Home›Repair guides›Generac›Manual Transfer to Generator Power Source

Generac — Manual Transfer to Generator Power Source

Operation · transfer_switch

From a Generac owner's manual — check it applies to your exact model before use.

Applies to: Generac GH-410 engine, Generac GT-530 engine, Generac GT-990 engine, Generac GT-999 engine

Before you start

  • Do not activate the transfer switch manually until all power voltage supplies to the switch have been completely turned off

Procedure

  1. Press the Control Panel OFF button
  2. Set the Main Circuit Breaker to OFF (Open)
  3. Turn off utility power supply to the transfer switch
  4. Use the manual transfer handle to move main contacts to STANDBY position
  5. Press the Control Panel MANUAL button to crank and start the engine
  6. Allow engine to stabilize and warm up for a few minutes
  7. Set the Main Circuit Breaker to ON (Closed)

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Source: Generac owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.

More Generac repair guides →