Kohler — Overcrank Test (Typical)
Testing & diagnosis · Controller overcrank fault shutdown protection
From a Kohler service manual covering: 125REOZJG, 150 REOZJ4, 150REZG, 175REOZT4, 2000REOZM, 2000REOZMD, 2250REOZDD, 275REOZJD, 275REOZJE, 400REZX, 400RZX, 48REOZK4…. Check it applies to your exact model before use.
Applies to: Kohler 125REOZJG, Kohler 150 REOZJ4, Kohler 150REZG, Kohler 175REOZT4, Kohler 2000REOZM, Kohler 2000REOZMD, Kohler 2250REOZDD, Kohler 275REOZJD, Kohler 275REOZJE, Kohler 400REZX, Kohler 400RZX, Kohler 48REOZK4
Procedure
- On gas-fueled sets, disconnect the coil wire at the distributor cap and ground it or disconnect the ignition system.
- On diesel-fueled sets, unplug the fuel injector harness from ECM or disconnect wire no. 70 from the injector pump solenoid.
- Place unit in RUN mode; observe 15-second on-off cranking cycles and maximum 75-second elapsed time to overcrank shutdown.
- Observe controller fault lamp and display for an overcrank shutdown.
- Place unit in OFF/RESET mode.
- Reconnect the ignition coil wire/ignition system, or reconnect the fuel injector harness/wire no. 70.
Specs & values
- 15-second on-off cranking cycles
- Maximum 75-second elapsed time to overcrank shutdown