HomeSDMOSDMO R550K

SDMO R550K Generator Set

The SDMO R550K is a 440 kW (550 kVA) DIESEL standby generator set powered by a Volvo Penta TAD1641GE engine. It is available at 415/240 V, 400/230 V, 380/220 V, 240/120 V, 230/115 V, 220/110 V and 200/115 V, 3-phase and 50 Hz. It holds about 48 L (12.7 gal) of oil and 43.8 L (11.6 gal) of coolant. The set measures 5083×1560×2705 mm (200.1×61.4×106.5 in), weighs about 5590 kg (12324 lb) and produces 70 dBA at 7 m. The same TAD1641GE engine also powers generator sets from AKSA, Atlas Copco, Generac, Kohler, Simson-Maxwell and Volvo Penta.

440 kW
Standby
16.12 L
Displacement
48.0 L
Oil capacity
1
Document types

Specifications

FuelDIESEL
Frequency50.0 Hz
Standby power440 kW
Standby kVA550
Prime power400 kW
ControllerMicroprocessor control panel
Oil capacity48.0 L
AlternatorLeroy-Somer LSA472M7
Voltage options415/240 V, 400/230 V, 380/220 V, 240/120 V, 230/115 V, 220/110 V, 200/115 V
Phase3
Power factor0.8
Circuit breaker473 A
Battery voltage12 V
Coolant capacity43.8 L
Dimensions (L×W×H)5083×1560×2705 mm
Dry weight5590 kg
Sound level70.0 dBA @ 7 m

Engine

Volvo Penta TAD1641GE
Oil capacity48.0 L
Coolant capacity60.0 L
Displacement16.12 L
AspirationTurbocharged
Rated speed1800 rpm

Maintenance & consumables

for the Volvo Penta TAD1641GE
ItemSpecCapacityPart #Interval
Air filter30801086201 Amazon eBay $442.95 PartsGeek
Fuel filter330051369 Amazon eBay PartsGeek
Oil filter330050545 Amazon eBay PartsGeek
Belt330051528 Amazon eBay PartsGeek
Coolant30.0 gal330910098 Amazon eBay PartsGeek
Oil48.0 gal330910115 Amazon eBay PartsGeek

Common questions

What is the power rating of the SDMO R550K?

The SDMO R550K is rated 440 kW standby (550.0 kVA).

What engine does the SDMO R550K use?

The SDMO R550K is powered by the Volvo Penta TAD1641GE engine.

What fuel does the SDMO R550K use?

The SDMO R550K runs on DIESEL.

What is the oil capacity of the SDMO R550K?

The Volvo Penta TAD1641GE engine in the SDMO R550K has an oil capacity of 48.0 liters.

What alternator does the SDMO R550K use?

The SDMO R550K uses a Leroy-Somer LSA472M7 alternator.

Troubleshooting

8

Fault codes

CodeMeaning
Oil pressureOil pressure
Water temperatureWater temperature
No start-upNo start-up
OverspeedOverspeed
Min/max alternatorMin/max alternator
Min/max battery voltageMin/max battery voltage
Low fuel levelLow fuel level
Emergency stopEmergency stop

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.

Parts

18
Part #DescriptionQtySystem
7746012Air filter1Air filter PartsGeek
7746022Oil filter1Oil filter PartsGeek
7746032Fuel filter1Fuel filter PartsGeek
GM24832A-NPulse converter circuit boardPump PartsGeek
GM25508Filter, oil1Oil filter Amazon eBay $14.95 PartsGeek
GM25537Filter, fuel1Fuel filter Amazon eBay PartsGeek FridayParts $32.00
GM25540Air filter insert1Air filter Amazon eBay $107.25 PartsGeek
GM25554Fuel filter1Fuel filter Amazon eBay $19.99 PartsGeek
GM26679V-Belt set (fan)Belt PartsGeek
GM29673V-Belt set (alt)Belt PartsGeek
CL130110-200Hotstart Pre heater1Service part / kit PartsGeek
GM25520Decarbonizing kitService part / kit PartsGeek
GM41339Cylinder head (includes items 2--34)1Service part / kit PartsGeek
GM41427Rocker arm shaft (includes item 2)1Service part / kit PartsGeek
GM65855Cylinder head (includes 2--34)1Service part / kit PartsGeek
GM65981Rocker arm shaft1Service part / kit PartsGeek
GM78736Rocker arm6Service part / kit PartsGeek
TAD1641GEService part / kit PartsGeek sinocmp $249.00

Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.

Fuel consumption

RatingLoadL/hgal/h
Prime
Standby

Available documents

Spec sheet — R550K GB