Home›Repair guides›Generac›Removal From Service

Generac 8.1 GN — Removal From Service

Maintenance · Generator

For the Generac 8.1 GN, from the Generac owner's manual.

Applies to: Generac 8.1 GN, Generac GH-410 engine, Generac GT-530 engine, Generac GT-990 engine, Generac GT-999 engine

Before you start

  • Never store the battery on any concrete or earthen floor.

Procedure

  1. Start the engine and let it warm up.
  2. Close the fuel shutoff valve and allow the unit to shut down.
  3. Set the Main Circuit Breaker to its OFF (OPEN) position.
  4. Turn off the utility power to the transfer switch.
  5. Remove the 7.5 Amp ATO fuse from the Control Panel.
  6. Disconnect the battery cables; remove negative cable first.
  7. Remove battery charger AC input T1/Neutral cable (white sleeve) at controller.
  8. While warm, drain the oil completely, then refill the crankcase with oil.
  9. Attach a tag indicating the viscosity and classification of the new oil.
  10. Remove the spark plug(s) and spray a fogging agent into the threaded openings; reinstall and tighten.
  11. Remove the battery and store it in a cool, dry room on a wooden board.
  12. Clean and wipe down the entire generator.

Specs & values

  • Prepare for storage if out of service longer than 90 days

Full service-parts list: Generac 8.1 GN →

Source: Generac owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.