Generac GT-530 — Reconfiguring The Fuel System (10, 12, 14, 16, 17 And 20 kW, V-twin Engines)
Operation
For the Generac GT-530, from the Generac service manual.
Applies to: Generac GH-410 engine, Generac GT-530 engine, Generac GT-990 engine, Generac GT-999 engine
Procedure
- Open the roof.
- For 10 kW units: loosen clamp and slide back the air inlet hose.
- Slide fuel selector on carburetor out towards the back of the enclosure.
- Return the inlet hose and tighten clamp securely.
- For 12, 14, 16, 17 and 20 kW units: remove the air cleaner cover.
- Slide the selector lever out towards the back of the enclosure.
- Return the air cleaner cover and tighten the two thumb screws.
- Close the roof.
- Reverse the procedure to convert back to natural gas.
Specs & values
- Primary regulator for propane supply is NOT INCLUDED with the generator
- LP fuel pressure 10 to 12 inches water column to the fuel inlet must be supplied
Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.