Kohler — Overvoltage Feature Testing and Adjustment (Decision-Maker 3+)

Adjustments · Controller main circuit board GM28725 overvoltage feature

From a Kohler service manual covering: 125REOZJG, 150 REOZJ4, 150REZG, 175REOZT4, 2000REOZM, 2000REOZMD, 2250REOZDD, 275REOZJD, 275REOZJE, 400REZX, 400RZX, 48REOZK4…. Check it applies to your exact model before use.

Applies to: Kohler 125REOZJG, Kohler 150 REOZJ4, Kohler 150REZG, Kohler 175REOZT4, Kohler 2000REOZM, Kohler 2000REOZMD, Kohler 2250REOZDD, Kohler 275REOZJD, Kohler 275REOZJE, Kohler 400REZX, Kohler 400RZX, Kohler 48REOZK4

Before you start

  • Hazardous voltage. Moving parts. Will cause severe injury or death. Operate the generator set only when all guards and electrical enclosures are in place.
  • Disconnecting the electrical load. Hazardous voltage will cause severe injury or death.

Procedure

  1. Disconnect generator set from load by opening line circuit breaker or disconnecting and taping output leads.
  2. Determine overvoltage shutdown value based on user requirement; factory setting is 15% above nominal line-to-neutral voltage.
  3. Remove the controller cover.
  4. Place master switch in RUN to start the generator set.
  5. Observe AC voltmeter; turn voltage adjustment potentiometer CW until generator set shuts down.
  6. If the shutdown point is correct, go to step 12; otherwise continue.
  7. Turn controller circuit board R42 adjustment potentiometer fully CW.
  8. Place master switch to OFF/RESET to reset; then to RUN to start.
  9. Observe AC voltmeter while turning voltage adjustment potentiometer to desired overvoltage shutdown point.
  10. Turn R42 adjustment potentiometer slowly CCW until the generator set shuts down.
  11. Turn controller voltage adjustment potentiometer slightly CCW.
  12. Place master switch OFF/RESET then RUN to start; adjust for correct voltage and phase.
  13. Place master switch OFF/RESET to stop.
  14. Disconnect battery negative lead first; reconnect generator set to load; reconnect battery negative lead last.

Specs & values

  • Factory setting 15% above nominal voltage
  • Maximum value about 200 volts

Full service-parts list: Kohler 125REOZJG →, Kohler 150 REOZJ4 →, Kohler 175REOZT4 →, Kohler 2000REOZM →, Kohler 2000REOZMD →, Kohler 2250REOZDD →, Kohler 275REOZJD →, Kohler 275REOZJE →, Kohler 48REOZK4 →

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.