Cummins/Onan — Testing Exciter Stator

Testing & diagnosis

From a Cummins/Onan service manual — check it applies to your exact model before use.

Applies to: Cummins/Onan MDKC, Cummins/Onan MDKD, Cummins/Onan RGA-OP'

Procedure

  1. Disconnect F1+ and F2- exciter field leads from terminal block in generator end bell.
  2. Measure resistance between field leads with a Wheatstone bridge or digital ohmmeter.
  3. Resistance should be 11.16 to 13.64 ohms at 77°F (25°C).
  4. Apply 500 VDC or more between either field lead and the exciter stator lamination.
  5. Insulation reading should be 1,000,000 ohms or greater.
  6. A shorted stator must be replaced.

Tools required

  • Wheatstone bridge or digital ohmmeter Amazon
  • Megger or insulation resistance meter (500 VDC or more) Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Field lead resistance 11.16 to 13.64 ohms at 77°F (25°C).
  • Ground reading 1,000,000 ohms or greater.

Full service-parts list: Cummins/Onan MDKC →, Cummins/Onan MDKD →, Cummins/Onan RGA-OP' →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.