Cummins/Onan — Solenoid Check

Testing & diagnosis · Start/fuel solenoid

From a Cummins/Onan service manual — check it applies to your exact model before use.

Applies to: Cummins/Onan MDKC, Cummins/Onan MDKD, Cummins/Onan RGA-OP'

Procedure

  1. Apply battery positive (B+) to the terminal marked S.
  2. Connect a ground wire to the solenoid mounting bracket.
  3. Solenoid should activate.
  4. Battery voltage should be read between terminal 1 and ground if contacts good.
  5. Voltage drop across contacts should never exceed one volt.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Voltage drop across contacts never exceed one volt.

Full service-parts list: Cummins/Onan MDKC →, Cummins/Onan MDKD →, Cummins/Onan RGA-OP' →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.