The Power Zone Plus is a generator-set controller. It is used on generator sets from Generac, including the MLT4060, MLT4060KVLED, MLT4060MV and MLT4080KV.
Also fitted to: Generac MLT4060KVLED / MLT4060KV / MLT4060MVLED / MLT4060MV, Generac MLT4080KVLED / MLT4080KV.
| Symptom | Cause | Remedy |
|---|---|---|
| Air Cleaner Element - Clean, Check And Replace | Clean, Check And Replace Air Cleaner Element | |
| Belt And Belt Tension - Inspect And Adjust | Inspect And Adjust Belt And Belt Tension | |
| Blockage in radiator | Inspect radiator shroud and ducting for blockage and remove any foreign matter. | |
| Damaged or loose electrical connections | Check the mast coil cord, mast junction box and mast light connections. | |
| Electrical connections damaged or loose | Check: • Mast coil cord • Mast junction box • Mast light connections | |
| Fuel System - Bleed Air | Bleed Air From Fuel System | |
| Fuel Tank - Drain Water | Drain Water From Fuel Tank | |
| Fuel filter faulty | With engine running and lights off, measure voltage and frequency at the GFCI receptacle. Voltage should indicate 120VAC ± 5%, and frequency should indicate 60.7 Hz ± 5%. If frequency and voltage are both low (<114VAC, <58 Hz), replace the fuel filter. | |
| Generator capacitor faulty | Measure the capacitance of the generator capacitor. If measurement is outside rating (as indicated on the capacitor), replace the capacitor. | |
| Generator output incorrect | Incoming voltage to the ballast is incorrect, Engine speed may need to be adjusted. | Check the incoming voltage to the ballast by checking the available voltage on the GFCI receptacle. Incoming voltage should be 120V +/-5V. |
| High coolant temperature shutdown | Low coolant level | Add coolant if needed. Allow engine to cool, then check coolant level in radiator. Restart engine and check coolant temperature. Stop engine immediately if coolant temperature is 210°F (99°C) or more. |
| Leakage in coolant hoses, engine block, or water pump | Inspect for visible leaks. Verify tension of water pump serpentine drive belt. | |
| Low oil pressure shutdown | Low oil level | Verify oil level on dipstick. Add oil, if needed. |
| Low transformer output | Perform capacitor check to determine if the capacitor or coil needs to be replaced. | |
| Mast Lights OFF and ballast indicators on control panel OFF | Lighting connections loose | Check wire connections: • Inside control box • Inside each ballast box |
| Mast Lights OFF but ballast indicators on control panel ON | Light fixture too hot | Allow light fixture to cool 10-15 minutes before restarting. |
| Mast Lights ON but light output low | Fixture and/or lens is dirty | Clean components: • Reflective surface of light fixture • Inside and outside surface of glass lens IMPORTANT NOTE: Clean components only with mild soap and water. Other chemicals may damage surfaces and glass. |
| Mast Lights Off, and Ballast Indicators on the Control Panel are Off | Generator output incorrect. Low transformer output. | Check the connections inside the control box and inside each ballast box. Check the incoming voltage to the ballast by checking the available voltage on the GFCI receptacle. Incoming voltage should be 120V +/- 5V. If voltage is incorrect, the engine speed may need to be adjusted or generator may require service. |
| Mast Lights Off, but Ballast Indicators on Control Panel are On | Light fixture is too hot | Allow light to cool 10-15 minutes before restarting. |
| Mast Lights On But the Light Output is Low | Fixture and/or lens is dirty | Clean reflective surface inside fixture and both inside and outside surface of glass lens. Use mild soap and water to clean lens. Other chemicals may have an adverse effect on the glass. |
| Mast lights OFF and ballast indicators OFF | Loose lighting connections | Check connections inside control box and inside each ballast box. |
| Mast lights OFF but ballast Indicators ON | Light fixture is too hot, Faulty lamp connection. | Allow light to cool 10-15 minutes before restarting. Check that the lamp is tight in the socket. |
