Home› Troubleshooting›Generac MGG350N2

Generac MGG350N2 Troubleshooting

Generac MGG350N2 troubleshooting: 10 fault codes and 33 symptom-cause-remedy entries from the manufacturer's own service documentation.

Generac MGG350N2 — full specs, parts & maintenance.

All Generac fault codes →

Troubleshooting

43

Fault codes

CodeMeaningCauseRemedy
ECUIndication of error in communication with ECUCheck if the ECU is: correctly connected to the CAN1 port of the controller (refer to Comap Electronic Engines Support manual for information about ECU connection); powered up; terminating resistors are properly connected; the CAN bus Low and High wires are not swapped
SHAinCfgErrShared Analog module configuration errorMore than one source module (SHAOUT) were configured (on the CAN2 bus)Make sure that only one SHAOUT x module is configured in controllers
ECUDiagBlockedAlarm is active when Comms settings: ECU diag = DISABLED. This setting means that ECU alarms are not displayed and considered by controller and this alarm is the setting notification
Wrong configWrong controller configuration indication. Indicates that controller hardware doesn't support PLC used in configurationTo check it send the IDch and Dngl strings from controller Info screen 2 and archive to your technical support
RTCbatteryFlatThis warning message "RTCbatteryFlat" appears in Alarmlist when battery is close to be completely flatIf power supply cut comes when the RTC battery is flat, the statistic values, history and setpoints settings are lostSend a controller to your distributor for battery exchange if the RTCbatteryFlat message is displayed
Al/Hist. msg 1-16Al/Hist. msg 1-16 activity indication (Al/Hist. msg means Alarm/History message)Al/Hist. msg can be used as a customized message for additional protection configured to any controller internal value. See GenConfig manual - Protections
Batt voltIndication of battery voltage protection activityThis protection is based on Analog protect: Batt >V, Batt <V, and Batt volt del setpointsCheck if engine alternator or independent battery charger works properly
EarthFaultCurrIndication of Earth fault current protection activityThis protection is based on Gener protect: EarthFaultCurr and EthFltCurr del setpoints. Setpoint EarthFltCurrCT from Basic settings group of setpoints is related to this protection too
Gen V unbalGenerator voltage unbalance alarmBased on Gener protect: Gen V unbal and Gen V unb del setpoints. The voltage unbalance is calculated as a maximum difference between phase voltages
Gen I unbalGenerator voltage unbalance alarmBased on Gener protect: Gen V unbal and Gen V unb del setpoints

Symptoms & remedies

SymptomCauseRemedy
Engine Cranks But Will Not StartNo fuelCheck that fuel valves are open
Engine Cranks But Will Not StartLow oil levelLow Oil Pressure Shutdown activated. Replenish oil to full
Engine Cranks But Will Not StartRestricted air flowCheck/replace air filter
Engine Cranks But Will Not StartNo sparkCheck/replace spark plug(s)
Engine Will Not Crank (Electric Start)Dead batteryRemove batteries and trickle charge. Never jump start. Even if only one battery is bad, it is recommended that both batteries be replaced at the same time
Engine Will Not Crank (Electric Start)Emergency stop is activatedReset controller after an emergency stop
Engine Starts But Will Not Run SmoothlyFuel or ignition problemRefer to engine manual. Contact Generac Mobile Products Technical Service
Engine OverheatsExcessive loadRemove one or more electrical loads
Engine OverheatsDebris or dirt buildup on engine/radiatorRemove debris. Clean engine surfaces to allow cooling
No Output VoltageCircuit breaker tripped or failedReset circuit breaker or replace if required
No Output VoltageInternal failure of alternatorCheck electrical connections. Contact Generac Mobile Products Technical Service
High Output VoltageExcessive speed (fixed speed mode)Check engine for malfunction. Verify engine RPM
Electrical Shock When Frame Is TouchedStatic chargeGround unit frame at local reference ground
Electrical Shock When Frame Is TouchedGrounded armature or field coilContact service
Mechanical NoiseInternal failure of alternatorContact service
Mechanical NoiseLoose flexplateTighten flexplate to flywheel and alternator shaft
Mechanical NoiseEngine fan or belts issuesContact Generac Power Products Technical Service
Controller Does Not Power Up Even With Correct DC Power AppliedWiring mistakeCheck that there are no wiring errors/short circuits connected to the controller
Controller Does Not Power Up Even With Correct DC Power AppliedOverload conditionCheck breaker on the control panel. Check fuses on control panel
LCD Display Cannot Be ViewedImproper supply voltageCheck DC supply voltage at terminals B+ & B- (10-30VDC)
LCD Display Cannot Be ViewedImproper contrast adjustmentAdjust LCD contrast for best display
Controller Cannot Be "Reset"Engine not stoppedVerify the engine is at a complete stop before trying to reset
Controller Cannot Be "Reset"Controller not in OFF modeSet the controller to the OFF mode before trying to reset
No "RUN" Output Signal"Shutdown Faults" not resetAll shutdown faults must be reset (red shutdown LED must be off)
No "RUN" Output SignalEngine speed not detected at crankingEngine speed signal must be detected (speed signal green LED on) during cranking if the "run-output fail safe" feature is enabled. Verify correct magnetic pickup signal at cranking (2.0VAC min. during cranking)
Overspeed Shutdown Occurs At Normal SpeedController programmed values are wrong or controller has failedVerify the controller programmed values are correct for the number of flywheel teeth, nominal RPM, and overspeed set point percentage. Replace controller if failed
Voltage Or Current Metering Is IncorrectController programmed values are wrongVerify the controller programmed values are correct for the voltage sensing PT ratio and/or current sensing CT ratio
Voltage Or Current Metering Is IncorrectGround is missingVerify that the battery supply DC negative conductor is properly grounded to the engine block (i.e. to a common ground point)
Voltage Or Current Metering Is IncorrectVoltage sensing wiring mistakeVerify the voltage sensing wiring connection to the controller matches power distribution type. NOTE: Standard direct voltage connection requires that the generator's neutral is solidly grounded
Engine Temperature Or Oil Pressure Display Is IncorrectFailed engine sensorVerify engine sensors. NOTE: Engine sensors must be factory supplied units only
Engine Temperature Or Oil Pressure Display Is IncorrectGround is missingVerify that the battery supply DC negative conductor is properly grounded to the engine block (i.e. to a common ground point)
Engine Alarms Are On For High Engine Temperature Or Low Oil Pressure When Engine Is Operating ProperlyWrong temp or pressure calibrationVerify the engine mounted senders have correct resistance values for corresponding input temperature or pressure. Verify calibration
Keypad Buttons (Switches) Do Not OperateKeypad not connected to controllerVerify the interconnecting ribbon cable between the lexan faceplate and main printed circuit board is correctly connected. Replace controller if failed

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.

Cross-brand guides for these symptoms

Common questions

Generac MGG350N2: Engine Cranks But Will Not Start — what causes it?

Documented causes: No fuel; Low oil level; Restricted air flow; No spark. See the table for the matching fixes.

Generac MGG350N2: Mechanical Noise — what causes it?

Documented causes: Internal failure of alternator; Loose flexplate; Engine fan or belts issues. See the table for the matching fixes.

Generac MGG350N2: Voltage Or Current Metering Is Incorrect — what causes it?

Documented causes: Controller programmed values are wrong; Ground is missing; Voltage sensing wiring mistake. See the table for the matching fixes.