Generac G0070420 — Manual Transfer to Generator Power Source
Operation · Transfer switch
For the Generac G0070420, from the Generac owner's manual.
Applies to: Generac G0070420, Generac GH-426 engine, Generac GTH-530 engine, Generac GT-999 engine
Before you start
- Electrocution. Do not manually transfer under load. Disconnect transfer switch from all power sources prior to manual transfer.
Procedure
- Verify generator is OFF.
- Set the MLCB (generator disconnect) to OFF (OPEN).
- Turn off the utility power supply to the transfer switch.
- Use manual transfer handle to move main contacts to STANDBY.
- Press control panel MANUAL button to crank and start engine.
- Allow engine to stabilize and warm up for a few minutes.
- Set the MLCB (generator disconnect) to ON (CLOSED).
Full service-parts list: Generac G0070420 →
Source: Generac owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.