Cummins/Onan C2750 D5 / QSK60 — Stopping at Operator Panel (Manual Mode)
Operation · PowerCommand 3.3 operator panel
For the Cummins/Onan C2750 D5 / QSK60, from the Cummins/Onan operator's manual.
Applies to: Cummins/Onan C2750 D5, Cummins/Onan DQKAN, Cummins/Onan QSK60, Cummins/Onan QSK60 engine, Cummins/Onan QSK60-G19 engine, Cummins/Onan QSK60-G22 engine
Before you start
- Avoid hot shutdown under load to help prolong reliability.
Procedure
- Remove the load.
- Open the main circuit breaker.
- Press the stop button on the HMI operator panel to initiate cool down.
- Once the cool down timer expires, the generator set shuts off and enters Off mode.
Specs & values
- Run the generator set at no load for three to five minutes before stopping
- Pressing the stop button twice stops the set immediately without cool down
Full service-parts list: Cummins/Onan C2750 D5 →, Cummins/Onan DQKAN →, Cummins/Onan QSK60 →
Source: Cummins/Onan operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.