Cummins/Onan C2750 D5 / QSK60 — Starting at Operator Panel (Manual Run Mode)

Operation · PowerCommand 3.3 operator panel

For the Cummins/Onan C2750 D5 / QSK60, from the Cummins/Onan operator's manual.

Applies to: Cummins/Onan C2750 D5, Cummins/Onan DQKAN, Cummins/Onan QSK60, Cummins/Onan QSK60 engine, Cummins/Onan QSK60-G19 engine, Cummins/Onan QSK60-G22 engine

Before you start

  • Make sure all pre-start checks are carried out before starting.
  • Warn all others in the vicinity that the generator set is about to start.

Procedure

  1. Make sure the main circuit breaker is in the open position.
  2. Press the Manual button, then press the Start button within ten seconds.
  3. Allow the engine to warm up and reach rated speed and voltage.
  4. Close the main circuit breaker and apply load as required.

Specs & values

  • Failure to press Start within ten seconds returns the genset to Off mode
  • Default: 3 start cycles, 15 seconds cranking and 30 seconds rest

Full service-parts list: Cummins/Onan C2750 D5 →, Cummins/Onan DQKAN →, Cummins/Onan QSK60 →

Source: Cummins/Onan operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.