| Mast lights OFF, ballast indicators OFF | Loose lighting connections Generator output incorrect Low transformer output | Check the connections inside the control box and inside each ballast box. Check the incoming voltage to the ballast by checking the available voltage on the GFCI receptacle. Incoming voltage should be 120V ±5V. If voltage is incorrect, the engine speed may need to be adjusted or generator may require service. The voltage from the transformer should read approximately 400VAC as the light “strikes” (induces an arc), then drop and slowly rise back up to stabilize at 240-260VAC. On hard wired models, remove the mast junction box cover and insert the wire probes into the connector blocks for the light and ground. If proper voltage is not achieved, perform capacitor check to determine if the capacitor or coil needs to be replaced. |
| Mast lights OFF, ballast indicators ON | Light fixture is too hot Faulty lamp connection Lamp broken Loose lighting connections Damaged or loose electrical cord | Allow light to cool 10-15 minutes before restarting. Check that the lamp is tight in the socket. Check for broken arc tube or outer lamp jacket, broken or loose components in lamp envelope, or blackening/deposits inside tube. Check the connections inside the mast junction box and each mast light housing/socket. Check the mast electrical cord for damage and check the cord connections inside the control box. |
| Mast lights ON but light output is low | Fixture and/or lens is dirty, Lamp worn due to normal use. | Clean reflective surface inside fixture and both inside and outside surface of glass lens. Replace lamp. |
| Mast lights ON, low light output | Fixture and/or lens is dirty Lamp worn due to normal use Damaged or loose electrical connections Generator output incorrect Low transformer output | Clean reflective surface inside fixture and both inside and outside surface of glass lens. Use mild soap and water to clean lens. Other chemicals may have an adverse effect on the glass. Replace lamp. Check the mast coil cord, mast junction box and mast light connections. Check the incoming voltage to the ballast. Incoming voltage should be 120V ±5V. If the voltage is incorrect, the engine speed may need to be adjusted or the generator may require service. The voltage from the transformer should read approximately 400VAC as the light “strikes” (induces an arc), then drop and slowly rise back up to stabilize at 240-260VAC. On hard wired models, remove the mast junction box cover and insert the wire probes into the connector blocks for the light and ground. If proper voltage is not achieved, perform capacitor check to determine if the capacitor or coil needs to be replaced. |
| Mast lights off, checking inside control box | Lighting connections loose | Check connections inside control box. |
| Mast lights off, checking outside control box | Light fixture too hot | Allow light fixture to cool 10–15 minutes before restarting. |
| Oil leaking from engine | Visually inspect the engine for leaks. | |
| Oil pressure switch failure | Refer to OEM engine operator’s manual to identify corrective action. | |
| Overspeed or Underspeed Shutdown | Frequency setting incorrect | Disconnect all loads and restart unit. Read frequency (Hz) in the LCD window on controller. Frequency should read 60 Hz. If frequency is above 60 Hz, engine speed will need to be adjusted. Refer to the engine operator’s manual for throttle adjustment information. |
| Restricted air filter | Refer to OEM engine operator’s manual for additional information. | |
| Transformer output low | Verify voltage from transformer: When a bulb strikes (induces an arc), transformer voltage should be approximately 400 VAC. Next, voltage should drop, slowly rise, then stabilize at 240–260 VAC. On hard-wired models, remove mast junction box cover and insert wire probes into the connector blocks of the light and ground. If correct voltage is not achieved, check the capacitor to determine if capacitor or coil must be replaced. | |
| Unit cranks but does not start | Fuel level low, Verify fuel pump operation. | Check fuel level in tank. Inspect air filter for blockage. |
| Unit cranks, but will not start | Fuel level low | Check fuel level in tank. Verify fuel pump operation. |
| Water Sedimenter - Drain Water | Drain Water From Water Sediment Separator |
Fault codes and symptom→remedy steps extracted from this controller’s service/owner documentation; verify against the official manual before servicing. Aggregated from the service documentation of generator sets built on this controller.