The Kohler 275REOZJD is a 275 kW standby generator set powered by a John Deere 6090HF484 engine. It is available at 480 V, 3-phase, 60 Hz and rated 330.8 A. It holds about 31 L (8.2 gal) of oil and 53.5 L (14.1 gal) of coolant. Starting uses 1 group-31 battery. The same 6090HF484 engine also powers generator sets from AKSA and MTU.

275 kW
Standby
9.0 L
Displacement
31.0 L
Oil capacity
1
Document types

How to read your Kohler serial & model number →

Service parts for the 275REOZJD

Grouped by system, with how many of each the parts manual calls for.

Fuel system

2 required
GM50263Fuel filter (secondary)$99.99eBay

Oil system

1 required

Prices captured from merchant listings; some links are affiliate links. Confirm against your serial number before ordering.

Specifications

Frequency60.0 Hz
Standby power275 kW
Oil capacity31.0 L
Voltage options480 V
Phase3
Rated current330.8 A
Power factor1
Battery group31group
Battery quantity1

Engine

John Deere 6090HF484
Oil capacity31.0 L
Coolant capacity53.5 L
Displacement9.0 L
AspirationTurbocharged, Charge Air-Cooled
Rated speed1800 rpm

Filters for the John Deere 6090HF484

5

Engine-mounted filters the filter manufacturers list for this engine family. These come from the engine, not from this generator set’s own parts list, so confirm against your serial number before ordering.

SystemFilterDescriptionCross-references
Oil filterP550938Lube Filter, CartridgeJOHN DEERE RE509672, JOHN DEERE RE530656, NAPA 1370, LIEBHERR 11212420 KuduParts $16.00
Fuel filterP550090Fuel Filter, In-LineJOHN DEERE AE20952, JOHN DEERE AT101565, ASV INCORPORATED 0201914, LOESING 025125 FridayParts $45.66
Fuel filterP502392Fuel Filter, BoxJOHN DEERE N378886, BALDWIN BF7912, SEPAR 01030, SEPAR 01030HV FridayParts $39.99
Fuel / water separatorP552952Fuel Filter, Water Separator Spin-OnJOHN DEERE DZ130550, JOHN DEERE RE532952, NAPA 3969, BALDWIN BF9866-O FridayParts $59.99
Fuel / water separatorP551858Fuel Filter, Water Separator Spin-OnJOHN DEERE AT365869, JOHN DEERE RE503676, NAPA 3780, BALDWIN BF1265 FridayParts $39.00 KuduParts $48.00

Same engine, other brands

2 brands

The John Deere 6090HF484 in this set also powers 6 generator sets sold under 2 other brands. Service parts and maintenance intervals for the engine are shared; enclosure, alternator, controller and ratings are not.

BrandModels
MTU6R0150 DS230, 6R0150 DS250, 6R0150 DS275, MTU 6R0150 DS230, MTU 6R0150 DS275
AKSAAPD-ULJ275

Maintenance & consumables

for the John Deere 6090HF484
ItemSpecCapacityPart #Interval
Air filterAir Cleaner Dry—
Fuel filterGM80460 Amazon eBay $93.00 PartsGeek $48.97
Fuel filterSecondaryGM50263 Amazon eBay $99.99
Oil filter11/14/24, 432hrs×1GM48731 Amazon eBay $49.99 NAPA $3.59
BatteryBattery Box and Cables×2—
BeltRadiator - Unit Mounted, Blower Fan and Fan Drive—
Coolant53.5 L—
Oil33.4 L—
Spark plug—

Compatible filters for the John Deere 6090HF484 — cross-referenced via Donaldson. Options to verify against your serial number, not confirmed for this exact unit.

  • Air filter: John Deere RE587794 John Deere 4S00686R John Deere AH115833 John Deere F071151 John Deere F071150

