Kohler — React Droop Compensator Testing
Testing & diagnosis · Reactive droop compensator load sharing
From a Kohler service manual covering: 125REOZJG, 150 REOZJ4, 150REZG, 175REOZT4, 2000REOZM, 2000REOZMD, 2250REOZDD, 275REOZJD, 275REOZJE, 400REZX, 400RZX, 48REOZK4…. Check it applies to your exact model before use.
Applies to: Kohler 125REOZJG, Kohler 150 REOZJ4, Kohler 150REZG, Kohler 175REOZT4, Kohler 2000REOZM, Kohler 2000REOZMD, Kohler 2250REOZDD, Kohler 275REOZJD, Kohler 275REOZJE, Kohler 400REZX, Kohler 400RZX, Kohler 48REOZK4
Procedure
- Parallel the units at 1/2 to full load; verify each unit carries equal kW load or load proportional to capacity using wattmeter readings.
- If load unbalance exists, adjust and recheck the electronic governor throttle control.
- With load balanced, check ammeters for equal current or proportional according to capacity.
- If currents are incorrect, adjust the reactive droop compensator rheostat reducing the current of the unit with the highest reading.
- Stop each generator set by placing Master switch in OFF.