Kohler — Overfrequency Adjustment (Over/Underfrequency Relay, Decision-Maker 3+)
Adjustments
From a Kohler service manual covering: 125REOZJG, 150 REOZJ4, 150REZG, 175REOZT4, 2000REOZM, 2000REOZMD, 2250REOZDD, 275REOZJD, 275REOZJE, 400REZX, 400RZX, 48REOZK4…. Check it applies to your exact model before use.
Applies to: Kohler 125REOZJG, Kohler 150 REOZJ4, Kohler 150REZG, Kohler 175REOZT4, Kohler 2000REOZM, Kohler 2000REOZMD, Kohler 2250REOZDD, Kohler 275REOZJD, Kohler 275REOZJE, Kohler 400REZX, Kohler 400RZX, Kohler 48REOZK4
Procedure
- Turn the overfrequency adjustment potentiometer fully clockwise (CW).
- Place master switch in RUN to start the generator set.
- Adjust governor per engine operation manual, engine service manual, or governor section of this manual.
- Slowly turn overfrequency potentiometer counterclockwise (CCW) until the LED starts flashing; after about 10 seconds the set shuts down on auxiliary fault.
- Place master switch to OFF/RESET to reset the controller.
- Place master switch to RUN to start the generator set.
- Readjust the governor to the desired frequency as required.
- Place master switch to OFF/RESET to stop the generator set.
Specs & values
- Standard overfrequency 63 Hz, FAA 61.5 Hz
Full service-parts list: Kohler 125REOZJG →, Kohler 150 REOZJ4 →, Kohler 175REOZT4 →, Kohler 2000REOZM →, Kohler 2000REOZMD →, Kohler 2250REOZDD →, Kohler 275REOZJD →, Kohler 275REOZJE →, Kohler 48REOZK4 →
Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.