Service specifications

33
TypeItemValueUnitCondition
GapSpeed sensor air gap0.36- 0.71mm
OtherAmperage PH1331Aload bank test, 1 hour
OtherAmperage PH2331Aload bank test, 1 hour
OtherAmperage PH3331Aload bank test, 1 hour
OtherEng Hours342.5hload bank test, 1 hour
OtherKilowatts276kWload bank test, 1 hour
PressureBattery equalizer input voltage (24 volts nominal)20- 35volts
PressureBattery equalizer output voltage(input voltage/2) ±2%volts
PressureOil Pressure45load bank test, 1 hour
PressurePressure switch 364345483 ±14kPa
ResistancePressure sender 264390 value A240 +17/- 15ohms at 0 psi
ResistancePressure sender 264390 value B153 +12/- 15ohms at 25 psi
ResistancePressure sender 264390 value C33.5ohms at 100 psi
ResistancePressure sender 365624 value A241 ±16ohms at 0 psi
ResistancePressure sender 365624 value B152 ±13ohms at 50 psi
ResistancePressure sender 365624 value C33.5ohms at 200 psi
ResistanceTemperature sender 226717 value A123.8 +7.2/- 7.8ohms at 90.6 C (195 F)
ResistanceTemperature sender 226717 value B35.6 +3.4/- 3.6ohms at 137.8 C (280 F)
ResistanceTemperature sender 226919 value A942 ±22ohms at 37.7 C (100 F)
ResistanceTemperature sender 226919 value B35ohms at 115.6 C (240 F)
SpeedHertz/Cycles60Hzload bank test, 1 hour
SpeedOverspeed shutdown70Hz60 Hz models
TemperatureAmbient Temperature47°Fload bank test, 1 hour
TemperatureBattery equalizer operating temperature- 40 to 71C (- 40 F to 160 F)
TemperatureCoolant Temperature180°Fload bank test, 1 hour
TemperatureTemperature switch 241308107 ±4C (225 F ±7 F)normally open to close on temp. rise
TemperatureTemperature switch 290090/GM5170516 ±3C (60 F ±5 F)normally open to close on temp. fall
VoltageDC Voltage28load bank test, 1 hour
VoltageSpeed sensor voltage, wire 2 (black) & 16 (white)3- 6volts DC
VoltageSpeed sensor voltage, wire 2 (black) & 24 (red)8- 10volts DC
VoltageVoltage PH1483Vload bank test, 1 hour
VoltageVoltage PH2483Vload bank test, 1 hour
VoltageVoltage PH3483Vload bank test, 1 hour

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Overfrequency Adjustment (Over/Underfrequency Relay, Decision-Maker 3+) adjustment
  1. Turn the overfrequency adjustment potentiometer fully clockwise (CW).
  2. Place master switch in RUN to start the generator set.
  3. Adjust governor per engine operation manual, engine service manual, or governor section of this manual.
  4. Slowly turn overfrequency potentiometer counterclockwise (CCW) until the LED starts flashing; after about 10 seconds the set shuts down on auxiliary fault.
  5. Place master switch to OFF/RESET to reset the controller.
  6. Place master switch to RUN to start the generator set.
  7. Readjust the governor to the desired frequency as required.
  8. Place master switch to OFF/RESET to stop the generator set.
Overvoltage Feature Testing and Adjustment (Decision-Maker 3+) adjustment

⚠ Hazardous voltage. Moving parts. Will cause severe injury or death. Operate the generator set only when all guards and electrical enclosures are in place.

⚠ Disconnecting the electrical load. Hazardous voltage will cause severe injury or death.

  1. Disconnect generator set from load by opening line circuit breaker or disconnecting and taping output leads.
  2. Determine overvoltage shutdown value based on user requirement; factory setting is 15% above nominal line-to-neutral voltage.
  3. Remove the controller cover.
  4. Place master switch in RUN to start the generator set.
  5. Observe AC voltmeter; turn voltage adjustment potentiometer CW until generator set shuts down.
  6. If the shutdown point is correct, go to step 12; otherwise continue.
  7. Turn controller circuit board R42 adjustment potentiometer fully CW.
  8. Place master switch to OFF/RESET to reset; then to RUN to start.
  9. Observe AC voltmeter while turning voltage adjustment potentiometer to desired overvoltage shutdown point.
  10. Turn R42 adjustment potentiometer slowly CCW until the generator set shuts down.
  11. Turn controller voltage adjustment potentiometer slightly CCW.
  12. Place master switch OFF/RESET then RUN to start; adjust for correct voltage and phase.
  13. Place master switch OFF/RESET to stop.
  14. Disconnect battery negative lead first; reconnect generator set to load; reconnect battery negative lead last.
Reactive Droop Compensator Adjustment Procedure adjustment

