeler gauge between coil and land.
- Hold coil tight against gauge and land.
- Torque the two mounting bolts to 5 lb-ft (7 N-m).
Valve Lash Adjustment adjustment
⚠ Adjust valve lash only when engine is at room temperature
Tools: Feeler gauge, Socket wrench, Torque wrench
- Adjust valve lash with engine at room temperature.
- Remove spark plugs and valve covers.
- Turn engine until No. 2 intake valve is at maximum lift.
- Adjust No. 1 intake valve lash to 0.004 in (0.10 mm).
- Turn engine until No. 2 exhaust valve at maximum lift; adjust No. 1 exhaust.
- Turn engine until No. 1 intake valve at maximum lift; adjust No. 2 intake.
- Turn engine until No. 1 exhaust at maximum lift; adjust No. 2 exhaust.
- Torque lock nuts to 6.5 lb-ft (8.5 Nm) and install valve covers.
Voltage Adjustment (HGJAD, HGJAE, HGJAF) adjustment
⚠ Hazardous voltage: touching uninsulated live parts can cause severe injury or death
Tools: AC voltmeter, frequency meter
- Disconnect all generator loads and connect accurate AC volt and frequency meters.
- Start genset; let voltage and frequency stabilize 5 to 10 seconds.
- Rapidly press control switch to START 6 times within 1 minute of start.
- Adjust up: press START and release quickly (voltage rises about 0.6 volt).
- Adjust down: press START and release after about 2 seconds (voltage drops about 0.6 volt).
Fuel Pump Flow Test (EFI Gasoline Models) diagnostic
⚠ Gasoline is flammable; do not smoke; keep ignition sources away
Tools: Fuel pressure gauge, Gallon container
- Disconnect fuel return line between genset and tank.
- Collect fuel in a gallon container.
- Prime the genset for exactly one minute.
- Verify flow is approximately 1 quart (0.9 liter) per minute.
- Verify fuel pressure is approximately 45 psi.
- Reconnect the fuel return line.
Fuel Pump Flow Test (EFI) diagnostic
⚠ Gasoline is flammable and explosive
Tools: gallon container, fuel pressure gauge
- Disconnect the fuel return line between genset and supply tank.
- Be prepared to collect fuel in a gallon container.
- Prime the genset for exactly one minute.
- Verify flow is approximately 1 quart (0.9 liter) per minute and pressure about 45 psi.
- Reconnect the fuel return line.
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Voltage reconnection
| Voltage | Phase | Connection | Leads | Notes |
|---|---|---|---|---|
| These generator sets are not reconnectable for voltages other than stated on the nameplate | AC output through rain-tight 1/2 inch conduit connector; 12 AWG leads, 125 °C rated wire | |||
| 100-120 | 1-Phase | 2-Wire | T1-T2 and T3-T4 in phase, neutral L0 and ground | The two generator windings marked T1-T2 are in phase; neutral conductors must carry the sum of the currents |
| 100-120V | 1 | "2-wire" | CB1-LOAD (L1), CB2-LOAD (L2), NEUTRAL (L0) | Not reconnectable; generator windings T1-T2 are in phase so neutral conductors must be sized to carry the sum of the currents |
| 100/200 | 1-Phase | standard 3-Wire | T1-T2, T3-T4 with neutral L0 | Not reconnectable |
| 100/200V, 115/230V, 120/240V | 1 | Standard 3-wire | CB1-LOAD (L1), CB2-LOAD (L2), NEUTRAL (L0) | These are not reconnectable generators; 12 AWG AC output leads through rain-tight 1/2 inch trade size conduit connector |
| 110/120 | 3-Phase | standard 3-phase | T1-T2, T3-T4, T5-T6 with neutral L0 | Not reconnectable for voltages other than stated on the nameplate |
| 110/120V, 115/230V, 120/240V | 3-phase | 3-phase | CB1-LOAD (L1), CB2-LOAD (L2), CB3-LOAD (L3), NEUTRAL (L0) | These are not reconnectable generators |
| 115/230 | 1-Phase | standard 3-Wire | T1-T2, T3-T4 with neutral L0 | Not reconnectable |
| 115/230 | 3-Phase | standard 3-phase | T1-T2, T3-T4, T5-T6 with neutral L0 | 12 AWG leads exit through rain-tight 1/2 inch trade size conduit connector |
| 120 | 1 | 2-wire 120 VAC; alternator leads T2 and T4, green AC output lead and two white (L0, L0) leads secured to base with alternator neutral ground screw | T2, T4, L0, L0, green | 2-wire 120 VAC configuration only |
| 120/240 | 1-Phase | standard 3-Wire | T1-T2, T3-T4 with neutral L0 | Not reconnectable |
| 120/240 | 3-Phase | standard 3-phase | T1-T2, T3-T4, T5-T6 with neutral L0 | Not reconnectable |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Common questions
What fuel type does the Cummins/Onan HGJAE take?
