Cummins/Onan C2750 D5 / QSK60 — Starting at Operator Panel (Manual Run Mode)
Operation · PowerCommand 3.3 operator panel
For the Cummins/Onan C2750 D5 / QSK60, from the Cummins/Onan operator's manual.
Applies to: Cummins/Onan C2750 D5, Cummins/Onan DQKAN, Cummins/Onan QSK60, Cummins/Onan QSK60 engine, Cummins/Onan QSK60-G19 engine, Cummins/Onan QSK60-G22 engine
Before you start
- Make sure all pre-start checks are carried out before starting.
- Warn all others in the vicinity that the generator set is about to start.
Procedure
- Make sure the main circuit breaker is in the open position.
- Press the Manual button, then press the Start button within ten seconds.
- Allow the engine to warm up and reach rated speed and voltage.
- Close the main circuit breaker and apply load as required.
Specs & values
- Failure to press Start within ten seconds returns the genset to Off mode
- Default: 3 start cycles, 15 seconds cranking and 30 seconds rest
Full service-parts list: Cummins/Onan C2750 D5 →, Cummins/Onan DQKAN →, Cummins/Onan QSK60 →
Source: Cummins/Onan operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.