Tools: Voltmeter, Wattmeter

  1. Remove any load; start each generator set with master switch in RUN.
  2. Set reactive droop compensator rheostat on generator set no. 1 to minimum CCW; record rpm/frequency and voltage at 1/4 load steps to full load.
  3. Repeat for generator set no. 2.
  4. Compare readings; adjust voltage within 1 volt and speed within 3 rpm (or 0.1 Hz) at each load step.
  5. Check droop compensation on each unit with an inductive load 1/2 to full load.
  6. Adjust rheostat to approximately 4% below rated voltage at full load.
  7. Repeat for unit no. 2.
Reactive Droop Compensator Alternate Adjustment Procedure adjustment

Tools: Voltmeter

  1. Turn reactive droop compensator rheostat on generator set no. 1 to minimum setting.
  2. Remove controller cover; move voltage sensing lead from V7 to V9 at the AC fuse terminal block.
  3. Remove any load connected to the generator set.
  4. Start the generator set with master switch in RUN.
  5. Use controller or remote voltage adjusting potentiometer to fine adjust voltage.
  6. Apply resistive load (1.0 power factor) until reaching rated current.
  7. Adjust reactive droop compensator rheostat to achieve a 4% droop in voltage.
  8. Remove the resistive load and stop the generator set.
  9. Return voltage sensing lead from V9 to V7 at the AC fuse terminal block.
  10. Replace the controller cover and repeat for generator set no. 2.
Underfrequency Adjustment (Over/Underfrequency Relay, Decision-Maker 3+) adjustment
  1. Turn underfrequency adjustment potentiometer fully clockwise (CW).
  2. Place master switch in RUN to start the generator set.
  3. Adjust governor per engine operation manual, engine service manual, or governor section of this manual.
  4. Slowly turn underfrequency potentiometer counterclockwise (CCW) until LED starts flashing; after about 10 seconds the set shuts down on auxiliary fault.
  5. Place master switch to OFF/RESET to reset the controller.
  6. Place master switch to RUN to start the generator set.
  7. Readjust the governor to the desired frequency as required.
  8. Place master switch to OFF/RESET to stop the generator set.
2-Wire Low Water Level Sender Test diagnostic

⚠ Hot engine and exhaust system can cause severe injury or death. Do not work on the generator set until it cools.

⚠ Hazardous voltage. Moving parts. Will cause severe injury or death. Operate the generator set only when all guards and electrical enclosures are in place.

Tools: DC voltmeter

  1. Measure DC voltage between lead 31A (+) and ground (- ) with sender submerged in coolant; voltmeter indicates approximately 12.5 VDC.
  2. Measure DC voltage between lead 31A (+) and ground (- ) with sender removed from coolant for at least 5-15 seconds; voltmeter indicates a drop to approximately 7 VDC.
3-Wire Low Water Level Sender Test diagnostic

⚠ Hot engine and exhaust system can cause severe injury or death. Do not work on the generator set until it cools.

⚠ Hazardous voltage. Moving parts. Will cause severe injury or death.

Tools: Ohmmeter

  1. Measure resistance between lead 31 and ground with sender submerged in coolant; ohmmeter indicates a high resistance reading.
  2. Measure resistance between lead 31 and ground with sender removed from coolant for at least 5-15 seconds; ohmmeter indicates a low resistance reading.
Battery Equalizer Troubleshooting diagnostic

⚠ To prevent reverse polarity damage to the battery equalizer, remove the ground (GND) connection first and attach the ground connection last when disconnecting the battery equalizer.

Tools: 12-volt test light with alligator clips, Voltmeter with 0.01 volt resolution, Battery load tester

  1. Remove the ground (GND) connections from the battery equalizer; do not allow contact with other connections.
  2. Verify a differential of 12 volts between the +12 volt and +24 volt terminals using a 12-volt test light; the light will illuminate on a functional unit. Remove the test light.
  3. Connect the test light between the +12 volt and GND terminals; the light will illuminate on a functional unit.
  4. With the test light connected, measure and record the voltage between the +12 volt and +24 volt terminals.
  5. With the test light connected, measure and record the voltage between the +12 volt and GND terminals.
  6. Remove the test light.
  7. Compare the values from steps 4 and 5; the difference should be - 0.5 and +0.13 volts on a functional unit.
Oil Pressure Sender Testing diagnostic

