Generac — Return to Service
Maintenance · Generator storage
From a Generac owner's manual — check it applies to your exact model before use.
Applies to: Generac GH-410 engine, Generac GT-530 engine, Generac GT-990 engine, Generac GT-999 engine
Before you start
- Damage may occur if the battery is connected incorrectly.
Procedure
- Verify that utility power is turned off and that the AUTO/OFF/MANUAL switch is set to OFF.
- Check the tag on the engine for oil viscosity and classification.
- Verify that the correct recommended oil is used in the engine.
- Check the state of the battery and recharge or replace as needed.
- Clean and wipe the entire generator.
- Make sure the 7.5A fuse is removed from the generator control panel.
- Reconnect the battery, observing polarity.
- Open the fuel shutoff valve.
- Insert the 7.5A fuse into the generator control panel.
- Start the unit by moving the AUTO/OFF/MANUAL switch to MANUAL and allow it to warm up thoroughly.
- Stop the unit by setting the AUTO/OFF/MANUAL switch to OFF.
- Turn on the utility power to the transfer switch.
- Set the AUTO/OFF/MANUAL switch to AUTO.
Specs & values
- 7.5A fuse
- Recharge battery to 100 percent state of charge
Source: Generac owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.