Generac — Removal From Service (Out of Service Procedure)

Maintenance · generator

From a Generac owner's manual — check it applies to your exact model before use.

Applies to: Generac GH-410 engine, Generac GT-530 engine, Generac GT-990 engine, Generac GT-999 engine

Before you start

  • If generator cannot be exercised every 7 days and will be out of service longer than 90 days, prepare for storage

Procedure

  1. Start engine and let it warm up
  2. Close the fuel shutoff valve and allow unit to shut down
  3. Set Main Circuit Breaker to Off (Open)
  4. Turn off utility power to the transfer switch
  5. Remove the 7.5 Amp fuse from the Control Panel
  6. Disconnect battery cables, negative first
  7. Remove battery charger AC input T1/Neutral cable at controller
  8. While engine is still warm, drain oil completely, then refill crankcase with oil
  9. Attach a tag indicating viscosity/classification of the new oil
  10. Remove spark plug(s), spray fogging agent into threaded openings, reinstall and tighten
  11. Remove battery and store in a cool, dry room on a wooden board
  12. Clean and wipe down the entire generator

Source: Generac owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.