Cummins/Onan C2750 D5 / QSK60 — Stopping at Operator Panel (Manual Mode)

Operation · PowerCommand 3.3 operator panel

For the Cummins/Onan C2750 D5 / QSK60, from the Cummins/Onan operator's manual.

Applies to: Cummins/Onan C2750 D5, Cummins/Onan DQKAN, Cummins/Onan QSK60, Cummins/Onan QSK60 engine, Cummins/Onan QSK60-G19 engine, Cummins/Onan QSK60-G22 engine

Before you start

  • Avoid hot shutdown under load to help prolong reliability.

Procedure

  1. Remove the load.
  2. Open the main circuit breaker.
  3. Press the stop button on the HMI operator panel to initiate cool down.
  4. Once the cool down timer expires, the generator set shuts off and enters Off mode.

Specs & values

  • Run the generator set at no load for three to five minutes before stopping
  • Pressing the stop button twice stops the set immediately without cool down

Full service-parts list: Cummins/Onan C2750 D5 →, Cummins/Onan DQKAN →, Cummins/Onan QSK60 →

Source: Cummins/Onan operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.