Tools: Ohmmeter, Mechanical oil pressure gauge

  1. Disconnect the oil pressure sender lead 7C.
  2. Check the sender resistance with an ohmmeter.
  3. Compare resistance values when the generator set is shut down and when running at operating temperature to Section 1, Specifications.
  4. Use a mechanical oil pressure gauge to further verify correct readings.
Overcrank Test (Typical) diagnostic
  1. On gas-fueled sets, disconnect the coil wire at the distributor cap and ground it or disconnect the ignition system.
  2. On diesel-fueled sets, unplug the fuel injector harness from ECM or disconnect wire no. 70 from the injector pump solenoid.
  3. Place unit in RUN mode; observe 15-second on-off cranking cycles and maximum 75-second elapsed time to overcrank shutdown.
  4. Observe controller fault lamp and display for an overcrank shutdown.
  5. Place unit in OFF/RESET mode.
  6. Reconnect the ignition coil wire/ignition system, or reconnect the fuel injector harness/wire no. 70.
Speed Sensor Test with Generator Set Running diagnostic

⚠ Keep leads connected to the speed sensor terminals during the test; do not disconnect the leads.

Tools: DC voltmeter

  1. Connect a DC voltmeter between positive (+) lead (wire 24) at the speed sensor and ground (wire 2) with master switch OFF/RESET; read approximately 8- 12 volts DC.
  2. Place master switch in RUN to start the generator set.
  3. Connect DC voltmeter negative probe to 0 terminal (wire 16 white) and positive probe to positive (+) terminal (wire 24 red); read approximately 7- 12 volts DC.
  4. Place master switch in OFF/RESET to stop the generator set.
  5. If sensor emits a signal, check continuity of speed sensor leads (wires 2, 16, 24) between controller P1 connector and sensor terminals.
Speed Sensor Test with Separate 12 VDC Source diagnostic

Tools: DC voltmeter, 12-volt battery or DC power supply, Flat piece of iron or steel

  1. Place master switch in OFF/RESET position.
  2. Disconnect the speed sensor leads.
  3. Connect speed sensor, DC voltmeter, and DC voltage source as shown.
  4. Touch sensing surface with a flat piece of iron or steel at least 4.1 cm (1/4 cu. in.) in size.
  5. DC voltmeter reading should equal the source voltage, approximately 12 VDC.
  6. Remove the iron or steel piece and observe a voltmeter reading of 0 VDC.
  7. If the sensor passes, it is functional; replace if it fails.
  8. Connect the speed sensor leads and adjust the air gap.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

How many kW is the Kohler 275REOZJD?

The Kohler 275REOZJD is rated 275 kW standby.

What engine is in the Kohler 275REOZJD?

The Kohler 275REOZJD is powered by the John Deere 6090HF484 engine.

How much oil does the Kohler 275REOZJD take?

The John Deere 6090HF484 engine in the Kohler 275REOZJD has an oil capacity of 31.0 liters.

How much coolant does the Kohler 275REOZJD hold?

The Kohler 275REOZJD cooling system holds 53.5 liters (14.1 US gallons) for the engine, per the manufacturer specification sheet.

What voltages is the Kohler 275REOZJD available in?

The Kohler 275REOZJD is offered in 480 V, 3-phase.

How many cold cranking amps does the Kohler 275REOZJD require?

The Kohler 275REOZJD uses 1 battery, group 31group, per the manufacturer specification sheet.

What oil filter does the Kohler 275REOZJD use?

The Kohler 275REOZJD uses oil filter part number GM48731.

What fuel filter does the Kohler 275REOZJD use?

The Kohler 275REOZJD uses fuel filter part numbers GM80460, GM50263.

What air filter does the Kohler 275REOZJD use?

The Kohler 275REOZJD uses air filter part numbers JOHN DEERE RE587794, JOHN DEERE 4S00686R.

Troubleshooting

7

Fault codes

CodeMeaningRemedy
32High Coolant Temperature
32AEmergency StopReset the emergency stop switch.
40Pre High Coolant Temp.
41Pre Low Oil PressureCheck and adjust oil level or replace oil pump.
62Low Battery Volts
63Low FuelRefuel the generator set.
48Emergency Stop

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.

Parts

3
Part #DescriptionQtySystem
4UA1015 Relay I/O Board1Battery Amazon eBay
CB125100-200Coolant heater, 2500W, 120V1Service part / kit eBay
D-292865Battery charger, 120/240V, 5.1/3AService part / kit eBay

Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.

Available documents

Reference — Kohler-275REOZJD-SN-2253997-Load-Test-Report-and-Inspection-Checklist (Csdg)Reference — tp6146 (Kohler)Service manual — TP-6356 (Kohler)Service manual — decision maker tp6356 (Kohler)Service manual — tp6439 (Kohler)

This page was generated from the 5 manufacturer documents above by automated extraction; every figure shown is copied from one of them. How the data is compiled.