The Cummins/Onan HGJAE runs on gasoline/LPG.
What is the oil capacity of the Cummins/Onan HGJAE?
The Cummins/Onan HGJAE has an engine oil capacity of 1.8 liters (1.9 US quarts), per the manufacturer specification sheet.
What is the sound level of the Cummins/Onan HGJAE?
The Cummins/Onan HGJAE is rated at 67.0 dBA at 3 m, per the manufacturer specification sheet.
What is the dry weight of the Cummins/Onan HGJAE?
The Cummins/Onan HGJAE has a dry weight of 127 kg (279 lb).
What voltage does the Cummins/Onan HGJAE produce?
The Cummins/Onan HGJAE is offered in 120/240 V, 120 V, 1-phase.
How many cold cranking amps does the Cummins/Onan HGJAE require?
The Cummins/Onan HGJAE uses 12 V each, 450 CCA, per the manufacturer specification sheet.
Troubleshooting
6Fault codes
| Code | Meaning |
|---|---|
| 2 | Low Oil Pressure Fault |
| 3 | Service Check Fault |
| 4 | Overcrank |
| 12 | Overvoltage |
| 13 | Undervoltage |
| 14 | Overfrequency |
Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing. Full Cummins/Onan HGJAE troubleshooting guide (37 entries) →
Repair guides
15- Adjusting Governor (Mechanical)
- Adjusting Governor (Mechanical, HGJAB and HGJAE)
- Cleaning the Spark Arrestor (Series HGJAD)
- Cylinder Head Reassembly and Torque Sequence
- Fuel Pump Flow Test (EFI Gasoline Models)
- Fuel Pump Flow Test (Gasoline EFI)
- Fuel Pump Pressure Test (Carburetor Models)
- Ignition Coil (Magneto) Installation
- Lock-Off Pressure Test (Low-Pressure LPG Demand Regulator)
- Removing the Generator Set
- Replacing Spark Plugs
- Replacing the Spark Plug(s)
- Spark Check
- Testing Low-Pressure LPG Shutoff E4
- Valve Lash Adjustment
Step-by-step procedures compiled from the Cummins/Onan service manual for this model.
Parts
5| Part # | Description | Qty | System | |
|---|---|---|---|---|
| 0541-1287 | Harness Kit for InPower Diagnostic Service Tool | 1 | Hose | Amazon eBay |
| 0541-1374 | InPower Harness Kit (Spec J and later) | 1 | Hose | Amazon eBay |
| 0541-1389 | Harness Kit for InPower Diagnostic Service Tool | 1 | Hose | Amazon eBay |
| 0420-0603 | Bypass Control Board Tester | 1 | Service part / kit | Amazon eBay $599.99 |
| 0541-1143 | Bypass Control Board Tester Adapter Kit | 1 | Service part / kit | Amazon eBay |
Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| 1.6 | 0.43 | ||
| 50% | 2.7 | 0.7 | |
| 100% | 4.3 | 1.13 | |
| Continuous | 1.6 | 0.43 | |
| Continuous | 50% | 2.7 | 0.7 |
| Continuous | 100% | 4.3 | 1.13 |