Specifications
| Fuel | natural gas / LP |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 400 kW |
| Standby kVA | 500 |
| Prime power | 360 kW |
| Controller | Decision-Maker 3000 |
| Oil capacity | 47.1 L |
| Alternator | PMG |
| Voltage options | 480 V |
| Phase | 3 |
| Max ambient | 50 °C |
| Sound level | 71.0 dBA @ 23 m |
Engine
| Oil capacity | 47.1 L |
|---|---|
| Coolant capacity | 242.0 L |
| Displacement | 21.9 L |
| Aspiration | Turbocharged, Charge Air-Cooled |
| Rated speed | 1800 rpm |
Maintenance & consumables
for the Doosan D219TIC| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Oil filter | Cartridge | — | |||
| Oil | 47.1 L | — |
Service specifications
30| Type | Item | Value | Unit | Condition |
|---|---|---|---|---|
| Other | 10 in. weld flange bolt circle diameter B | 361.95 | mm (14.25 in.) | |
| Other | 10 in. weld flange outside diameter C | 406.4 | mm (16.0 in.) | |
| Other | 10 in. weld flange quantity of bolts / bolt hole diameter D | 12, 25.40 | mm (1.00 in.) | |
| Other | 12 in. weld flange bolt circle diameter B | 431.80 | mm (17.00 in.) | |
| Other | 12 in. weld flange outside diameter C | 482.6 | mm (19.0 in.) | |
| Other | 12 in. weld flange quantity of bolts / bolt hole diameter D | 12, 25.40 | mm (1.00 in.) | |
| Other | 14 in. weld flange bolt circle diameter B | 476.25 | mm (18.75 in.) | |
| Other | 14 in. weld flange outside diameter C | 533.4 | mm (21.0 in.) | |
| Other | 14 in. weld flange quantity of bolts / bolt hole diameter D | 12, 28.58 | mm (1.13 in.) | |
| Other | 16 in. weld flange bolt circle diameter B | 539.75 | mm (21.25 in.) | |
| Other | 16 in. weld flange outside diameter C | 596.9 | mm (23.5 in.) | |
| Other | 16 in. weld flange quantity of bolts / bolt hole diameter D | 16, 28.58 | mm (1.13 in.) | |
| Other | 18 in. weld flange bolt circle diameter B | 577.85 | mm (22.75 in.) | |
| Other | 18 in. weld flange outside diameter C | 635.0 | mm (25.0 in.) | |
| Other | 18 in. weld flange quantity of bolts / bolt hole diameter D | 16, 31.75 | mm (1.25 in.) | |
| Other | 20 in. weld flange bolt circle diameter B | 635.00 | mm (25.00 in.) | |
| Other | 20 in. weld flange outside diameter C | 698.5 | mm (27.5 in.) | |
| Other | 20 in. weld flange quantity of bolts / bolt hole diameter D | 20, 31.75 | mm (1.25 in.) | |
| Other | 5 in. weld flange bolt circle diameter B | 215.90 | mm (8.50 in.) | |
| Other | 5 in. weld flange outside diameter C | 241.30 | mm (9.50 in.) | |
| Other | 5 in. weld flange quantity of bolts / bolt hole diameter D | 8, 22.23 | mm (0.88 in.) | |
| Other | 6 in. weld flange bolt circle diameter B | 254.0 | mm (10.0 in.) | |
| Other | 6 in. weld flange outside diameter C | 279.4 | mm (11.0 in.) | |
| Other | 6 in. weld flange quantity of bolts / bolt hole diameter D | 8, 22.23 | mm (0.88 in.) | |
| Other | 8 in. weld flange bolt circle diameter B | 298.45 | mm (11.75 in.) | |
| Other | 8 in. weld flange outside diameter C | 342.9 | mm (13.5 in.) | |
| Other | 8 in. weld flange quantity of bolts / bolt hole diameter D | 8, 22.23 | mm (0.88 in.) | |
| Other | Weld flange angle A (10, 12, 14 in. nominal pipe size) | 30 | deg. | |
| Other | Weld flange angle A (16, 18, 20 in. nominal pipe size) | 22.5 | deg. | |
| Other | Weld flange angle A (5, 6, 8 in. nominal pipe size) | 45 | deg. |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Common questions
What size generator is the Kohler 400REZX?
The Kohler 400REZX is rated 400 kW standby (500.0 kVA).
What engine does the Kohler 400REZX use?
The Kohler 400REZX is powered by the Doosan D219TIC engine.
What fuel type does the Kohler 400REZX take?
The Kohler 400REZX runs on natural gas / LP.
What is the oil capacity of the Kohler 400REZX?
The Doosan D219TIC engine in the Kohler 400REZX has an oil capacity of 47.1 liters.
What alternator comes on the Kohler 400REZX?
The Kohler 400REZX uses a PMG alternator.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 25% | 37.7 | 9.96 |
| Prime | 50% | 60.5 | 15.98 |
| Prime | 75% | 85.1 | 22.48 |
| Prime | 100% | 109.2 | 28.85 |
| Standby | 25% | 40.0 | 10.57 |
| Standby | 50% | 65.6 | 17.33 |
| Standby | 75% | 93.4 | 24.67 |
| Standby | 100% | 119.8 | 31.65 |