Kohler — Verify Paralleling and Load Sharing

Testing & diagnosis · Paralleling system

From a Kohler service manual covering: 125REZGT, 145REOZT4, 175REOZT4, 30REZG, 35 REOZT4, 45 REOZT4, 50REZG, 55REOZT4, 70REZGT, GM88594-KP1-QS, REOZT4. Check it applies to your exact model before use.

Applies to: Kohler 125REZGT, Kohler 145REOZT4, Kohler 175REOZT4, Kohler 30REZG, Kohler 35 REOZT4, Kohler 45 REOZT4, Kohler 50REZG, Kohler 55REOZT4, Kohler 70REZGT

Procedure

  1. Place all generators in automatic mode by pressing the Auto button; verify the red shutdown indicator is not illuminated.
  2. Provide a local start request by holding AUTO, pressing RUN, releasing RUN, then releasing AUTO.
  3. Verify all generators start, one generator closes its contactor, and the others synchronize and close their contactors.
  4. Verify that the % of rated power of the generators matches, showing the generators are sharing load equally.
  5. If a load bank is available, test the system under load.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Full service-parts list: Kohler 125REZGT →, Kohler 145REOZT4 →, Kohler 175REOZT4 →, Kohler 30REZG →, Kohler 35 REOZT4 →, Kohler 45 REOZT4 →, Kohler 50REZG →, Kohler 55REOZT4 →, Kohler 70REZGT →

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.