Before you start
- Accidental or remote starting can cause severe personal injury or death.
Procedure
- Press the Off mode switch on the operator panel to shut down the generator set.
- Press the Emergency Stop button to prevent starting from any source.
- Thoroughly ventilate the plant room before disconnecting any leads.
- Isolate and lock off the supply to the heater, where fitted.
- Isolate and lock off the supply to the battery charger, where fitted.
- Isolate the fuel supply to the engine.
- Using an insulated wrench, disconnect the negative (–) battery cable first.
- Fit warning notices to indicate Maintenance in Progress – Plant Immobilized.
Tools required
Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.
Full service-parts list: Cummins/Onan C2750 D5 →, Cummins/Onan DQKAN →, Cummins/Onan QSK60 →