  1. On the generator panel, set the AUTO-OFF-MANUAL switch to OFF.
  2. On the generator, set the main line circuit breaker to its OFF or "Open" position.
  3. Turn OFF the power supply to the transfer switch, using whatever means provided.
  4. Manually actuate the transfer switch main contacts to their "Standby" position.
  5. On the generator panel, set the AUTO-OFF-MANUAL switch to MANUAL. The engine should crank and start.
  6. Let the engine warm up and stabilize for a minute or two at no-load.
  7. Set the generator main line circuit breaker to its "On" or "Closed" position. The generator now powers the electrical loads.