Generac — Drying the Generator

Maintenance · Stator and Rotor windings

From a Generac service manual covering: IM100G, IM80G, NP100G, NP80G. Check it applies to your exact model before use.

Browse Generac generators & specs →

Before you start

  • No electrical loads must be applied while drying

Procedure

  1. Open the generator's main circuit breaker. NO ELECTRICAL LOADS MUST BE APPLIED TO THE UNIT WHILE DRYING.
  2. Disconnect Wire No. 4 from the Voltage Regulator.
  3. Provide an external source to blow warm, dry air through the generator. DO NOT EXCEED 185° F. (85° C.).
  4. Start the generator and let it run for 2 or 3 hours.
  5. Stop the engine and retest Stator and Rotor insulation for breakdown.

Tools required

  • Megohmmeter or hi-pot tester Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Do not exceed 185° F. (85° C.)

Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.